Delta 1 kVA UPS Amplon Family RT Gen Instruction Manual

June 1, 2024
Delta

Delta 1 kVA UPS Amplon Family RT Gen

Delta-1-kVA-UPS-Amplon-Family-RT-Gen-product

Specifications

Technical Specifications

  • Model: RT-1K (1 kVA), RT-2K (2 kVA)
  • Topology: Online double-conversion
  • Power Rating: 1 kVA (0.9 kW) for RT-1K, 2 kVA (1.8 kW) for RT-2K

Input

  • Nominal Voltage: 220/230/240 Vac, 1 phase
  • Voltage Range: 180~280 Vac (full load); 120~300 Vac (50% load)
  • Frequency: 40~70 Hz
  • Power Factor: 0.99 (full load)
  • Connection: IEC C14 x1

Output

  • Nominal Voltage: 208(1), 220, 230, 240 Vac
  • Voltage Regulation: < 3% (linear load)
  • Frequency: Standard
  • Total Harmonic Distortion (THDv): < 3%
  • Power Factor: 0.9
  • Connection: IEC C13 x4, C19 x1
  • Overload Capability: Up to 150% for short durations
  • Current Crest Ratio: 3:1

Battery

  • Battery Type: VRLA, inbuilt battery
  • Nominal Voltage: 24 Vdc for RT-1K, 48 Vdc for RT-2K
  • Quantity: 2 pcs for RT-1K, 4 pcs for RT-2K
  • Runtime: Varies based on load percentage
  • Charging Time: Approximately 4 hours to reach 90%
  • Parallel Configuration: Up to 4 EBCs
  • Charge Current: 1 A

Communication Interface

  • Display Port: LCD screen with LED indicators
  • Interfaces: USB, RS232, mini slot (option for Modbus TCP/IP, SNMP), REPO

Physical

  • Dimensions (W x D x H): 438 x 310 x 86 mm for RT-1K, 438 x 410 x 86 mm for RT-2K
  • Net Weight: 10.6 kg for RT-1K, 17.9 kg for RT-2K
  • Packing Dimensions (W x D x H): 600 x 500 x 240 mm for RT-1K, 565 x 700 x 240 mm for RT-2K
  • Packing Weight: 13.9 kg for RT-1K, 22 kg for RT-2K

Environment

  • Operating Temperature: Standard range
  • Humidity: Standard levels
  • Audible Noise: Standard levels
  • Altitude: Standard levels
  • Storage Temperature: Standard range
  • Ingress Protection: Standard level

Conformance

  • Safety: Compliant with safety standards
  • EMC: Compliant with EMC standards
  • Sustainability: Sustainable design and materials used

Product Usage Instructions

Installation

  1. Select a stable location for the UPS.
  2. Ensure proper ventilation around the UPS unit.
  3. Connect the input power to the UPS using the provided power cord.
  4. If needed, connect additional external battery cabinets (EBC)following the provided guidelines.
  5. Tightly secure all connections and turn on the UPS.

Operation

  1. The UPS will start providing power to the connected devices automatically.
  2. You can monitor the UPS status and parameters using the LCD screen and indicators.
  3. In case of a power outage or voltage irregularities, the UPS will switch to battery power to ensure continuous operation of your devices.
  4. If the UPS enters overload conditions, reduce the connected load or add external battery cabinets to support it.

Maintenance

  1. Regularly check the battery status and runtime to ensure optimal performance.
  2. Clean the UPS unit and ensure proper ventilation to prevent overheating.

Frequently Asked Questions (FAQ)

  • Q: How can I check the remaining runtime of the UPS?
    A: You can check the remaining runtime either on the LCD screen of the UPS or through the monitoring software if connected to a computer.

  • Q: Can I use the UPS in a rack-mounted configuration?
    A: Yes, the UPS offers a convertible rack and tower configuration to suit your needs.

  • Q: What should I do if the UPS shows an overload indication?
    A: If the UPS indicates an overload, reduce the connected load or consider adding external battery cabinets to support the load.

  • Q: Is it possible to extend the battery runtime of the UPS?
    A: Yes, you can extend the battery runtime by adding external battery cabinets as needed.

  • Q: What communication interfaces are available for the UPS?
    A: The UPS is equipped with USB, RS232, and other optional interfaces for monitoring and management purposes.

  • Q: How do I know if the UPS is operating in ECO mode?
    A: The UPS typically indicates when it is operating in ECO mode through its display panel or status indicators.

  • Q: Can I connect multiple devices to the UPS?
    A: The UPS provides multiple output connections allowing you to connect several devices depending on their power requirements.

