IND506 Lumination LED Luminaire
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING
RISK OF ELECTRIC SHOCK
- Turn the power off before inspection, installation or removal.
- Properly ground electrical enclosure.
RISK OF FIRE
- Follow all NEC and local codes.
- Use only UL-approved wire for input/output connections.
Only use size 18 AWG.
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any
questions, contact the manufacturer.
Tools and Components Required
Electrical Requirements
- The LED driver must be supplied with 120-277 VAC, 50/60 Hz, and connected to an individual properly grounded branch circuit, protected by a 15 or 20-ampere circuit breaker. Use min. 75°C supply conductor.
Grounding Instructions
- The grounding and bonding of the overall system shall be done in accordance with National Electric Code (NEC) Article 600 and local codes.
Tools and Components Required
- M4 Phillips head screwdriver.
- M5 Hex Phillips head screwdriver.
- M5 hexagon socket wrench head screwdriver
- UL/cUL Recognized wire connectors.
- Safety tether and fitting hook.
Provided in the Package
- Luminaire with 10’ cord and hook
- Accessory Refractor – ordered separate
- Accessory Drop Lens and Clamp – ordered separate
- Accessory Male and Female Hook – ordered separate
- Accessory U-Bracket – ordered separate
- Accessory Safety Tether – ordered separate
Accessory List
ACCESSORY NAME | PRODUCT CODE | DESCRIPTION |
---|---|---|
Refractor | 93099795 | 16” High bay Moonglow™ refractor 80 |
Drop Lens and Clamp | 93083042 | 16” Conical Drop Lens with Clamp |
Pendant Male Hook | 14686 | Pendant Loop, 3/4” Male NPT |
Pendant Female Hook | 27414 | Pendant Loop, 3/4” Female NPSC |
U-Bracket | 93099238 | LPS U-bracket Wall Mount |
Safety Tether | 93099239 | LPS Safety tether (0.71m/2.3ft) |
Installation of Units
- Carefully unpack the LPS fixture and optional refractor. Properly inspect each unit for defects before installing. Wear work gloves to prevent dirt and oil from being transferred to the luminaire.
- Choose an appropriate mounting method for the luminaire. Follow all UL/cUL, NEC, and minimum load rating guidelines when selecting and installing a chain or cable.
LPS FIXTURE WEIGHT
**** Fixture| 120-277V Version w/o accessory| 120-277V Version w/ accessory
---|---|---
LPS0XXX| 8.8lbs/4.0kg| 12.1lbs/5.5kg
-
First, unfasten the M4 screw of the luminaire and carefully tighten the hook on the luminaire by the tool. Fix the anti-rotation M4 screw to secure the hook to the fixture.
-
Optional: To install a safety tether, unfasten one screw from the driver enclosure and put the safety tether on the bolt. Use a screwdriver to secure the tether to the driver enclosure and heatsink.
Refractor Installation (optional)
If using a refractor, attach the refractor to the luminaire using the provided lock bolts and plastic nuts. All 4 bolts must be used to secure the refractor to the refractor brackets.
-
Arrange all four brackets around the lens frame.
-
Fasten each bracket to the lens frame with a self-tapping screw
-
Align holes in the refractor over the standoffs on the brackets and fit in place.
-
Secure the refractor place using plastic nuts.
NOTE: Only tighten the plastic nuts by hand, avoid the nuts unfastened from the luminaire by vibration
Hanging Options
Cable or Chain
Carefully connect the hanging hook on the luminaire to the selected mounting
chain or cable.
NOTE: Must ensure the structure and the suspending cable /chain are
suitable for the weight of the fixture.
NOTE: Ensure the M4 screw on the hook is screwed into the hook correctly.
Pendant
If mounting to a pendant solution, attach an appropriate mounting hook to the
fixture ring, ensuring set screws or clips are securely in place. Attach the
threaded hook end to the pendant pipe and use an appropriate J-Box cover.
BRAND | HOOK | THREAD |
---|---|---|
Current | Pedant LOOPF | 3/4” Female NPSC |
Current | Pedant LOOPFM | 3/4” Male NPT |
U-Bracket
If installing a U-bracket wall mounting the fixture, fix the U-bracket with
two bolts and washers on the side of the driver enclosure. Suggest using a
3/8” (M10) screw and thickness 2.0mm min washer to fix the bracket on the
wall.
NOTE: If changing the direction of the fixture is required, loosen the M5
screws and tilt the luminaire to determine direction. If determined, use a
hexagon socket wrench to fix the screw tightly.
Electrical Connections
-
Connect the wires from the fixture following all NEC and local electrical codes. If a dimming wire connection is required, pull out the dimming wire from the cable clip, and carefully press back the plastic cover on the heatsink.
NOTE: Prior to installation, disconnect all incoming power to the fixture.
NOTE: Must use UL and cUL listed canopy for AC line connected to the branch circuit, also must seal the seam using silicone sealant between the canopy and junction
box, when finishing the wire connection.
NOTE: Must use UL and cUL listed waterproof strain relief bushing for the cable of branch circuit connection. -
If a dimming wire connection is required, pull out the dimming wire from the cable clip, and carefully press back the plastic cover on the heatsink.
NOTE: Must strip the cable jacket. Also, need to strip off 10mm from the violet and gray wires.
NOTE: Must use the waterproof connector to connect the dimming wire.
Wiring Diagram
Risk of Damage: Must use UL-approved conduit fittings for all enclosure box
connections to prevent wire cuts by sharp edges and excessive strain on
wiring. This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation. CAN ICES-005 (A) /
NMB-005 (A)
Note: This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE
monogram are trademarks of the
General Electric Company and are used under license. Information provided is
subject to change without
notice. All values are designed or typical values when measured under
laboratory conditions.
IND506 (Rev 04/02/2021)
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>