Specifications

  • Lamp type: LED
  • Finish: RAL 9003 (White)
  • Materials: Mild Steel
  • Weight: Recessed Max = 1.5kg, Surface Max = 1.9kg
  • Supply: 220-240V AC, 50/60Hz
  • Operating temp: 0-30°C
  • Connection: Recessed: 6-pole Wieland plug
  • Ingress protection: IP20

Product Usage Instructions

Installation Instructions

  1. Remove the product from the packaging and check for any damage.
  2. Wire the 6-pole female plug to the incoming supply as shown in Fig. 1.
  3. Bring the female plug through the cut aperture and connect it to the male plug attached to the product.
  4. Connect the battery and Florin LED head and fill in the commissioning date on the label.
  5. Feed the gear tray through the aperture and rest it on the back of the ceiling. Use the included fixing points to secure the gear tray to the hard ceiling.
  6. Insert the fascia plate using the springs. Bend both springs simultaneously before fitting them into the aperture. Be cautious, especially with thin or soft ceilings. Once the springs are sufficiently through the aperture, the fitting will be pulled through rapidly.
  7. If your product has an escape route/corridor lens, it may need to be rotated in the ceiling. Refer to the Florin Setup on the back page for guidance.

RECESSED MOUNT

RECESSED MOUNT – PREPARATION
A Ø115 +/- 1mm hole should be cut in the ceiling before installation. This product is suitable for ceiling thicknesses of 10-25mm. Where installing into thin or soft ceiling tiles, an additional pattress may be required. This should be a support panel, to be fitted behind the ceiling, cut from suitable sheet material with a hole drilled to match the luminaire cut aperture. The minimum ceiling void is 175mm based on 10mm ceiling tile. The gear tray has holes for secondary suspension which should be used to retain it during installation or when removing.

Whitecroft Lighting Limited

Part Codes

  • FLE31/RG3
  • FLE32/RG3
  • FLH31/RG3

Care should be taken during installation and removal as the springs are under a lot of tension when loaded.
Gloves should be worn at all times.
Do not connect batteries until there is a reliable permanent mains supply present as a mains interruption will reset the commissioning test clock.

INSTALL

  1. Remove the product from the packaging and check for damage.
  2. Wire 6-pole female plug to incoming supply (Fig.1).
  3. Bring the female plug through the cut aperture and connect it to the male plug attached to the product.
  4. Connect the battery and Florin LED head and fill in the commissioning date on the label.
  5. Feed the gear tray through the aperture and rest on the back of the ceiling. Fixing points have been included to secure the gear tray to the hard ceiling i.e. via safety cables.
  6. Insert fascia plate using springs. Bend both springs at the same time before fitting into the aperture. Be careful, especially on thin or soft ceilings. When springs are sufficiently through the aperture the fitting will be pulled through rapidly.
  7. FLE32/RG3 has an escape route/corridor lens so fitting may have to be rotated in the ceiling. See Florin Setup on the back page.

Whitecroft-lighting-FLORIN-E3-High-Performance-Emergency-Light-
fig-3

SURFACE MOUNT – PREPARATION

Product is not suitable for conduit mounting. Side entry should be via a hard cable gland.

Whitecroft Lighting Limited

Part Codes:

  • FLSE31/RG3
  • FLSE32/RG3
  • FLSH31/RG3

Whitecroft-lighting-FLORIN-E3-High-Performance-Emergency-Light-
fig-4

  1. Remove the product from the packaging and check for damage.
  2. Remove the ceiling bracket from the gearbox via M5 screws and detaching safety cords and earth.
  3. Screw the ceiling bracket to the surface using appropriate fixings – supplied by others. Please note that FLSH31/RG3 has an escape route/corridor lens so the fitting should be orientated with a long edge parallel to a corridor or escape route. See Florin Setup on the back page.
  4. Attach safety cords.
  5. Attach earth lead from the gearbox to the ceiling bracket.
  6. Bring incoming supply through cable entry points on the side or top and wire into a terminal block (Fig. 2) using strain relief clamps to secure flex.
  7. Re-attach the gearbox to the ceiling bracket ensuring all cables are tucked inside.

SPECIFICATION

  • Lamp type LED
  • Finish RAL 9003(White)
  • Materials Mild Steel
  • Weight Recessed Max = 1.5kg
  • Surface Max = 1.9kg. Supply 220-240V AC, 50/60Hz
  • Operating temp 0-30Cv
  • Connection Recessed: 6-pole Wieland plug
  • Surface: Piano key terminal block max 2.5mm² cable
  • Ingress protection IP20

Please note: These luminaires are part of a lighting control system that requires both additional equipment as well as programming. The maximum distance between fittings or a 2.4GHz low-energy gateway is 8 metres. For full details, please contact Whitecroft technical support.

FLORIN EMERGENCY LED TEST
DALI /Self-test luminaire local bi-colour LED indicator status

Whitecroft-lighting-FLORIN-E3-High-Performance-Emergency-Light-
fig-1

Slow flash – a flash every 2 seconds, Fast flash – a flash every 0.5 seconds.
Note that the start times of the tests are set automatically to ensure random testing of the units. As a consequence, tests may occur at any time, and caution should be exercised in situations where this may be inconvenient, such as hotels and hospitals.

FLORIN EMERGENCY LED ORIENTATION
For best photometric performance ensure that the long axis of the escape route lens is in line (parallel) with the path of the escape route as shown above.

Whitecroft-lighting-FLORIN-E3-High-Performance-Emergency-Light-
fig-2

GENERAL INFORMATION

  1. A qualified electrician, by IET wiring regulations, should carry out connection to mains wiring.
  2. Observe ESD precautions during installation.
  3. This surface mount unit must be EARTHED. The recessed fitting does not require an earth.
  4. Ensure that the rated voltage and frequency requirements are compatible with the available mains supply.
  5. Cleaning of reflectors and lenses should be carried out using clean, soft and lint-free cloths and anti-static cleaning fluid.
  6. Do not carry out high voltage insulation test, i.e. 500/1000v this may damage internal components.
  7. The light source contained in the luminaire shall only be replaced by the manufacturer, their service agent or a similarly qualified person.
  8. Batteries must only be replaced by a qualified electrician once they fail to meet the required duration.
  9. The luminaire must be isolated before commencing any necessary maintenance work or battery connection.

TECHNICAL SUPPORT

Whitecroft Lighting Limited

  • Burlington Street, Ashton-under-Lyne, Lancashire OL7 0AX
  • Telephone +44 (0)161 330 6811
  • Facsimile: +44 (0)161 331 5855
  • Registered No. 3848973 England
  • Registered Office: As above

FAQ

  • Q: Are batteries required for this product?
    • A: Yes, batteries need to be connected, but only when there is a reliable permanent mains supply present to avoid resetting the commissioning test clock.
  • Q: What is the maximum distance between fittings?
    • A: The maximum distance between fittings is 8 meters when using a 2.4GHz low-energy gateway for full support details.
  • Q: What is the operating temperature range of the product?
    • A: The operating temperature range is from 0 to 30 degrees Celsius.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Whitecroft lighting User Manuals

Related Manuals