Delta UPS Amplon Family

RT Gen3 Series, Single Phase, 1/2/3 kVA

Safeguard your edge with a smart and economical power solution
Delta’s Amplon RT series UPS is a robust online double-conversion UPS offering strong power protection with a convertible rack and tower configuration in 2U size. With its clean output power in pure sine wave, RT Gen3 can handle a wide range of utility problems, from blackout to harmonic distortion. Rest assured that your device is always fortified and safeguarded with RT Gen3!

High Availability

  • True online double-conversion topology and zero transfer time to battery mode
  • Operates at up to 50 ? adapting to various environments
  • Excellent overload capacity allows the overload condition to continue within the timeframe
  • External battery connector for easy scaling of longer backup time

Green with Low TCO

  • Output power factor 0.9 provides more capacity to load
  • Up to 90 % online mode efficiency and 95 % ECO mode efficiency contributes to significant energy cost savings
  • Capable of working in harsh electrical environments with a wide input voltage range to minimize battery usage

Easy Management

  • Convertible rack and tower configuration with rotatable LCD screen
  • LCD display and intuitive interface offer effortless monitoring and configuration
  • Remote Emergency Power Off (REPO) provides added safety by allowing UPS and connected devices to be remotely shut down during emergencies
  • Intelligent management software connectivity via RS232, mini slot or USB port for remote monitoring and setting

Rear Panel

  1. AC input
  2. Input circuit breaker
  3. USB port
  4. RS-232 port
  5. Mini slot
  6. External battery pack connector
  7. Output socket
  8. REPO

Delta-1-kVA-UPS-Amplon-Family-RT-Gen- \(2\)

LCD Delta-1-kVA-UPS-Amplon-Family-RT-Gen- \(3\)

Form Factor

Runtime Table

1 kVA

| 90 W| 180 W| 270 W| 360 W| 450 W| 540 W| 630 W| 720 W| 810 W| 900 W
---|---|---|---|---|---|---|---|---|---|---
UPS| 57.5| 26.9| 16.8| 11.9| 9.1| 7.3| 6.1| 3.5| 3.5| 3.1
UPS+1EBC| 182.2| 94.3| 61.8| 45.0| 34.7| 27.9| 23.1| 3.5| 3.5| 3.5
UPS+2EBC| 310.6| 163.7| 109.2| 80.8| 63.5| 51.8| 43.4| 3.5| 3.5| 3.5
UPS+3EBC| 439.1| 233.3| 156.8| 117.0| 92.5| 76.1| 64.2| 3.5| 3.5| 3.5
UPS+4EBC| 567.7| 302.9| 204.5| 153.2| 121.7| 100.5| 85.2| 3.5| 3.5| 3.5

2 kVA

| 180 W| 360 W| 540 W| 720 W| 900 W| 1080 W| 1260 W| 1440 W| 1620 W| 1800 W
---|---|---|---|---|---|---|---|---|---|---
UPS| 61.1| 28.3| 17.7| 12.5| 9.5| 7.7| 6.5| 3.5| 3.5| 3.3
UPS+1EBC| 190.6| 98.9| 64.9| 47.3| 36.6| 29.4| 24.3| 3.5| 3.5| 3.5
UPS+2EBC| 324.8| 171.6| 114.6| 84.9| 66.7| 54.5| 45.7| 3.5| 3.5| 3.5
UPS+3EBC| 459.1| 244.4| 164.5| 122.8| 97.2| 79.9| 67.5| 3.5| 3.5| 3.5
UPS+4EBC| 593.3| 317.3| 214.4| 160.8| 127.8| 105.5| 89.5| 3.5| 3.5| 3.5

3 kVA

| 270 W| 540 W| 810 W| 1080 W| 1350 W| 1620 W| 1890 W| 2160 W| 2430 W| 2700 W
---|---|---|---|---|---|---|---|---|---|---
UPS| 67.1| 29.4| 18.1| 12.5| 10.3| 8.2| 6.9| 3.5| 3.5| 3.5
UPS+1EBC| 203.5| 106.0| 69.7| 50.9| 39.4| 31.8| 26.3| 3.5| 3.5| 3.5
UPS+2EBC| 346.5| 183.7| 122.9| 91.2| 71.7| 58.6| 49.2| 3.5| 3.5| 3.5
UPS+3EBC| 489.6| 261.5| 176.3| 131.7| 104.4| 85.9| 72.6| 3.5| 3.5| 3.5
UPS+4EBC| 632.8| 339.4| 229.7| 172.4| 137.2| 113.4| 96.2| 3.5| 3.5| 3.5

  1. Up to 4 EBCs can be paralleled.
  2. Runtime table is estimated based on operation at 25 °C with batteries fully charged.

