Delta 1 kVA UPS Amplon Family RT Gen Instruction Manual
- June 1, 2024
- Delta
Table of Contents
Delta 1 kVA UPS Amplon Family RT Gen
Specifications
Technical Specifications
- Model: RT-1K (1 kVA), RT-2K (2 kVA)
- Topology: Online double-conversion
- Power Rating: 1 kVA (0.9 kW) for RT-1K, 2 kVA (1.8 kW) for RT-2K
Input
- Nominal Voltage: 220/230/240 Vac, 1 phase
- Voltage Range: 180~280 Vac (full load); 120~300 Vac (50% load)
- Frequency: 40~70 Hz
- Power Factor: 0.99 (full load)
- Connection: IEC C14 x1
Output
- Nominal Voltage: 208(1), 220, 230, 240 Vac
- Voltage Regulation: < 3% (linear load)
- Frequency: Standard
- Total Harmonic Distortion (THDv): < 3%
- Power Factor: 0.9
- Connection: IEC C13 x4, C19 x1
- Overload Capability: Up to 150% for short durations
- Current Crest Ratio: 3:1
Battery
- Battery Type: VRLA, inbuilt battery
- Nominal Voltage: 24 Vdc for RT-1K, 48 Vdc for RT-2K
- Quantity: 2 pcs for RT-1K, 4 pcs for RT-2K
- Runtime: Varies based on load percentage
- Charging Time: Approximately 4 hours to reach 90%
- Parallel Configuration: Up to 4 EBCs
- Charge Current: 1 A
Communication Interface
- Display Port: LCD screen with LED indicators
- Interfaces: USB, RS232, mini slot (option for Modbus TCP/IP, SNMP), REPO
Physical
- Dimensions (W x D x H): 438 x 310 x 86 mm for RT-1K, 438 x 410 x 86 mm for RT-2K
- Net Weight: 10.6 kg for RT-1K, 17.9 kg for RT-2K
- Packing Dimensions (W x D x H): 600 x 500 x 240 mm for RT-1K, 565 x 700 x 240 mm for RT-2K
- Packing Weight: 13.9 kg for RT-1K, 22 kg for RT-2K
Environment
- Operating Temperature: Standard range
- Humidity: Standard levels
- Audible Noise: Standard levels
- Altitude: Standard levels
- Storage Temperature: Standard range
- Ingress Protection: Standard level
Conformance
- Safety: Compliant with safety standards
- EMC: Compliant with EMC standards
- Sustainability: Sustainable design and materials used
Product Usage Instructions
Installation
- Select a stable location for the UPS.
- Ensure proper ventilation around the UPS unit.
- Connect the input power to the UPS using the provided power cord.
- If needed, connect additional external battery cabinets (EBC)following the provided guidelines.
- Tightly secure all connections and turn on the UPS.
Operation
- The UPS will start providing power to the connected devices automatically.
- You can monitor the UPS status and parameters using the LCD screen and indicators.
- In case of a power outage or voltage irregularities, the UPS will switch to battery power to ensure continuous operation of your devices.
- If the UPS enters overload conditions, reduce the connected load or add external battery cabinets to support it.
Maintenance
- Regularly check the battery status and runtime to ensure optimal performance.
- Clean the UPS unit and ensure proper ventilation to prevent overheating.
Frequently Asked Questions (FAQ)
-
Q: How can I check the remaining runtime of the UPS?
A: You can check the remaining runtime either on the LCD screen of the UPS or through the monitoring software if connected to a computer. -
Q: Can I use the UPS in a rack-mounted configuration?
A: Yes, the UPS offers a convertible rack and tower configuration to suit your needs. -
Q: What should I do if the UPS shows an overload indication?
A: If the UPS indicates an overload, reduce the connected load or consider adding external battery cabinets to support the load. -
Q: Is it possible to extend the battery runtime of the UPS?
A: Yes, you can extend the battery runtime by adding external battery cabinets as needed. -
Q: What communication interfaces are available for the UPS?
A: The UPS is equipped with USB, RS232, and other optional interfaces for monitoring and management purposes. -
Q: How do I know if the UPS is operating in ECO mode?
A: The UPS typically indicates when it is operating in ECO mode through its display panel or status indicators. -
Q: Can I connect multiple devices to the UPS?
A: The UPS provides multiple output connections allowing you to connect several devices depending on their power requirements.
