The CASPR Technologies enhanced air and surface disinfection system is
designed to be mounted into central HVAC duct systems. It uses Natural
Catalytic Conversion (NCC) technology to generate safe, low levels of hydrogen
peroxide. The NCC technology replicates natural purifying processes by using a
high-intensity light to activate a proprietary metal catalytic coating,
converting water vapor into hydrogen peroxide. Hydrogen peroxide acts as an
oxidizer inactivating surface and air pathogens. The CASPR Pro units are
available in four models: CASPR Pro 400, CASPR Pro 1000, CASPR Pro 2500, and
CASPR Pro 5000. Each model has different coverage sizes, dimensions, weights,
and power specifications.
Specifications
Unit | Coverage Size (HxWxD)* | Weight | Watts | Amps DC 24V | Amps AC 120V |
---|---|---|---|---|---|
CASPR Pro 400 | 4,000 ft3 | 9.75 x 9.75 x 8 | 3.0 lb | 8 | 0.52 |
CASPR Pro 1000 | 10,000 ft3 | 9.75 x 9.75 x 11 | 3.1 lb | 10 | 0.64 |
CASPR Pro 2500 | 25,000 ft3 | 9.75 x 9.75 x 16.75 | 3.3 lb | 18 | 1.0 |
CASPR Pro 5000 | 50,000 ft3 | 10 x 11.3 x 16.75 | 5.0 lb | 36 | 2.0 |
The product contents include an NCC Cell, mounting bracket, ballast housing, power supply (hardwired and plug-in), and installation hardware.
Replacement Parts
The NCC Cell and bulb should be replaced every 18-24 months. Please contact your distributor for new replacements.
- CASPR Pro 400 NCC Cell Part Number: CELL-HV-5-001-AP
- CASPR Pro 1000 NCC Cell Part Number: CELL-HV-9-001-AP
- CASPR Pro 2500 and 5000 NCC Cell Part Number: CELL-HV-14-001-AP
Recommended Installation Tools
-
8 3/4 Hex Self-tapping Screws
- Flange Nuts
Product Usage Instructions
- Read the manual carefully for proper procedures and operations.
- Ensure the unit is mounted into central HVAC duct systems.
- Follow all safety warnings and service procedures outlined in the manual.
- Use only genuine CASPR Technologies replacement parts available from your CASPR Technologies Distributor.
- If you have any questions or concerns, contact your CASPR Technologies Distributor.
- Disconnect the unit from the power supply before servicing to avoid severe eye damage.
- Mount the unit at least 24 inches from the heat exchanger or heating element to prevent combustion of the photocatalytic matrix.
- If necessary, have an HVAC professional install the proper outlet for the grounding-type plug.
- Do not alter the plug in any way.
Note: For detailed installation instructions, please refer to the manual or visit the CASPR Technologies website at www.CASPRtech.com.
Congratulations
on your purchase of a CASPR Technologies enhanced air and surface disinfection
system. This unit is designed to be mounted into central HVAC duct systems.
Please read and follow all safety warnings and service procedures outlined in
this manual. Use only genuine CASPR Technologies replacement parts available
from your CASPR Technologies Distributor. If you have any questions concerning
this or any CASPR Technologies product, contact your CASPR Technologies
Distributor.
Principles of Operation
CASPR PRO uses Natural Catalytic Conversion (NCC) to generate safe, low levels
of hydrogen peroxide. NCC technology replicates natural purifying processes by
using a high-intensity light to activate a proprietary metal catalytic
coating, converting water vapor into hydrogen peroxide. Hydrogen peroxide acts
as an oxidizer inactivating surface and air pathogens. It can compromise
cellular integrity by disrupting cell walls, or internal molecular structures,
rendering contaminants harmless. To learn more about this and other CASPR
Technologies products, please visit our website at
www.CASPRtech.com.WARNING! – UV light in
operation. Disconnect the unit from the power supply before servicing. Failure
to follow warnings may result in severe eye damage.
WARNING! The unit should be mounted at least 24 inches from the heat
exchanger or heating element. Placing the photocatalytic cell too close to the
heating element can cause the photocatalytic matrix to combust. To reduce the
risk of electric shock, this equipment may have a grounding-type plug that has
a third (grounding) pin. This plug will only fit into a grounding-type power
outlet. If the plug does not fit into the outlet, contact an HVAC professional
to install the proper outlet. Do not alter the plug in any way.
Specifications
Unit
| ****
Coverage
| ****
**Size (HxWxD)***
| ****
Weight
| ****
Watts
| Amps DC 24V| Amps AC 120V
---|---|---|---|---|---|---
CASPR Pro 400
| ****
4,000 ft3
| ****
9.75” x 9.75x 8”
| ****
3.0 lb
| ****
8
| ****
0.52
| ****
0.28
CASPR Pro 1000
| ****
10,000 ft3
| ****
9.75” x 9.75” x 11”
| ****
3.1 lb
| ****
10
| ****
0.64
| ****
0.30
CASPR Pro 2500
| ****
25,000 ft3
| ****
9.75” x 9.75” x 16.75”
| ****
3.3 lb
| ****
18
| ****
1.0
| ****
0.44
CASPR Pro 5000
| ****
50,000 ft3
| ****
10” x 11.3” x 16.75”
| ****
5.0 lb
| ****
36
| ****
2.0
| ****
0.74
Product Contents
Installation Hardware
- (8) #8 3/4 Hex Self-tapping Screws
- (4) Flange Nuts
- (2 or 4) Cell Mounting Screws (2 screws per NCC Cell)
Replacement Parts
The NCC Cell and bulb should be replaced every 18-24 months. Please contact
your distributor for new replacements.
- CASPR Pro 400 NCC Cell Part Number: CELL-HV-5-001-AP
- CASPR Pro 1000 NCC Cell Part Number: CELL-HV-9-001-AP
- CASPR Pro 2500 and 5000 NCC Cell Part Number: CELL-HV-14-001-AP
Recommended Installation Tools
- 4” Hole Saw Bit B – 3/8” Drill Bit
- Drill/Power Driver
- Utility Knife
- Tin Snips
- Phillips Head Screwdriver
Electrical Requirement
All CASPR Pro duct-mounted units run on DC 24V. Each unit comes with a power
adapter that will take AC 100-240V. We recommend locating the unit within 6
ft. of a standard 120V Grounded outlet to plug in directly. Long-term use of
an extension cord is not recommended due to safety considerations. If an
outlet is not available within 6 feet of the installation location, you may
hardwire the unit into the HVAC system using a licensed HVAC professional.
Hard-Wiring Requirement
Permanent wiring of the unit into your HVAC system may be completed using a
hardwire assembly (sold separately) and should be done by a licensed HVAC
Installer or Electrical Contractor only.
- For 110V or 220V Applications: Black = L1, White = Neutral,
- Green = Ground
- For International Applications: Brown = L1, Blue = L2,
- Green/Yellow = Ground
If DC 24V is available, splice the wire between the brick and the cell housing to wire directly to the unit circumventing the power brick. If the voltage is higher than AC 120-240V, you will need a transformer that converts your supply voltage to DC 24V eliminating the power brick. When hardwiring any of these units please be mindful of the Maximum Amp draw that your power supply transformer can handle to prevent damage (Equation: Power Supply Transformer Amps / CASPR Volts = Maximum Amp Load).
Installation Requirement
- The unit should be installed downstream of the air handler in the HVAC system. Additional HVAC units may be installed in the Return Plenum for added protection and to keep the internal parts clean.
- The duct work around the installation area should be cleaned and dry to ensure proper adhesion of the gasket materials and any tape used.
- One to two 4” circular openings will need to be cut into the existing ductwork to install the unit properly. (2- for CASPR Pro 5000; 1-CASPR Pro 400, 1000, 2500).
