GE APPLIANCES IND506 Lumination LED Luminaire Installation Guide

June 4, 2024
GE Appliances

GE logo 2

Lumination® LED Luminaire
LPS Series
Installation Guide
IND506

IND506 Lumination LED Luminaire

BEFORE YOU BEGIN
Read these instructions completely and carefully.

WARNING

RISK OF ELECTRIC SHOCK

  • Turn the power off before inspection, installation or removal.
  • Properly ground electrical enclosure.

RISK OF FIRE

  • Follow all NEC and local codes.
  • Use only UL-approved wire for input/output connections.
    Only use size 18 AWG.

Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.

Tools and Components Required

Electrical Requirements

  • The LED driver must be supplied with 120-277 VAC, 50/60 Hz, and connected to an individual properly grounded branch circuit, protected by a 15 or 20-ampere circuit breaker. Use min. 75°C supply conductor.

Grounding Instructions

  • The grounding and bonding of the overall system shall be done in accordance with National Electric Code (NEC) Article 600 and local codes.

Tools and Components Required

  • M4 Phillips head screwdriver.
  • M5 Hex Phillips head screwdriver.
  • M5 hexagon socket wrench head screwdriver
  • UL/cUL Recognized wire connectors.
  • Safety tether and fitting hook.

Provided in the Package

  • Luminaire with 10’ cord and hook
  • Accessory Refractor – ordered separate
  • Accessory Drop Lens and Clamp – ordered separate
  • Accessory Male and Female Hook – ordered separate
  • Accessory U-Bracket – ordered separate
  • Accessory Safety Tether – ordered separate

Accessory List

ACCESSORY NAME PRODUCT CODE DESCRIPTION
Refractor 93099795 16” High bay Moonglow™ refractor 80
Drop Lens and Clamp 93083042 16” Conical Drop Lens with Clamp
Pendant Male Hook 14686 Pendant Loop, 3/4” Male NPT
Pendant Female Hook 27414 Pendant Loop, 3/4” Female NPSC
U-Bracket 93099238 LPS U-bracket Wall Mount
Safety Tether 93099239 LPS Safety tether (0.71m/2.3ft)

Installation of Units

  1. Carefully unpack the LPS fixture and optional refractor. Properly inspect each unit for defects before installing. Wear work gloves to prevent dirt and oil from being transferred to the luminaire.
  2. Choose an appropriate mounting method for the luminaire. Follow all UL/cUL, NEC, and minimum load rating guidelines when selecting and installing a chain or cable.
    LPS FIXTURE WEIGHT
    **** Fixture| 120-277V Version w/o accessory| 120-277V Version w/ accessory
    ---|---|---
    LPS0XXX| 8.8lbs/4.0kg| 12.1lbs/5.5kg

GE APPLIANCES IND506 Lumination LED Luminaire - fig 1

  1. First, unfasten the M4 screw of the luminaire and carefully tighten the hook on the luminaire by the tool. Fix the anti-rotation M4 screw to secure the hook to the fixture.

  2. Optional: To install a safety tether, unfasten one screw from the driver enclosure and put the safety tether on the bolt. Use a screwdriver to secure the tether to the driver enclosure and heatsink.
    Refractor Installation (optional)
    GE APPLIANCES IND506 Lumination LED Luminaire - fig 3
    If using a refractor, attach the refractor to the luminaire using the provided lock bolts and plastic nuts. All 4 bolts must be used to secure the refractor to the refractor brackets.
    GE APPLIANCES IND506 Lumination LED Luminaire - fig 4

  3. Arrange all four brackets around the lens frame.
    GE APPLIANCES IND506 Lumination LED Luminaire - fig 5

  4. Fasten each bracket to the lens frame with a self-tapping screw

  5. Align holes in the refractor over the standoffs on the brackets and fit in place.

  6. Secure the refractor place using plastic nuts.
    NOTE: Only tighten the plastic nuts by hand, avoid the nuts unfastened from the luminaire by vibration

Hanging Options

Cable or Chain
Carefully connect the hanging hook on the luminaire to the selected mounting chain or cable.
NOTE: Must ensure the structure and the suspending cable /chain are suitable for the weight of the fixture.
NOTE: Ensure the M4 screw on the hook is screwed into the hook correctly.

GE APPLIANCES IND506 Lumination LED Luminaire - fig 8

Pendant
If mounting to a pendant solution, attach an appropriate mounting hook to the fixture ring, ensuring set screws or clips are securely in place. Attach the threaded hook end to the pendant pipe and use an appropriate J-Box cover.

GE APPLIANCES IND506 Lumination LED Luminaire - fig 9

BRAND HOOK THREAD
Current Pedant LOOPF 3/4” Female NPSC
Current Pedant LOOPFM 3/4” Male NPT

U-Bracket
If installing a U-bracket wall mounting the fixture, fix the U-bracket with two bolts and washers on the side of the driver enclosure. Suggest using a 3/8” (M10) screw and thickness 2.0mm min washer to fix the bracket on the wall.
NOTE: If changing the direction of the fixture is required, loosen the M5 screws and tilt the luminaire to determine direction. If determined, use a hexagon socket wrench to fix the screw tightly.

GE APPLIANCES IND506 Lumination LED Luminaire - fig 10

Electrical Connections

  1. Connect the wires from the fixture following all NEC and local electrical codes. If a dimming wire connection is required, pull out the dimming wire from the cable clip, and carefully press back the plastic cover on the heatsink.
    NOTE: Prior to installation, disconnect all incoming power to the fixture.
    NOTE: Must use UL and cUL listed canopy for AC line connected to the branch circuit, also must seal the seam using silicone sealant between the canopy and junction
    box, when finishing the wire connection.
    NOTE: Must use UL and cUL listed waterproof strain relief bushing for the cable of branch circuit connection.

  2. If a dimming wire connection is required, pull out the dimming wire from the cable clip, and carefully press back the plastic cover on the heatsink.
    NOTE: Must strip the cable jacket. Also, need to strip off 10mm from the violet and gray wires.
    NOTE: Must use the waterproof connector to connect the dimming wire.

Wiring Diagram

GE APPLIANCES IND506 Lumination LED Luminaire - fig 13

Risk of Damage: Must use UL-approved conduit fittings for all enclosure box connections to prevent wire cuts by sharp edges and excessive strain on wiring. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. CAN ICES-005 (A) / NMB-005 (A)
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without
notice. All values are designed or typical values when measured under laboratory conditions.
IND506 (Rev 04/02/2021)

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GE Appliances User Manuals

Related Manuals