BANNER R95C 8 Port 2 Channel Discrete IO Link Hub Instruction Manual
- June 2, 2024
- BANNER
Table of Contents
R95C 8-Port 2-Channel Discrete IO-Link Hub Instruction Manual
BANNER ENGINEERING CORP.
Features
- Compact bimodal to IO-Link device converter that connects discrete inputs and sends the value to the IO-Link Master
- Outputs a discrete value as received from IO-Link Master Process Data Out
- Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable One-shot, ON/OFF Pulse-stretcher and Totalizer
- Measurement Metrics: Count, Events Per Minute (EPM), and Duration
- Discrete Mirroring: Discrete signals (In/Out) from all eight ports can be mirrored to any of the eight ports, Discrete Out, or the host white wire output
- Discrete input/output can be independently configured as NPN or PNP
- Rugged overmolded design meets IP65, IP67, and IP68
- Connects directly to a sensor or anywhere in-line for ease of use
- R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IO-Link devices into an IO-Link system
Models
Overview
The R95C-8B22-KQ hub connects two discrete Input/Output channels to each of the eight unique ports, providing access to monitoring and configuring those ports with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/Host connection.
Configuration
Figure 1 details the logic flow for each of the eight ports, while the tables
define the configuration for each pin.
For more information, see P/N 233583 R95C-8B22-KQ IO-Link Data Reference Guide
and P/N 233584 R95C-8B22-KQ IODD Files.
Table 1: Measurements – Female Pins
Port 1-Port 8 Pin Number: Description | IO Metric | Description |
---|
Pin 4 – Discrete 1
Pin 2 – Discrete 2| Count Value| Running count of the received input pulses
Duration Value| Duration of the last input pulse in µs with 500 µs granularity
Events per Minute Value| Running count of the number of pulses received
averaged
over one minute Range: 1 to 37,500
Reset Metrics| • Do Not Reset
• Reset
Table 2: Pin Configuration – Female Input
Port 1-Port 8 Pin Number: Description | Name | Values |
---|
Pin 4 – Discrete 1
Pin 2 – Discrete 2| Discrete I/O Selection| • NPN Input
• PNP Input
• NPN Output with Pull Up
• PNP Output with Pull Down
• NPN Output with Push/Pull
• PNP Output with Push/Pull
Discrete Delay Mode| • Disabled
• On/Off Delay
• On One-shot
• Off One-shot
• On Pulse-stretcher
• Off Pulse-stretcher
• Totalizer
• Retriggerable On One-shot
• Retriggerable Off One-shot
Discrete Delay Timer 1| Discrete On Delay, One-shot, Pulse-Stretcher
Time, or Totalizer Count
Discrete Delay Timer 2| Discrete Off Delay or Totalizer Time
Mirroring Enable| • Disabled
• Enabled
Mirroring Port Selection| • Port 1
• Port 2
• Port 3
• Port 4
• Port 5
• Port 6
• Port 7
• Port 8
Mirroring Channel Selection| • Pin 4 – Discrete 1
• Pin 2 – Discrete 2
Mirroring Inversion| • Not Inverted
• Inverted
Table 3: Pin Configuration – Male Output
Pin Number: Description | Name | Values |
---|---|---|
Pin 2 – Discrete Host Out | Host Mirroring Enable | • Disabled |
• Enabled
Host Mirroring Port Selection| • Port 1
• Port 2
• Port 3
• Port 4
• Port 5
• Port 6
• Port 7
• Port 8
Host Mirroring Channel Selection| • Pin 4 – Discrete 1
• Pin 2 – Discrete 2
Host Mirroring Inversion| • Not Inverted
• Inverted
Host Mirroring Polarity| • PNP
• NPN
Host Mirroring Output Type| • Open Collector
• Push/Pull
IO-Link®
IO-Link® is a point-to-point communication link between a master device and a
sensor and/or light. It can be used to automatically parameterize sensors or
lights and to transmit process data. For the latest IO-Link protocol and
specifications, please visit www.io-link.com.
For the latest IODD files, please refer to the Banner Engineering Corp website
at: www.bannerengineering.com.
Mechanical Installation
Install the R95C to allow access for functional checks, maintenance, and
service or replacement. Do not install the R95C in such a way to allow for
intentional defeat.
Fasteners must be of sufficient strength to guard against breakage. The use of
permanent fasteners or locking hardware is recommended to prevent the
loosening or displacement of the device. The mounting hole (4.5 mm) in the
R95C accepts M4 (#8) hardware. See the figure below to help in determining the
minimum screw length.
CAUTION: Do not overtighten the R95C’s mounting screw during installation. Overtightening can affect the performance of the R95C.