Orientation and Airflow
When installing the CASPR Pro 5000, make sure the airflow moves through the
NCC cells as indicated by the blue arrow. Make sure, when installing several
units at once, that they are staggered to minimize the overlap of NCC cells
and maximize airflow. When installing the CASPR Pro 400, 1000, and 2500 make
sure The airflow moves through the NCC cells as indicated by the blue arrow.
Make sure, when installing several units at once, that they are staggered to
minimize the overlap of NCC cells and maximize airflow.
Installation Instructions
Diagrams are representative of the CASPR Pro 400, 1000, and 2500. The steps
are the same for the CASPR Pro 5000 with slight variations in orientation and
number of holes. Please refer to the airflow and orientation section above for
proper installation of all models.
- Find a suitable location to mount your Unit.
- If necessary, cut away insulation for your plate to adhere to the duct.
- Using the Adhesive Mounting Bracket, trace the hole location onto the duct. Keep in mind the CASPR Pro 5000 orientation before cutting (Refer to orientation and airflow above).
- Use the Hole Saw and Drill to cut out the marked hole.
Alternative Cutting Method
-
Using the Adhesive Mounting Bracket, trace the hole location onto the duct. Keep in mind the CASPR Pro 5000 orientation before cutting (Refer to orientation and airflow above).
-
Drill holes around the outside edges of the previously marked hole but inside the outer holes of the Adhesive Mounting Bracket.
-
Use the Tin Snips to cut out the space around the marked hole.
-
Remove the plastic backing on your Adhesive Mounting Bracket.
-
Press the Adhesive Mounting Bracket onto the duct. Secure with the (8 Self-Tapping Screws.
-
Remove the packing foam from the NCC Cell
-
Connect the Cell to the Ballast Housing using the (2) Cell Mounting Screws provided. Repeat this step if you have a double-cell unit.
-
Place the unit and cell through the opening and align the four studs with the four holes in the Ballast Housing. Secure the unit with the (4) Flange Nuts until it is flush with the duct. MAKE SURE THE AIRFLOW MOVES
THROUGH THE NCC CELL (Refer to orientation and airflow above). -
Plug the Power Cable into the receptacle or have a Licensed electrician or HVAC Installer hard wire the unit directly into the HVAC system.
Hardwire Instructions
If you plan to Hardwire your CASPR Pro unit directly into the electrical
supply you may do so using the hardwire power assembly (sold separately) which
accepts AC 120-277V (1.8 A) and outputs DC 24V (2.5 A).
- Place the hardwire assembly at the bottom of the CASPR Unit power supply and attach it as demonstrated in the figures below.
- Once the assembly is connected to the unit, fasten the two screws to secure the assembly and the CASPR device together.
- Run an 18-gauge 2-wire cord through the wire outlet (left image below) and connect the power supply to the transformer (right image below). Here, red represents AC/L, and black represents AC/N. Note that the male connector is already wired into the transformer.
- Hardwire Instructions (continued) Once the unit is connected to the proper power supply and your unit is running You have successfully connected the hardwired power supply.
Indicator Lights
- Unit Power – The red light is ON.
- Cell Power – The red light is ON.
- Red light ON – Bulbs are on.
- Red light OFF – bulb has burned out and needs to be replaced. Doubleunits have one light for each lamp.
NOTE: THIS MODEL IS NOT WIFI ENABLED; The Wi-Fi indicator light will not function
Maintenance
Your CASPR Pro unit requires no periodic maintenance beyond the normal replacement of the NCC cells and bulbs every 18-24 months. We recommend the replacement of the NCC cells and bulbs, even if the bulb appears to be operating normally. The bulb operation indicator on the face of the unit will glow when the bulb is in use. If the indicator does not glow and the unit has power, the NCC cell bulb should be replaced
Disposal of the NCC Cell
Please do not throw the used NCC Cells or bulbs in the garbage. v The high-
intensity bulb used in the CASPR Pro unit contains a very small amount of
mercury. Contact your local Waste Management Center for a proper disposal
procedure.
