Danfoss MCD 600 Remote VLT Control Panel VLT Soft Starter Installation Guide

June 1, 2024
Danfoss

Danfoss MCD 600 Remote VLT Control Panel VLT Soft Starter

Danfoss MCD 600 Remote VLT Control Panel VLT Soft Starter

Overview

Description

The remote VLT® Control Panel LCP 601 can be mounted up to 3 m (9.8 ft) away from the soft starter. The LCP is rated IP65 when mounted correctly in accordance with these instructions.
The LCP connects to the soft starter via the DB9 connector on a hardware expansion card. A hardware expansion card must be installed to use the remote LCP with the soft starter. Separate kits are available with a dedicated LCP connector expansion card, or with no expansion card for applications already using another smart card.

Parts List

Item Quantity
Remote VLT® Control Panel LCP 601 1
LCP connector expansion card (selected kits) 1
Cable, DB9 1
Gasket, foam 1
Installation guide 1
M3 x 16 screw 4
M3 flat washer 4
M3 spring washer 4
M3 nut 4
Jack screw 4

Table 1: Ordering Numbers

Kit Ordering number
Remote VLT® Control Panel LCP 601 and Mounting Kit 175G0134

Installation

Installing the Expansion Card

Context:

Symbols SHOCK HAZARD
The soft starter contains dangerous voltages when connected to mains voltage. Attaching or removing accessories when the soft starter is connected to mains may cause death or serious injury.

  • Isolate the soft starter from mains voltage before attaching or removing accessories.

Symbols RISK OF INJURY   AND EQUIPMENT DAMAGE
Inserting foreign objects or touching the inside the soft starter while the expansion port cover is open may endanger personnel, and can damage the soft starter.

  • Be careful when installing the expansion cards and make sure not to touch the inside the soft starter.

Procedure

  1. Push a small flat-bladed screwdriver into the slot in the center of the expansion port cover and ease the cover away from the soft starter.
    Installation

  2. Line up the card with the expansion port. Gently push the card along the guide rails until it clicks into the soft starter.
    Installation

Installing the Remote VLT® Control Panel LCP 601

Symbols The remote VLT® Control Panel LCP 601 can be safely connected or removed while the soft starter is running. It is not necessary to remove mains or control voltage.

Procedure

  1. Measure and drill 4 holes for the mounting screws and 2 holes for the DB9 connector, see 2.4 Mounting Diagram.

  2. Apply the foam gasket to the back of the LCP.

  3. Align the LCP over the holes and screw in place. Tighten the screws so that the foam gasket is compressed to half its original thickness (torque approximately 1 Nm (8.8 in-lb)).
    Symbols If the screws are too long, the gasket does not provide IP65 protection. Overtightening the screws can damage the LCP, gasket, or panel.

  4. Plug the cable into the LCP and the soft starter.
    Installation

  5. Press the faceplate onto the front of the LCP.

Control via the Remote VLT® Control Panel LCP 601

The soft starter only accepts start and reset commands from the remote VLT® Control Panel LCP 601 if parameter 1A Command Source is set to Remote Keypad.

Illustration 1: Remote LCP

1 Four-line display for status and programming details.
2 Status LEDs.
3 Menu navigation keys:
parameter change. Menu/Store: Enter a menu or parameter, or save a
parameter change. Arrow keys: Scroll to the next or previous menu or

parameter, change the setting of the current parameter, or scroll through the status screens.
4| Shortcut to the command source menu in Set-up Tools.
5| Local control keys.
6| Shortcut keys for quick access to common tasks:| Logs: Open the Logs Menu.| Graph: Select which graph to view, or pause/ restart the graph (hold longer than 0.5 s).| Tools: Open the Set-up Tools.

Installation

Symbols If the commissioning menu is open on the built-in LCP, the soft starter ignores all commands from the remote LCP except stop commands.

Symbols The remote LCP can be safely connected or removed while the soft starter is running. It is not necessary to remove mains or control voltage.

Symbols If parameter 1A Command Source is set to Remote LCP, removing the remote LCP causes a trip.

Mounting Diagram

Drill 4 mounting holes for screws (1 in each corner) and 2 holes for the DB9 connector.

Symbols The image is not to scale. Dimensions are given with the faceplate removed.

Dimensions

Illustration 2: Drilling Template

Dimensions

Exploded View

Illustration 3: Exploded View

1 Faceplate
2 Screw
3 Jack screw
4 Flat washer
5 Spring washer
6 Nut
7 VLT® Control Panel LCP 601
8 Gasket
9 Panel
10 Cable

Exploded View

Customer Support

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without sub sequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S Ulsnaes 1 DK-6300 Graasten
vlt-drives.danfoss.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals