CASPR TECHNOLOGIES CASPR PRO Duct Mounted Air Purification System Owner’s Manual
- May 15, 2024
- CASPR TECHNOLOGIES
Table of Contents
- CASPR TECHNOLOGIES CASPR PRO Duct Mounted Air Purification System
- Product Information
- Product Usage Instructions
- IMPORTANT SAFETY INSTRUCTIONS
- Specifications
- Product Contents
- Installation Hardware
- Electrical Requirement
- Orientation and Airflow
- Indicator Lights
- Maintenance
- Troubleshooting Q&A
- Warranty Information
- Documents / Resources
CASPR TECHNOLOGIES CASPR PRO Duct Mounted Air Purification System
Product Information
Specifications
- Unit: CASPR Pro 400 | CASPR Pro 1000 | CASPR Pro 2500 | CASPR Pro 5000
- Coverage Size (HxWxD): Varies per unit
- Weight: Varies per unit
- Watts: Varies per unit
- Amps DC 24V: Varies per unit
- Amps AC 120V: Varies per unit
Product Usage Instructions
Principles of Operation
- The CASPR PRO utilizes Natural Catalytic Conversion (NCC) to produce safe levels of hydrogen peroxide.
- The NCC technology activates a proprietary metal catalytic coating using high-intensity light, converting water vapor into hydrogen peroxide.
- This acts as an oxidizer, inactivating pathogens in the air and on surfaces.
Safety Instructions
- Ensure to read all safety instructions before using the product. Disconnect the unit from the power supply before servicing, especially when UV light is in operation.
- Maintain a minimum distance of 24 inches from the heat exchanger to prevent combustion of the photocatalytic matrix.
Installation
- Mount the unit into the central HVAC duct system.
- Use only genuine CASPR Group replacement parts.
- Refer to the installation hardware provided.
- Recommended tools for installation include a Hole Saw Bit, Drill Bit, and Drill/Power Driver.
FAQ
Q: How often should the NCC Cell and bulb be replaced?
- A: The NCC Cell and bulb should be replaced every 18-24 months. Contact your distributor for new replacements.
Q: Where can I find the NCC Cell Part Number for replacement?
- A: CASPR Pro 400 NCC Cell Part Number: CELL-HV-5-001-AP CASPR Pro 1000 NCC Cell Part Number: CELL-HV-9-001-AP CASPR Pro 2500 and 5000 NCC Cell Part Number: CELL-HV-14-001-AP
Congratulations
-
On your purchase of a CASPR Group-enhanced air and surface disinfection system. This unit is designed to be mounted into central HVAC duct systems.
Please read and follow all safety warnings and service procedures outlined in this manual. Use only genuine CASPR Group replacement parts available from your CASPR Group Distributor. -
If you have any questions concerning this or any CASPR Group product, contact your CASPR Group Distributor.
Principles of Operation
- CASPR PRO uses Natural Catalytic Conversion (NCC) to generate safe, low levels of hydrogen peroxide.
- NCC technology replicates natural purifying processes by using a high-intensity light to activate a proprietary metal catalytic coating, converting water vapor into hydrogen peroxide.
- Hydrogen peroxide acts as an oxidizer inactivating surface and air pathogens. It can compromise cellular integrity by disrupting cell walls, or internal molecular structures, rendering contaminants harmless.
- To learn more about this and other CASPR Group products and technologies, please visit our website at www.CASPRgroup.com.
IMPORTANT SAFETY INSTRUCTIONS
- When using an electrical appliance, basic precautions should always be taken.
- READ ALL INSTRUCTIONS BEFORE USING THIS PRODUCT
WARNING! To reduce the risk of fire, electrical shock, or injury:
- Use only as described in this manual.
- Do not attempt to repair or adjust any of the electrical or mechanical functions. Contact Customer Service for service information.
- Do not use it outdoors or on wet surfaces.
- Do not allow it to be used as a toy. Do not allow children around the unit.
- Do not handle it with wet hands.
- Do not touch the NCC bulb with bare hands.
WARNING
- WARNING! – UV light in operation. Disconnect the unit from the power supply before servicing. Failure to follow warnings may result in severe eye damage.
- WARNING! The unit should be mounted at least 24 inches from the heat exchanger or heating element. Placing the photocatalytic cell too close to the heating element can cause the photocatalytic matrix to combust.
- To reduce the risk of electric shock, this equipment may have a grounding-type plug that has a third (grounding) pin. This plug will only fit into a grounding-type power outlet.
- If the plug does not fit into the outlet, contact an HVAC professional to install the proper outlet. Do not alter the plug in any way.
Specifications
**Unit| ****Coverage| ****Size (HxWxD)*| ****Weight|
****Watts| Amps DC 24V| Amps AC 120V
---|---|---|---|---|---|---
** CASPR Pro 400| 4,000 ft3| 9.75” x 9.75x 8”| 3.0 lb|
8| 0.52| 0.28
CASPR Pro 1000| 10,000 ft3| 9.75” x 9.75” x 11”| 3.1
lb| 10| 0.64| 0.30
CASPR Pro 2500| 25,000 ft3| 9.75” x 9.75” x 16.75”|
3.3 lb| 18| 1.0| 0.44
CASPR Pro 5000| 50,000 ft3| 10” x 11.3” x 16.75”| 5.0
lb| 36| 2.0| **** 0.74
Product Contents
Installation Hardware
- (8) #8 3/4 Hex Self-tapping Screws
- (4) Flange Nuts
- (2 or 4) Cell Mounting Screws (2 screws per NCC Cell)
Replacement Parts
- The NCC Cell and bulb should be replaced every 18-24 months.
- Please contact your distributor for new replacements.
- CASPR Pro 400 NCC Cell Part Number: CELL-HV-5-001-AP
- CASPR Pro 1000 NCC Cell Part Number: CELL-HV-9-001-AP
- CASPR Pro 2500 and 5000 NCC Cell Part Number: CELL-HV-14-001-AP
Recommended Installation Tools
- A – 4” Hole Saw Bit
- B – 3/8” Drill Bit
- C – Drill/Power Driver
- D – Utility Knife
- E – Tin Snips
- F – Phillips Head Screwdriver
Electrical Requirement
- All CASPR Pro duct-mounted units run on DC 24V. Each unit comes with a power adapter that will take AC 100-240V. We recommend locating the unit within 6 ft. of a standard 120V Grounded outlet to plug in directly.
- Long-term use of an extension cord is not recommended due to safety considerations.
- If an outlet is not available within 6 feet of the installation location, you may hardwire the unit into the HVAC system using a licensed HVAC professional.
Hard-Wiring Requirement
- Permanent wiring of the unit into your HVAC system may be completed using a hardwire assembly (sold separately) and should be done by a licensed HVAC Installer or Electrical Contractor only.
- For 110V or 220V Applications: Black = L1, White = Neutral, Green = Ground
- For International Applications: Brown = L1, Blue = L2, Green/Yellow = Ground
- If DC 24V is available, splice the wire between the brick and the cell housing to wire directly to the unit circumventing the power brick.
- If the voltage is higher than AC 120-240V, you will need a transformer that converts your supply voltage to DC 24V eliminating the power brick.
- When hardwiring any of these units please be mindful of the Maximum Amp draw that your power supply transformer can handle to prevent damage (Equation: Power Supply Transformer Amps / CASPR Volts = Maximum Amp Load).
Installation Requirement
- The unit should be installed downstream of the air handler in the HVAC system.
- Additional HVAC units may be installed in the Return Plenum for added protection and to keep the internal parts clean.
- The duct work around the installation area should be cleaned and dry to ensure proper adhesion of the gasket materials and any tape used.
- One to two 4” circular openings will need to be cut into the existing ductwork to install the unit properly. (2-for CASPR Pro 5000; 1-CASPR Pro 400, 1000, 2500).
Orientation and Airflow
- When installing the CASPR Pro 5000, make sure the airflow moves through the NCC cells as indicated by the blue arrow.
- Make sure, when installing several units at once, that they are staggered to minimize overlap of NCC cells and maximize airflow.
- When installing the CASPR Pro 400, 1000, and 2500 make sure the airflow moves through the NCC cells as indicated by the blue arrow.
- Make sure, when installing several units at once, that they are staggered to minimize overlap of NCC cells and maximize airflow.
Installation Instructions
- Diagrams are representative of the CASPR Pro 400, 1000, and 2500. The steps are the same for the CASPR Pro 5000 with slight variations in orientation and number of holes.
- Please refer to the airflow and orientation section above for proper installation of all models.
- Find a suitable location to mount your Unit.
- If necessary, cut away insulation for your plate to adhere to the duct.
- Using the Adhesive Mounting Bracket, trace the hole location onto the duct.
- Keep in mind the CASPR Pro 5000 orientation before cutting (Refer to orientation and airflow above).
- Use the Hole Saw and Drill to cut out the marked hole.
Alternative Cutting Method
- Using the Adhesive Mounting Bracket, trace the hole location onto the duct. Keep in mind the CASPR Pro 5000 orientation before cutting (Refer to orientation and airflow above).
- Drill holes around the outside edges of the previously marked hole but inside the outer holes of the Adhesive Mounting Bracket.
- Use the Tin Snips to cut out the space around the marked hole.
- Remove the plastic backing on your Adhesive Mounting Bracket.
- Press the Adhesive Mounting Bracket onto the duct. Secure with the (8 Self-Tapping Screws.
- Remove the packing foam from the NCC Cell
- DO NOT TOUCH BULB WITH BARE HANDS
- Connect the Cell to the Ballast Housing using the (2) Cell Mounting Screws provided. Repeat this step if you have a double-cell unit.
- Place the unit and cell through the opening and align the four studs with the four holes in the Ballast Housing. Secure the unit with the (4) Flange Nuts until it is flush with the duct. MAKE SURE THE AIRFLOW MOVES THROUGH THE NCC CELL (Refer to orientation and airflow above).
- Plug the Power Cable into the receptacle or have a Licensed Electrician or HVAC Installer hard wire the unit directly into the HVAC system.
Hardwire Instructions
If you plan to Hardwire your CASPR Pro unit directly into the electrical supply you may do so using the hardwire power assembly (sold separately) which accepts AC 120- 277V (1.8 A) and outputs DC 24V (2.5 A).
- Place the hardwire assembly at the bottom of the CASPR Unit power supply and attach as demonstrated in the figures below.
- Once the assembly is connected to the unit, fasten the two screws to secure the assembly and the CASPR device together.
- Run an 18-gauge 2-wire cord through the wire outlet (left image below) and connect the power supply to the transformer (right image below). Here, red represents AC/L, and black represents AC/N. Note that the male connector is already wired into the transformer.
- Once the unit is connected to the proper power supply and your unit is running you have successfully connected the hardwired power supply.
Indicator Lights
- Unit Power – The red light is ON.
- Cell Power – The red light is ON.
- Red light ON – Bulbs are on.
- Red light OFF – bulb has burned out and needs to be replaced. Double units have one light for each lamp.
NOTE: THIS MODEL IS NOT WIFI ENABLED; The Wi-Fi indicator light will not function
Maintenance
- Your CASPR Pro unit requires no periodic maintenance beyond the normal replacement of the NCC cells and bulbs every 18-24 months. We recommend the replacement of the NCC cells and bulbs, even if the bulb appears to be operating normally.
- The bulb operation indicator on the face of the unit will glow when the bulb is in use. If the indicator does not glow and the unit has power, the NCC cell and bulb should be replaced.
Disposal of the NCC Cell
- Please do not throw the used NCC Cells or bulbs in the garbage.
- The high-intensity bulb used in the CASPR Pro unit contains a very small amount of mercury. Contact your local Waste Management Center for a proper disposal procedure.
Changing the NCC Cell
- Remove the Power Cable from the receptacle or ensure the unit isn’t powered.
- Remove the (4) Flange Nuts from the Unit Cover and Remove the Unit Cover and NCC Cell.
- Remove the (2) Screws holding the NCC Cell in place and remove the NCC Cell from the Unit Cover.
- Remove the packing foam from the new NCC Cell
- Exchange the Old NCC Cell with the new NCC Cell and replace the (2) Screws that hold it in place.
- Replace the Cover and NCC Cell in the duct and secure with the (4) Flange Nuts. MAKE SURE THE AIRFLOW MOVES THROUGH THE NCC CELL (Refer to orientation and airflow above).
- Place the Power Cable back into the receptacle or repower your unit.
Troubleshooting Q&A
- How big is the cut hole?
- A. You must cut a 4” diameter hole.
- What power does it run on? (Voltage)
- A. You may use an AC 120VAC (With transformer) or a DC/AC 24V Direct. Remember that the wire must be cut and spliced to properly connect to the device (Please see hard wiring requirements).
- How do I know that it is working?
- A. The Indicator Lights, on the cell housing, will be on (red) indicating that the ballast and NCC cell have power and are on. Please see the Indicator Lights section above for more information.
- What should I do if there is no power to the unit?
- A. Check each connection point to ensure it is properly connected, if this does not work, please contact your distributor.
- How often does the bulb need to be changed?
- A. The NCC cells and bulbs need to be replaced once every 18-24 months.
- How does it mount? (Adhesive or Screws)
- A. It mounts using the self-tapping screws NOT the adhesive.
Warranty Information
- LIMITED 3-YEAR WARRANTY ON CASPR GROUP UNITS AND 1-YEAR WARRANTY ON CASPR GROUP REPLACEMENT PARTS
- Customers should not repackage and ship the CASPR Pro unit due to the possibility of irreparable damage.
