Danfoss USV-I Balancing Valve User Guide
- October 27, 2023
- Danfoss
Table of Contents
USV-I Balancing Valve
User Guide
USV-I Balancing Valve
USV-I / USV-M
Presetting valve USV-I is used together with shut-off upgradeable valve USV-M to balance the flow in heating installations. After upgrading with PV controller, USV-M becomes an automatic balancing valve.
Function
USV-I gives maximum limitation of water flow and the riser can be shut off by
turning the knob fully clockwise.
USV-M can shut-off the riser by turning the knob fully clockwise.
USV-M (after upgrading to USV-PV) regulates together with USV-I the
differential pressure and flow across the riser to the preset value.
Data
Max. working pressure…………………………………16 bar
Max. differential pressure across the valve ………………………… 80 kPa
Max. flow temperature ………………………………..120 °C
Max. test pressure …………………………………………25 bar
Installation
USV-I must be installed in the flow pipe and USV-M must be installed in the
return pipe. The direction of the flow must be according to the arrow on the
valve body.It is recommended that an FV-filter is installed in the supply
pipe.
The valve must in addition be installed as determined by installation
conditions.
Measurment of flow
Measuring connector (accessory) can be fitted to the drain connection, and the differential pressure and flow across the valve can be measured using ordinary equipment, by doing the following:
- When the quick couplings on the measuring instrument are connected, turn the test plug one turn counterclockwise and open the drain connection
- Using the graph ❺ the actual definitely pressure across the valve can be converted to actual flow.
- Close the test plug and drain connection again, before removing the quick couplings.
Note: When measuring sized flow, all radiator valves mus be fully open.
Setting
To preset the valve:
- Turn the valve knob to the required setting ❻.
- Hold the knob to keep the setting, use a hexagon socket key to turn the spindle fully counterclockwise (until a stop can be felt) ➐.
- Turn the valve knob fully counter clock-wise, so that the mark on the knob is opposite “0” on the scale ❽. The valve is now open as many turns as required.
Resetting
To reset the setting, hold the knob and turn the spindle fully clockwise
(until a stop can be felt) ❾.
Check the setting
Close the valve by turning the valve knob fully clockwise and read the setting
on the scale ❻.
Fault location
Check the following if the riser valve does not function correctly:
- Is the flow direction through the valve correct?
- Is the USV-I valve open?
Insulation
The stropper packaging (accessories) can be used as an insulation jacket for temperature up to 120 °C.
Valve size | Internal thread | External thread |
---|---|---|
DN 15 | Rp 1/2 | G 3/4 A |
DN 20 | Rp 3/4 | G 1 A |
DN 25 | Rp 1 | G 1 1/4 A |
DN 32 | Rp 1 1/4 | G 1 1/2 A |
DN 40 | Rp 1 1/2 | G 1 3/4 A |
DN 50 | Rp 2 | G 2 1/4 A |
Danfoss A/S
Climate Solutions
- danfoss.com
- +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
© Danfoss I DCS-S/SI 12021.09
73693450 / AQ14688646059103-010601
References
- Engineering Tomorrow | Danfoss
- 丹佛斯 | Danfoss
- Danfoss - Engineering Tomorrow | Danfoss
- Danfoss Deutschland | Klima | Kälte | Heizung | Antriebe | Hydraulik | Danfoss
- Danfoss | Danfoss
- Danfoss Italia | Soluzioni innovative e digitali per l'efficienza energetica industriale e residenziale | Danfoss
- Danfoss – Engineering Tomorrow | Danfoss
- Engineering Tomorrow | Danfoss
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>