Delta UPS Amplon Family
RT Gen3 Series, Single Phase, 1/2/3 kVA
Safeguard your edge with a smart and economical power solution
Delta’s Amplon RT series UPS is a robust online double-conversion UPS offering
strong power protection with a convertible rack and tower configuration in 2U
size. With its clean output power in pure sine wave, RT Gen3 can handle a wide
range of utility problems, from blackout to harmonic distortion. Rest assured
that your device is always fortified and safeguarded with RT Gen3!
High Availability
- True online double-conversion topology and zero transfer time to battery mode
- Operates at up to 50 ? adapting to various environments
- Excellent overload capacity allows the overload condition to continue within the timeframe
- External battery connector for easy scaling of longer backup time
Green with Low TCO
- Output power factor 0.9 provides more capacity to load
- Up to 90 % online mode efficiency and 95 % ECO mode efficiency contributes to significant energy cost savings
- Capable of working in harsh electrical environments with a wide input voltage range to minimize battery usage
Easy Management
- Convertible rack and tower configuration with rotatable LCD screen
- LCD display and intuitive interface offer effortless monitoring and configuration
- Remote Emergency Power Off (REPO) provides added safety by allowing UPS and connected devices to be remotely shut down during emergencies
- Intelligent management software connectivity via RS232, mini slot or USB port for remote monitoring and setting
Rear Panel
- AC input
- Input circuit breaker
- USB port
- RS-232 port
- Mini slot
- External battery pack connector
- Output socket
- REPO
LCD
Form Factor
Runtime Table
1 kVA
| 90 W| 180 W| 270 W| 360 W| 450 W| 540 W| 630 W| 720 W| 810 W| 900 W
---|---|---|---|---|---|---|---|---|---|---
UPS| 57.5| 26.9| 16.8| 11.9| 9.1| 7.3| 6.1| 3.5| 3.5| 3.1
UPS+1EBC| 182.2| 94.3| 61.8| 45.0| 34.7| 27.9| 23.1| 3.5| 3.5| 3.5
UPS+2EBC| 310.6| 163.7| 109.2| 80.8| 63.5| 51.8| 43.4| 3.5| 3.5| 3.5
UPS+3EBC| 439.1| 233.3| 156.8| 117.0| 92.5| 76.1| 64.2| 3.5| 3.5| 3.5
UPS+4EBC| 567.7| 302.9| 204.5| 153.2| 121.7| 100.5| 85.2| 3.5| 3.5| 3.5
2 kVA
| 180 W| 360 W| 540 W| 720 W| 900 W| 1080 W| 1260 W| 1440 W| 1620 W| 1800 W
---|---|---|---|---|---|---|---|---|---|---
UPS| 61.1| 28.3| 17.7| 12.5| 9.5| 7.7| 6.5| 3.5| 3.5| 3.3
UPS+1EBC| 190.6| 98.9| 64.9| 47.3| 36.6| 29.4| 24.3| 3.5| 3.5| 3.5
UPS+2EBC| 324.8| 171.6| 114.6| 84.9| 66.7| 54.5| 45.7| 3.5| 3.5| 3.5
UPS+3EBC| 459.1| 244.4| 164.5| 122.8| 97.2| 79.9| 67.5| 3.5| 3.5| 3.5
UPS+4EBC| 593.3| 317.3| 214.4| 160.8| 127.8| 105.5| 89.5| 3.5| 3.5| 3.5
3 kVA
| 270 W| 540 W| 810 W| 1080 W| 1350 W| 1620 W| 1890 W| 2160 W| 2430 W| 2700 W
---|---|---|---|---|---|---|---|---|---|---
UPS| 67.1| 29.4| 18.1| 12.5| 10.3| 8.2| 6.9| 3.5| 3.5| 3.5
UPS+1EBC| 203.5| 106.0| 69.7| 50.9| 39.4| 31.8| 26.3| 3.5| 3.5| 3.5
UPS+2EBC| 346.5| 183.7| 122.9| 91.2| 71.7| 58.6| 49.2| 3.5| 3.5| 3.5
UPS+3EBC| 489.6| 261.5| 176.3| 131.7| 104.4| 85.9| 72.6| 3.5| 3.5| 3.5
UPS+4EBC| 632.8| 339.4| 229.7| 172.4| 137.2| 113.4| 96.2| 3.5| 3.5| 3.5
- Up to 4 EBCs can be paralleled.
- Runtime table is estimated based on operation at 25 °C with batteries fully charged.
