ACCURATE LOCK HARDWARE M9100ELR Motor Drive Electrified Latch Retraction Instruction Manual
- June 1, 2024
- ACCURATE LOCK HARDWARE
Table of Contents
ACCURATE LOCK HARDWARE M9100ELR Motor Drive Electrified Latch Retraction
Specifications
- Power Supply Voltage: 24VDC (21VDC-30VDC)
- Current: 625mA MAX Inrush, 150mA MAX Holding
- Non-polarized leads
Operating Instructions
The M9100ELR is a motor drive electrified latch retraction system. The outside trim (or both outside and inside trim depending on the lock function) is locked. The main latch bolt is retracted when power is applied, and it is extended in the event of a power failure. Key Cylinders (by others) can override electronics to retract the latch bolt.
Electrical Specifications
The power supply voltage should be within the range of 21VDC-30VDC. The system operates with a maximum current of 625mA in inrush and 150mA in holding mode. It uses non-polarized leads for connections.
- Filtered and Regulated Power Supply
- Voltage: 24VDC (21VDC-30VDC)
- Current: 625mA MAX Inrush, 150mA MAX Holding
- Non-polarized leads
Wire Run Distance and Gauge
Distance | Wire Gauge |
---|---|
125′ | 22 |
200′ | 20 |
350′ | 18 |
500′ | 16 |
800′ | 14 |
1250′ | 12 |
Indicator Lights
The onboard indicator lights are visible with the armour front removed. They provide information on power status, normal operation, and error indications.
- The outside trim (or both outside and inside trim depending on lock function) is locked.
- The main latch bolt is retracted when power is applied. The main latch bolt is extended in the event of a power failure.
- The key Cylinder (by others) will override electronics to retract the latch bolt.
ONBOARD INDICATOR LIGHT ASSIGNMENTS
Maintain input power to the mortise lock and check the onboard indicator lights. Remove input power before attempting a solution.