Danfoss AB-QM DN 40-100 Pressure Independent Control Valves Installation Guide
- October 27, 2023
- Danfoss
Table of Contents
Danfoss AB-QM DN 40-100 Pressure Independent Control Valves
Overview
Installation
Shut off
Setting
Resetting
DN 40-100
Locking
DN 40/50
DN 65-100
Measuring
DN 40 | L/h | L/s | GPM |
---|---|---|---|
20% | 1,500 | 0.416 | 6.6 |
25% | 1,875 | 0.520 | 8.3 |
30% | 2,250 | 0.625 | 9.9 |
35% | 2,625 | 0.729 | 11.6 |
40% | 3,000 | 0.833 | 13.2 |
45% | 3,375 | 0.937 | 14.9 |
50% | 3,750 | 1.041 | 16.5 |
55% | 4,125 | 1.145 | 18.2 |
60% | 4,500 | 1.250 | 19.8 |
65% | 4,875 | 1.354 | 21.5 |
70% | 5,250 | 1.458 | 23.1 |
75% | 5625 | 1.562 | 24.8 |
80% | 6,000 | 1.666 | 26.4 |
85% | 6,375 | 1.770 | 28.1 |
90% | 6,750 | 1.875 | 29.7 |
95% | 7,125 | 1.979 | 31.4 |
100% | 7,500 | 2.083 | 33.0 |
DN 50 | L/h | L/s | GPM |
--- | --- | --- | --- |
40% | 5,000 | 1.386 | 22.0 |
45% | 5,625 | 1.562 | 24.8 |
50% | 6,250 | 1.736 | 27.5 |
55% | 6,875 | 1.909 | 30.3 |
60% | 7,500 | 2.083 | 33.0 |
65% | 8,125 | 2.256 | 35.8 |
70% | 8,750 | 2.430 | 38.50 |
75% | 9,375 | 2.604 | 41.3 |
80% | 10,000 | 2.777 | 44.0 |
85% | 10,625 | 2.951 | 46.8 |
90% | 11,250 | 3.125 | 49.5 |
95% | 11,875 | 3.298 | 52.3 |
100% | 12,500 | 3.472 | 55.0 |
DN 65 | Flow | High Flow | |
--- | --- | --- | |
L/h | L/s | GPM | L/h |
40% | 8,000 | 2.22 | 35.2 |
45% | 9,000 | 2.50 | 39.6 |
50% | 10,000 | 2.78 | 44.0 |
55% | 11,000 | 3.06 | 48.4 |
60% | 12,000 | 3.33 | 52.8 |
65% | 13,000 | 3.61 | 57.2 |
70% | 14,000 | 3.89 | 61.6 |
75% | 15,000 | 4.17 | 66.0 |
80% | 16,000 | 4.44 | 70.4 |
85% | 17,000 | 4.72 | 74.9 |
90% | 18,000 | 5.00 | 79.3 |
95% | 19,000 | 5.28 | 83.7 |
100% | 20,000 | 5.56 | 88.1 |
Note: 1 turn = 10%
DN 80 | Flow | High Flow |
---|---|---|
L/h | L/s | GPM |
40% | 11,200 | 3.11 |
45% | 12,600 | 3.50 |
50% | 14,000 | 3.89 |
55% | 15,400 | 4.23 |
60% | 16,800 | 4.67 |
65% | 18,200 | 5.10 |
70% | 19,600 | 5.44 |
75% | 21,000 | 5.83 |
80% | 22,400 | 6.22 |
85% | 23,800 | 6.61 |
90% | 25,200 | 7.00 |
95% | 26,600 | 7.39 |
100% | 28,000 | 7.78 |
Note: 1 turn = 10%
DN 100 | Flow | High Flow |
---|---|---|
L/h | L/s | GPM |
40% | 15,200 | 4.22 |
45% | 17,100 | 4.75 |
50% | 19,000 | 5.28 |
55% | 20,900 | 5.81 |
60% | 22,800 | 6.33 |
65% | 24,700 | 6.86 |
70% | 26,600 | 7.39 |
75% | 28,500 | 7.92 |
80% | 30,400 | 8.44 |
85% | 32,300 | 8.97 |
90% | 34,200 | 9.50 |
95% | 36,100 | 10.03 |
100% | 38,000 | 10.56 |
Note: 1 turn = 10%
Danfoss A/S
Climate Solutions danfoss.com +45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogs descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative and is
only binding if and to the extent, explicit reference is made in a quotation
or order confirmation. Danfoss cannot accept any responsibility for possible
errors in catalogs, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
AlI trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
Read User Manual Online (PDF format)