- For warranty service, please contact your CASPR Group Distributor for the address of the nearest service center, email warranty@casprgroup.com call Customer Service at 844-717-8819.
WHAT IS COVERED BY THIS WARRANTY
- We warrant the CASPR Pro to the Customer, subject to the conditions below, against defects in workmanship or material, provided that the products are returned to a service location within three (3) years from the date of purchase.
INSTALLATION AND MAINTENANCE REQUIREMENTS
- This warranty is expressly conditioned upon proper installation, operation, cleaning, and maintenance, all under the Owner’s Manual.
- Failure to meet any of these requirements will void this warranty. Servicing of your CASPR Pro by parties other than our authorized representatives and/or using parts other than genuine parts will also void this warranty.
HOW TO OBTAIN WARRANTY SERVICE
- Customer must contact their CASPR Group Distributor and provide proof of purchase within the above periods.
- We will repair replace and return the product, without charge and within a reasonable time, subject to the conditions herein, if its examination shall disclose any part to be defective in workmanship or material.
- If we, at our discretion, are unable to repair the product after a reasonable number of attempts, we will provide either a refund of the purchase price or a replacement unit, at the company’s option.
WHAT IS NOT COVERED BY THIS WARRANTY
- Ordinary wear and tear shall not be considered a defect in workmanship or material.
- These warranties do not apply to filters nor for loss or damage caused by accident, fire, abuse, misuse, improper installation, leaking, modification, misapplication, or by any repairs other than those provided by our authorized Service Center.
- This warranty is non-transferable.
MISSING SERIAL NUMBERS AND UNAUTHORIZED CHANNELS
- If a valid serial number is missing from the product, the warranty will be voided. CASPR Group products are authorized for sale through CASPR Group Distributors only.
- Warranties are voided if a product is purchased through unauthorized channels; this includes websites that are not authorized to use CASPR Group’s trademarked names, images, and logos as well as Internet auction sites (e.g. eBay and Craigslist).
- To confirm warranty coverage before purchasing a product, contact CASPR Group at 844-717-8819 with the serial number located on the back of the unit.
- EXCLUSION OF OTHER WARRANTIES AND CONDITIONS EXCEPT AS PROVIDED HEREIN, WE MAKE NO REPRESENTATION OR WARRANTY OF ANY KIND.
- ALL OTHER WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, ARE HEREBY EXPRESSLY DISCLAIMED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
- LIMITATION OF LIABILITY FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES WE SHALL NOT, IN ANY CASE, BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING FROM BREACH OF EXPRESSED OR IMPLIED WARRANTIES, CONDITIONS, GUARANTEES OR REPRESENTATIONS, BREACH OF CONTRACT, NEGLIGENCE OR ANY OTHER LEGAL THEORY.
- Such excluded damages include but are not limited to, loss of profits or revenue, and loss of the use of the products, and any loss caused by leaks or other water damage.
FOR U.S. APPLICATION ONLY
- This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
- Some states do not allow limitations on warranties or remedies for breaches. In such states, the above limitations may not apply to you.
FOR CANADIAN APPLICATION ONLY
- Exclusion of Subsequent Owners: Except as otherwise required by applicable legislation, this warranty is not transferable.
- This warranty gives you specific legal rights and you may also have other rights which vary from province to province.
- Some provinces and territories do not allow limitations on warranties or remedies for breach. In such provinces or territories, the above limitations may not apply to you.
- If any provision of this warranty or part thereof is held by a court of competent jurisdiction to be invalid, illegal, or unenforceable, the validity, legality, and enforceability of the remaining provisions or parts thereof will not in any way be affected or impaired within the jurisdiction of that court. This entire warranty shall continue to be valid, legal, and enforceable in any jurisdiction where a similar determination has not been made.
This warranty is provided by CASPR Group, Inc
- 4505 Excel Parkway, #600
- Addison, TX 75001
SERVICE
- Every effort is made to ensure customers receive an up-to-date instructions manual on the use of our products; however, from time to time, modifications to our products may without notice make the information contained herein subject to alteration.
- For the latest information, please visit our website.
- www.CASPRgroup.com
- 4505 Excel Pkwy Suite 600,
- Addison, TX 75001
- 844-717-8819
Documents / Resources
|
CASPR TECHNOLOGIES CASPR PRO Duct Mounted Air Purification
System
[pdf] Owner's Manual
400, 1000, 2500, 5000, CASPR PRO Duct Mounted Air Purification System, CASPR
PRO, Duct Mounted Air Purification System, Mounted Air Purification System,
Air Purification System, Purification System, System
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>