Danfoss AK-PS 130 Power Supply Installation Guide

June 1, 2024
Danfoss

Danfoss AK-PS 130 Power Supply

Specifications

  • Product Name: Power supply Type AK-PS 130
  • Model Number : 080R9354 AN44283959533901-000101
  • Dimensions : 150mm x 90mm x 30mm
  • Input: AC
  • Output : DC
  • Functions: UVP (Under Voltage Protection), OVP (Over Voltage Protection), OTP (Over Temperature Protection), OCP (Over Current Protection), SCP (Short Circuit Protection)

Product Usage Instructions

Safety Notes and Warning Instructions

Prior to startup, read the installation notes and check the device for any damage.

Designation of the Elements

  • A. Mounting flange for wall mounting (back of the device)
  • B. Connection terminal block output voltage: Output DC +
  • C. Signaling DC OK LED (green)
  • D. Integrated snap-on foot for DIN rail mounting (back of the device)
  • E. Connection terminal block input voltage: Input L/N

Signalling

The DC OK LED is available for function monitoring. The LED lights up continuously when the output voltage reaches >90% of the nominal output voltage UOUT (24 V DC).

Mounting/Removing the Power Supply

The power supply can be installed onto all 35 mm DIN rails according to EN 60715. Normal mounting position is horizontal with the input terminals facing downward. The minimum gap to other devices should be 30 mm above/below.

Mounting the Power Supply Unit

To mount the power supply, follow the instructions in the provided figure.

Removing the Power Supply Unit

To remove the power supply, follow the instructions in the provided figure.

FAQ

  • Q: What is the input voltage range for this power supply unit?
  • A: The input voltage range is [specify range here].
  • Q : What are the protection functions included in this power supply?
  • A: The power supply includes Under Voltage Protection (UVP), Over Voltage Protection (OVP), Over Temperature Protection (OTP), Over Current Protection (OCP), and Short Circuit Protection (SCP).

Dimensions

Connections

Load Table AK I/O Modules
The AK-PS ___ has an output rating to power I/O devices in any combination. Refer to the table below for individual I/O device power requirements.

Module name| Description| Inputs & Outputs| Power
---|---|---|---
AK-CM 101_

/ 102_

| Communications module|  | 2 VA
AK-XM 101_| Universal input

module

| 8 universal

inputs

| 2 VA
AK-XM 102| Digital input module (low voltage) / (high voltage)| 8 digital inputs| 2 VA
AK-XM 103
| Universal input module & analog output module| 4 universal

inputs, 4 analog outputs

| 2 VA
AK-XM 107| Pulse measuring| 8 pulse inputs| 2 VA
AK-XM 204
| Digital output module| 8 relay outputs| 5 VA
AK-XM 205_| Universal analog input & digital output module| 8 relay outputs,

8 universal

inputs

| 5 VA
AK-XM 208| Bipolar stepper output module| 4 bipolar stepper outputs| 5 VA
AK-CC
/ PC_ …| AK controller|  | 8 VA

Primary-switched power supply unit

Use this power supply to convert the electrical energy fed in by the power grid. Hereby, the AC input voltage is electrically isolated from the DC output voltage. The DC output voltage is a safety extra-low voltage

afety notes and warning instructions:
Prior to startup, read the installation notes and check the device for damage.

WARNING

  • Danger to life by electric shock!
  • Only skilled persons may install, start-up, and operate the device.
  • Never carry out work when voltage is present.

Note

  • Observe the national safety and accident prevention regulations.
  • The power supply is a built-in device and is designed for mounting in a control cabinet.
  • A suitable electrical enclosure shall be provided in the end equipment.
  • Ensure that the primary-side wiring and secondary-side wiring are the correct size and have sufficient fuse protection.
  • Use copper cables for operating temperatures of
    • 75 °C (ambient temperature < 55 °C)

    • 90 °C (ambient temperature < 75 °C).

  • The power supply is approved for the connection to TN, TT and IT power grids (star networks) with a maximum phase voltage of 240 V AC.
  • The power supply is maintenance-free. Repairs may only be carried out by the manufacturer. The warranty no longer applies if the housing is opened.
  • The power supply may only be used for its intended use.

Designation of the elements (see fig. 1)

Code no. 080Z0058

  • A. Mounting flange for wall mounting (back of the device)
  • B. Connection terminal block output voltage: Output DC +/-
  • C. Signaling DC OK LED (green)
  • D. Integrated snap-on foot for DIN rail mounting (back of the device)
  • E. Connection terminal block input voltage: Input L/N

Signaling (see fig. 1/3)

The DC OK LED is available for function monitoring. The LED lights up continuously when the output voltage reaches >90% of the nominal output voltage UOUT (24 V DC).

Mounting/removing the power supply
The power supply can be installed onto all 35 mm DIN rails according to EN 60715. Normal mounting position is horizontally (with the input terminals facing downward). The minimum gap to other devices is 30 mm above/below

  • Mounting the power supply unit (see fig. 4/5) To mount the power supply, proceed as described in the figure.
  • Removing the power supply unit (see fig. 4/5) To remove the power supply, proceed as described in the figure

Danfoss-AK-PS-130-Power-Supply-fig-4 Technical data

Input data

Input voltage range

(for DC, connect a suitable fuse)

| 100 – 240 V AC, -15 – +10 %

110 – 250 V DC, -20 – +40 %

Frequency range (fN)| 50 – 60 Hz ±10 %
Current consumption (for nominal values)| 0.59 A (100 V AC) /

0.33 A (240 V AC)

0.31 A (110 V DC) /

0.13 A (250 V DC)

Inrush current (at 25 °C)/I²t| typ. 22 A / typ. 0.27 A2s
Mains bu ring| typ. 20 ms (120 V AC) / typ. 100 ms (230 V AC)
Input fuse, internal (device protection), slow-blow| 2 A
Recommended breaker for input protection

Characteristics B, C, D, K

| 6 – 16 A
Output data
Nominal output voltage UN| 24 V DC
Nominal output current IN| 1.3 A
E ciency| > 87.5 % (120 V AC) /

88.5 % (230 V AC)

Residual ripple| typ. 100 VMS
Protection against overvoltage at the output (OVP)| < 35 V DC
Feedback voltage resistance| ≤ 35 V DC

General data

General data

Insulation voltage (input/ output)

Type/routine test

| 4 kV AC / 3.75 kV AC
Degree of protection / Protection class| IP20 / II
Degree of pollution| 2
In flammability class in acc. with UL 94| V0
Overvoltage category EN 61010-1 / EN 62477-1| II (≤ 4000 m) / III (≤ 2000 m)
Installation height (> 2000 m,

Derating: -10 %/1000 m)

| ≤ 4000 m
Ambient temperature (operation)| -10 – +70 °C

(Derating: > 50 °C; -2 %/K)

Ambient temperature (storage/transport)| -40 – +85 °C
Humidity at 25 °C, non-

condensing

| ≤ 95 %
Dimensions (W/H/D) / + DIN rail| 36 x 90 x 55 mm
Horizontal pitch (DIN 43880)| 2 TE

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals