Whitecroft lighting EFL2H14KG Euroflood MidiLED User Manual
- June 1, 2024
- Whitecroft lighting
Table of Contents
Whitecroft lighting EFL2H14KG Euroflood MidiLED
Specifications
- Body: Die-cast aluminium
- Diffuser: Tempered glass
- Paint Finish: UV. ISO 9227
- Power: 220-240V / 50-60Hz
Product Usage Instructions
General Information
- A qualified electrician, following IEE wiring regulations, should handle mains wiring connections.
- Always turn off mains power during maintenance.
- Ensure the rated voltage and frequency match the available mains supply.
- Clean reflectors and lenses with soft, lint-free cloths and anti-static cleaning fluid.
- Avoid high voltage insulation tests as they may damage internal components.
- For LED version: Class 2 insulated, no earth connection needed. Metal halide version: Class 1 insulated, must be earthed.
- Some outdoor luminaires may accumulate condensation due to temperature differences; this is acceptable under BSEN60598.
- Only the manufacturer, service agent, or qualified individual should replace the light source.
LED Installation Sequence
All measurements in mm unless stated otherwise.
- Remove the fitting from packaging.
- Bolt the luminaire to a suitable strong surface.
- Aim using main pivot bolt and fixing screw.
- Fix Live / Neutral conductors to power connector using securing screws.
- Plug power connector into the socket at the bottom of the luminaire.
- Use accessory EFLBKT76 and EFLWG as needed for installation.
FAQ
-
Q: Can I carry out high voltage insulation tests on this product?
A: No, high voltage insulation tests should not be performed as they may damage internal components. -
Q: Is an earth connection required for the LED version of the product?
A: No, the LED version is Class 2 insulated and does not require an earth connection.
Euroflood MidiLED
Installation Leaflet
SPECIFICATION
- Light Source Type: LED
- Light Source Colour: 4000°K Ra 80 LED
- Control Gear: Fixed output
- Rating: IP66 / IK08
- Product Colour: Graphite Grey
- Body: Die-cast aluminium
- Diffuser: Tempered glass
- Paint Finish: UV. ISO 9227
- Power: 220-240V / 50-60Hz
Description | Lumen Output | Circuit Watts | Weight (Kg) |
---|---|---|---|
EFL2H14KG | 9679 | 53 | 5.985 |
EFL2H24KG | 12968 | 79 | 5.985 |
EFL2H34KG | 18934 | 118 | 6.17 |
EFL2H44KG | 15595 | 169 | 6.3 |
EFL2H54KG | 30081 | 211 | 8.125 |
EFL2H64KG | 40107 | 269 | 9.265 |
Replace ‘H’ with ‘Y’ for DALI | Add /SP at end for Swimming Pool Version* |
GENERAL INFORMATION
- A qualified electrician, in accordance with IEE wiring regulations, should carry out connection to mains wiring.
- Ensure mains power is turned off during maintenance.
- Ensure that the rated voltage and frequency requirements are compatible with the available mains supply.
- Cleaning of reflectors and lenses should be carried out using clean, soft and lint free cloths and anti-static cleaning fluid.
- Do not carry out high voltage insulation test, i.e. 500/1000v this may damage internal components.
- LED version: Class 2 insulated and so does not require an earth connection. Conventional metal halide version: Class 1 insulated and must be earthed.
- Some luminaires installed in outdoor environments may experience a build-up of internal condensation. This is due to a difference in temperature between inside and outside the luminaire which is quite common and acceptable under BSEN60598.
- Replacing the light source within this luminaire shall only be carried out by the manufacturer, service agent or a similar qualified person.
LED INSTALLATION SEQUENCE
All measurements in mm unless stated otherwise
The LED version is class 2 insulated and does not require an earth connection.
Remove the fitting from all of the packaging.
- Luminaire to be bolted to a suitable surface strong enough to take the loads applied (Point 1).
- Point of aiming (Point 2) to be done via main pivot bolt (Point 3) and fixing screw (Point 4)
- Fix the Live / Neutral conductors of the 2 core supply flex to the power connector using the securing screws (Point 5).
- Plug the power connector in the socket located at the bottom of the luminaire. (Point 6).
- Accessory EFLBKT76. Use the two bolts supplied to fix the luminaire to the pole attachment. Clamp the attachment to the pole using the rear allen bolt.
- Accessory EFLWG. Attach the wire guard to the front of the luminaire using the four screws supplied.
Please note : All images shown are for illustration purposes and should be used as a refer-ence guide only
| A.| B.
---|---|---
EFL2H14KG| 0.112m²| 0.030m²
EFL2H24KG| 0.112m²| 0.030m²
EFL2H34KG| 0.142m²| 0.037m²
EFL2H44KG| 0.142m²| 0.037m²
EFL2H54KG| 0.153m²| 0.046m²
EFL2H64KG| 0.153m²| 0.046m²
TECHNICAL SUPPORT
- Tel: 0161 331 5700
- e-mail: technical@whitecroftlight.com
- www.whitecroftlighting.com
Whitecroft Lighting Limited
- Burlington Street, Ashton-under-Lyne, Lancashire OL7 0AX
- Telephone +44 (0)870 5 087 087
- Facsimile: +44 (0)870 5 084 210
- Registered No. 3848973 England
- Registered Office: As above
References