Wiring
Port 1-Port 8 — Female | Pin | Signal Description |
---|---|---|
1 | 18 V DC to 30 V DC | |
2 | Discrete 2 (IN/OUT) | |
3 | Ground | |
4 | Discrete 1 (IN/OUT) | |
Male | Pin | Signal Description |
--- | --- | --- |
1 | 18 V DC to 30 V DC | |
2 | Banner-specific | |
3 | Ground | |
4 | IO-Link |
Status Indicators
The R95C 8-Port 2-Channel Discrete Bimodal IO-Link Hub has two matching amber LED indicators, one for each channel, on both sides for each discrete device port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the IO-Link communication.
LED 1 = Discrete 1 In/Out
LED 2 = Discrete 2 In/Out
LED | Indication | Status |
---|---|---|
Discrete Device Amber LEDs | Off | Discrete In and Out are inactive |
Solid Amber | Discrete In or Out is active | |
IO-Link Communication Amber LED | Off | IO-Link communications are not present |
Flashing Amber (900 ms On, 100 ms Off) | IO-Link communications are active | |
Power Indicator Green LED | Off | Power off |
Solid Green | Power on |
Specifications
Supply Voltage | 18 V DC to 30 V DC at 400 mA maximum (exclusive of load) |
---|---|
Power Pass-Through Current | 500 mA per port maximum |
Discrete Output Load Rating | 200 mA |
Supply Protection Circuitry | Protected against reverse polarity and transient |
voltages
Leakage Current Immunity| 400 µA
Indicators| Green: Power
Amber: IO-Link communications
Amber: 2x Discrete IN/OUT status
Connections| (8) Integral 4-pin M12 female quick disconnect
(1) Integral 4-pin M12 male quick-disconnect connector
Construction| Coupling Material: Nickel-plated brass
Connector Body: PVC translucent black
Vibration and Mechanical Shock| Meets IEC 60068-2-6 requirements (Vibration:
10 Hz to 55 Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
Environmental Rating| IP65, IP67, IP68
NEMA/UL Type 1
Operating Conditions| Temperature: –40 °C to +70 °C (–40 °F to +158 °F) 90% at
+70 °C maximum relative humidity (non-condensing) Storage Temperature: –40 °C
to +80 °C (–40 °F to +176 °F)
Required Overcurrent Protection
WARNING: Electrical connections must be made by qualified personnel in
accordance with local and national electrical codes and regulations.
Overcurrent protection is required to be provided by end product application
per the supplied table.
Overcurrent protection may be provided with external fusing or via Current
Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to
www.bannerengineering.com.
Supply Wiring (AWG)| Required Overcurrent Protection (A)| Supply
Wiring (AWG)| Required Overcurrent Protection (A)
---|---|---|---
20| 5| 26| 1
22| 3| 28| 0.8
24| 1| 30| 0.5
Certifications
Banner Engineering BV
Park Lane, Culliganlaan 2F bus 3, 1831 Diegem, BELGIUM
Turck Banner LTD Blenheim House, Blenheim Court, Wickford, Essex SS11 8YT, Great Britain
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation.
If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the
following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Industry Canada
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.
Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.
Accessories
Cordsets
4-Pin Threaded M12 Cordsets—Double Ended
Model | Length | Style | Dimensions | Pinout |
---|---|---|---|---|
MQDEC-401SS | 0.31 m (1 ft) |
Male
1 = Brown
2 = White
3 = Blue
4 = Black
MQDEC-403SS| 0.91 m (2.99 ft)
MQDEC-406SS| 1.83 m (6 ft)
MQDEC-412SS| 3.66 m (12 ft)
MQDEC-420SS| 6.10 m (20 ft)
MQDEC-430SS| 9.14 m (30.2 ft)
MQDEC-450SS| 15.2 m (49.9 ft)
Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in
material and workmanship for one year following the date of shipment. Banner
Engineering Corp. will repair or replace, free of charge, any product of its
manufacture which, at the time it is returned to the factory, is found to have
been defective during the warranty period. This warranty does not cover damage
or liability for misuse, abuse, or the improper application or installation of
the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER
EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING
UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of
Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING
CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS,
EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL
DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE
THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT
LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the
design of the product without assuming any obligations or liabilities relating
to any product previously manufactured by Banner Engineering Corp. Any misuse,
abuse, or improper application or installation of this product or use of the
product for personal protection applications when the product is identified as
not intended for such purposes will void the product warranty. Any
modifications to this product without prior express approval by Banner
Engineering Corp will void the product warranties. All specifications
published in this document are subject to change; Banner reserves the right to
modify product specifications or update documentation at any time.
Specifications and product information in English supersede that which is
provided in any other language. For the most recent version of any
documentation, refer to:
www.bannerengineering.com.
For patent information, see
www.bannerengineering.com/patents.
Document title: R95C 8-Port 2-Channel Discrete Bimodal IO-Link Hub Instruction
Manual
Part number: 233582
Revision: B
Original Instructions
© Banner Engineering Corp. All rights reserved.
© Banner Engineering Corp.
www.bannerengineering.com