Danfoss AB-QM DN 10-32 Pressure Independent Balancing Installation Guide
- October 27, 2023
- Danfoss
Table of Contents
Danfoss AB-QM DN 10-32 Pressure Independent Balancing
OVERVIEW
Installation
Shut off
Setting
Locking
Measuring
DN 10 | Low Flow | Normal Flow |
---|---|---|
L/h | L/s | GPM |
20% | 30 | 0.008 |
25% | 38 | 0.010 |
30% | 45 | 0.013 |
35% | 53 | 0.015 |
40% | 60 | 0.017 |
45% | 68 | 0.019 |
50% | 75 | 0.021 |
55% | 83 | 0.023 |
60% | 90 | 0.025 |
65% | 98 | 0.027 |
70% | 105 | 0.029 |
75% | 113 | 0.031 |
80% | 120 | 0.033 |
85% | 128 | 0.035 |
90% | 135 | 0.038 |
95% | 143 | 0.040 |
100% | 150 | 0.042 |
105% | 158 | 0.044 |
110% | 165 | 0.046 |
115% | 173 | 0.048 |
120% | 180 | 0.050 |
DN 15 | Low Flow | Normal Flow |
--- | --- | --- |
L/h | L/s | GPM |
20% | 55 | 0,015 |
25% | 69 | 0,019 |
30% | 83 | 0,023 |
35% | 96 | 0,027 |
40% | 110 | 0,031 |
45% | 124 | 0,034 |
50% | 138 | 0,038 |
55% | 151 | 0,042 |
60% | 165 | 0,046 |
65% | 179 | 0,050 |
70% | 193 | 0,053 |
75% | 206 | 0,057 |
80% | 220 | 0,061 |
85% | 234 | 0,065 |
90% | 248 | 0,069 |
95% | 261 | 0,073 |
100% | 275 | 0,076 |
105% | 289 | 0,080 |
110% | 303 | 0,084 |
115% | 316 | 0,088 |
120% | 330 | 0,092 |
DN 20 | Normal Flow | High Flow |
--- | --- | --- |
L/h | L/s | GPM |
20% | 180 | 0.050 |
25% | 225 | 0.063 |
30% | 270 | 0.075 |
35% | 315 | 0.088 |
40% | 360 | 0.100 |
45% | 405 | 0.113 |
50% | 450 | 0.125 |
55% | 495 | 0.138 |
60% | 540 | 0.150 |
65% | 585 | 0.163 |
70% | 630 | 0.175 |
75% | 675 | 0.188 |
80% | 720 | 0.200 |
85% | 765 | 0.213 |
90% | 810 | 0.225 |
95% | 855 | 0.238 |
100% | 900 | 0.250 |
105% | 945 | 0.263 |
110% | 990 | 0.275 |
115% | 1035 | 0.288 |
120% | 1080 | 0.300 |
DN 25 | Normal Flow | High Flow |
--- | --- | --- |
L/h | L/s | GPM |
20% | 340 | 0.094 |
25% | 425 | 0.118 |
30% | 510 | 0.142 |
35% | 595 | 0.165 |
40% | 680 | 0.189 |
45% | 765 | 0.213 |
50% | 850 | 0.236 |
55% | 935 | 0.260 |
60% | 1020 | 0.283 |
65% | 1105 | 0.307 |
70% | 1190 | 0.331 |
75% | 1275 | 0.354 |
80% | 1360 | 0.378 |
85% | 1445 | 0.401 |
90% | 1530 | 0.425 |
95% | 1615 | 0.449 |
100% | 1700 | 0.472 |
105% | 1785 | 0.496 |
110% | 1870 | 0.519 |
DN 32 | Normal Flow | High Flow |
--- | --- | --- |
L/h | L/s | GPM |
20% | 640 | 0.178 |
25% | 800 | 0.222 |
30% | 960 | 0.267 |
35% | 1120 | 0.311 |
40% | 1280 | 0.356 |
45% | 1440 | 0.400 |
50% | 1600 | 0.444 |
55% | 1760 | 0.489 |
60% | 1920 | 0.533 |
65% | 2080 | 0.578 |
70% | 2240 | 0.622 |
75% | 2400 | 0.667 |
80% | 2560 | 0.711 |
85% | 2720 | 0.756 |
90% | 2880 | 0.800 |
95% | 3040 | 0.844 |
100% | 3200 | 0.889 |
105% | 3360 | 0.933 |
110% | 3520 | 0.978 |
Danfoss A/S
Climate Solutions danfoss.com.+45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals,catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
Read User Manual Online (PDF format)