Technical Specifications

Model                                                                RT- 1K| RT-2K RT-3K
---|---
Topology| Online double-conversion
Power Rating

INPUT

| 1 kVA

0.9 kW

| 2 kVA

1.8 kW

| 3 kVA

2.7 kW

Nominal Voltage| 220/230/240 Vac, 1 phase 2 Wire (1PH+PE)
Voltage Range| 180~280 Vac (full load); 120~300 Vac (50 % load)
Frequency| 40~70 Hz
Power Factor| ≥ 0.99 (full load)
Connection| IEC C14 x1| IEC C20 x1
OUTPUT|
Nominal Voltage| 208(1), 220, 230, 240 Vac
Voltage Regulation| ±1 %
Frequency| 50/60 Hz ± 0.5 %
Total Harmonic Distortion (THDv)| < 3 % (linear load)
Power Factor| 0.9
Connection| IEC C13 x4| IEC C13 x4, C19 x1
Overload Capability| < 105~110 %: 10 minutes; 110~130 %: 30 seconds; 130~150 %: 3 seconds
Current Crest Ratio

EFFICIENCY

| 3:1
Online Mode| 88 %| 90 %
ECO Mode

BATTERY

| 93 %| 94 %| 95 %
Battery Type| VRLA, inbuilt battery
Nominal Voltage| 24 Vdc| 48 Vdc| 72 Vdc
Quantity| 2 pcs| 4 pcs| 6 pcs
Runtime                           100% load

70% load

| 3.1 mins

6.1 mins

| 3.3 mins

6.5 mins

| 3.5 mins

6.9 mins

Charging Time| 4 hours to 90 %| |
Parallel Configuration| Up to 4 EBCs
Charge Current| 1 A
COMMUNICATION INTERFACE|
Display| LCD screen with LED indicators
Port

PHYSICAL

| USB, RS232, mini slot (option for Modbus TCP/IP, SNMP), REPO
Dimensions (W x D x H)| 438 x 310 x 86 mm| 438 x 410 x 86 mm| 438 x 630 x 86 mm
Net Weight| 10.6 kg| 17.9 kg| 26.6 kg
Packing Dimensions (W x D x H)| 600 x 500 x 240 mm| 565 x 700 x 240 mm| 600 x 760 x 240 mm
Packing Weight

ENVIRONMENT

| 13.9 kg| 22 kg| 31.5 kg
Operating Temperature| 0 to 50 °C (40 to 50 °C de-rating to 70 % load)
Humidity| 10~90 % (non-condensing)
Audible Noise| ≤ 50 dBA
Altitude| 0-3,000 m (derating 1 %/100 m from 2,000-3,000 m)
Storage Temperature| -20 to +50 °C
Ingress Protection

CONFORMANCE

| IP20
Safety| CE, KC
EMC| IEC 62040-2
Sustainability| RoHS, REACH

(1) De-rating to 70 % load
All specifications are subject to change without prior notice.

Management Solution

UPSentry

  • Supports RS-232 & USB communication
  • Schedules shutdown, restart and battery test
  • Event tracking

ShutdownAgent

  • Provides a graceful unattended shutdown of multiple computer systems over a network

SNMP IPv6 (optional)

  • Remote UPS management from any workstation through internet or intranet
  • UPS and system function configuration from any client (password protected)
  • Event logs and data tracking

Delta-1-kVA-UPS-Amplon-Family-RT-Gen- \(5\)

What’s in the Box

Standard Accessories

RT Gen3 UPS User manual
USB cable (1.5 m) AC input cable with Schuko plug (1.5 m)
Ear kit and tower stand ShutdownAgent software
UPSentry software

Optional Accessories

External Battery Cabinet      Net Dimensions (W x D x H)  Net Weight  Packing Dimensions (W x D x H)  Packing Weight

RT-1K External Battery Cabinet

(Part number: BBA022B2009035)

| 480 x 380 x 86 mm| 16 kg| 600 x 500 x 240 mm| 18.1 kg
---|---|---|---|---
RT-2K External Battery Cabinet

(Part number: BBA042B5009035)

| 438 x 480 x 86 mm| 28.6 kg| 700 x 565 x 240 mm| 31.5 kg
RT-3K External Battery Cabinet

(Part number: BBA062B6009035)

| 430 x 600 x 86 mm| 45.1 kg| 760 x 600 x 240 mm| 48.1 kg

UPS Management Accessories

Mini SNMP IPv6 (Part number: SCMS100035)| Manages UPS and system functions securely and adjusts parameters through SNMP management stations or internet browsers using HTTP forms.
---|---
Mini Relay I/O Card (Part number: 3915101864-S)| Offers 6 relay output contacts to monitor status and 2 input contacts for simple shutdown and battery testing in UPS management.
Mini Modbus Card (Part number: 3915101865-S)| Supports Modbus communication with a PC via RS-485 and RS-232 interfaces, allowing for flexible and simultaneous use.

Installation Delta-1-kVA-UPS-Amplon-Family-RT-Gen-
\(7\)

Leaflet_UPS_RT Gen3_1-3 kVA_SB_en-KR_EGAKEM-04-JY

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>