Technical Specifications
Model RT-
1K| RT-2K RT-3K
---|---
Topology| Online double-conversion
Power Rating
INPUT
| 1 kVA
0.9 kW
| 2 kVA
1.8 kW
| 3 kVA
2.7 kW
Nominal Voltage| 220/230/240 Vac, 1 phase 2 Wire (1PH+PE)
Voltage Range| 180~280 Vac (full load); 120~300 Vac (50 % load)
Frequency| 40~70 Hz
Power Factor| ≥ 0.99 (full load)
Connection| IEC C14 x1| IEC C20 x1
OUTPUT|
Nominal Voltage| 208(1), 220, 230, 240 Vac
Voltage Regulation| ±1 %
Frequency| 50/60 Hz ± 0.5 %
Total Harmonic Distortion (THDv)| < 3 % (linear load)
Power Factor| 0.9
Connection| IEC C13 x4| IEC C13 x4, C19 x1
Overload Capability| < 105~110 %: 10 minutes; 110~130 %: 30 seconds; 130~150
%: 3 seconds
Current Crest Ratio
EFFICIENCY
| 3:1
Online Mode| 88 %| 90 %
ECO Mode
BATTERY
| 93 %| 94 %| 95 %
Battery Type| VRLA, inbuilt battery
Nominal Voltage| 24 Vdc| 48 Vdc| 72 Vdc
Quantity| 2 pcs| 4 pcs| 6 pcs
Runtime 100% load
70% load
| 3.1 mins
6.1 mins
| 3.3 mins
6.5 mins
| 3.5 mins
6.9 mins
Charging Time| 4 hours to 90 %| |
Parallel Configuration| Up to 4 EBCs
Charge Current| 1 A
COMMUNICATION INTERFACE|
Display| LCD screen with LED indicators
Port
PHYSICAL
| USB, RS232, mini slot (option for Modbus TCP/IP, SNMP), REPO
Dimensions (W x D x H)| 438 x 310 x 86 mm| 438 x 410 x 86 mm| 438 x 630 x 86
mm
Net Weight| 10.6 kg| 17.9 kg| 26.6 kg
Packing Dimensions (W x D x H)| 600 x 500 x 240 mm| 565 x 700 x 240 mm| 600 x
760 x 240 mm
Packing Weight
ENVIRONMENT
| 13.9 kg| 22 kg| 31.5 kg
Operating Temperature| 0 to 50 °C (40 to 50 °C de-rating to 70 % load)
Humidity| 10~90 % (non-condensing)
Audible Noise| ≤ 50 dBA
Altitude| 0-3,000 m (derating 1 %/100 m from 2,000-3,000 m)
Storage Temperature| -20 to +50 °C
Ingress Protection
CONFORMANCE
| IP20
Safety| CE, KC
EMC| IEC 62040-2
Sustainability| RoHS, REACH
(1) De-rating to 70 % load
All specifications are subject to change without prior notice.
Management Solution
UPSentry
- Supports RS-232 & USB communication
- Schedules shutdown, restart and battery test
- Event tracking
ShutdownAgent
- Provides a graceful unattended shutdown of multiple computer systems over a network
SNMP IPv6 (optional)
- Remote UPS management from any workstation through internet or intranet
- UPS and system function configuration from any client (password protected)
- Event logs and data tracking
What’s in the Box
Standard Accessories
RT Gen3 UPS | User manual |
---|---|
USB cable (1.5 m) | AC input cable with Schuko plug (1.5 m) |
Ear kit and tower stand | ShutdownAgent software |
UPSentry software |
Optional Accessories
External Battery Cabinet Net Dimensions (W x D x H) Net Weight Packing Dimensions (W x D x H) Packing Weight
RT-1K External Battery Cabinet
(Part number: BBA022B2009035)
| 480 x 380 x 86 mm| 16 kg| 600 x 500 x 240 mm| 18.1 kg
---|---|---|---|---
RT-2K External Battery Cabinet
(Part number: BBA042B5009035)
| 438 x 480 x 86 mm| 28.6 kg| 700 x 565 x 240 mm| 31.5 kg
RT-3K External Battery Cabinet
(Part number: BBA062B6009035)
| 430 x 600 x 86 mm| 45.1 kg| 760 x 600 x 240 mm| 48.1 kg
UPS Management Accessories
Mini SNMP IPv6 (Part number: SCMS100035)| Manages UPS and system functions
securely and adjusts parameters through SNMP management stations or internet
browsers using HTTP forms.
---|---
Mini Relay I/O Card (Part number: 3915101864-S)| Offers 6 relay output
contacts to monitor status and 2 input contacts for simple shutdown and
battery testing in UPS management.
Mini Modbus Card (Part number: 3915101865-S)| Supports Modbus communication
with a PC via RS-485 and RS-232 interfaces, allowing for flexible and
simultaneous use.
Installation