Changing the NCC Cell
- Remove the Power Cable from the receptacle or ensure the unit isn’t powered.
- Remove the (4) Flange Nuts from the Unit Cover and Remove the Unit Cover and NCC Cell.
- Remove the (2) Screws holding the NCC Cell in place and remove the NCC Cell from the Unit Cover.
Changing the NCC Cell Continued
- Remove the packing foam from the new NCC Cell
- Exchange the Old NCC Cell with the new NCC Cell and replace the (2) Screws that hold it in place.
- Replace the Cover and NCC Cell in the duct and secure with the
- Flange Nuts. MAKE SURE THE AIRFLOW MOVES THROUGH THE NCC CELL (Refer to orientation and airflow above).
- place the Power Cable back into the receptacle or repower your unit. Troubleshooting Q&A
How big is the cut hole?
A. You must cut a 4” diameter hole.
What power does it run on? (Voltage)
A. You may use an AC 120VAC (With transformer) or a DC/AC 24V Direct. Remember
that the wire must be cut and spliced in order to properly connect to the
device (Please see hard wiring requirements
How do I know that it is working?
A. The Indicator Lights, on the cell housing, will be on (red) indicating that
the ballast and NCC cell have power and are on. Please see the Indicator
Lights section above for more information.
What should I do if there is no power to the unit?
A. Check each connection point to ensure it is properly connected, if this
does not work, please contact your distributor.
How often does the bulb need to be changed?
A. The NCC cells and bulbs need to be replaced once every 18-24 months.
How does it mount? (Adhesive or Screws)
A. It mounts using the self-tapping screws NOT the adhesive
Warranty Information
NDS Sales LLC d/b/a CASPR Technologies (as “Seller”) offers the following Express Limited Warranty to a buying customer (a “Buyer”) of a CASPR product (the “Product”): Seller warrants to Buyer that (a) the Product will be free from defects caused by faulty workmanship or materials for three years from the date of purchase when operated under normal conditions and in accordance with Seller’s recommended use (the “Product Warranty Period),” and that (b) the Components (comprised of a bulb and a cell) will be free from defects caused by faulty workmanship or materials for one year from the date of purchase when operated under normal conditions and in accordance with Seller’s recommended use (the “Components Warranty Period).”
SELLER EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER EXPRESS OR
IMPLIED.
Should Buyer discover a covered defect within the Product Warranty Period or
the Components Warranty Period, Seller will repair or replace (at Seller’s
cost) the Product and/or the Components. Buyer’s sole and exclusive remedy for
Product or Component defects is limited to repair or replacement. To confirm
coverage or to schedule repair or replacement under this Express Limited
Warranty, the Buyer should contact the Seller at
www.casprtech.com/warranty and provide
the serial number located on the Product and proof of purchase. The absence of
a serial number or proof of purchase may void the Express Limited Warranty.
This Express Limited Warranty does not extend to or cover Product damage caused by accident, fire, flooding, exposure to temperature extremes, abuse, misuse, improper or unauthorized installation, modification, misapplication, or repairs performed by persons other than Seller. Repairs performed by persons other than Seller or Seller’s authorized representative will void the Express Limited Warranty. This Express Limited Warranty does not extend to or cover incidental or consequential damages incurred by Buyer arising from, related to, or in connection with, any Product or Component defects, including but not limited to downtime costs, loss of use, loss of revenue, and/or loss of profits.
SALES THROUGH DISTRIBUTOR OR RESELLER
To the extent the Product is purchased by the Buyer from an authorized CASPR
distributor or reseller, this Express Limited Warranty passes through to the
Buyer.
FOR U.S. APPLICATION ONLY
Product warranties are governed by state and federal laws and may vary from
state to state. This Express Limited Warranty provides the Buyer with specific
assurances regarding repair or replacement of the Product. Other warranties
are expressly negated.
FOR CANADIAN APPLICATION ONLY
Canadian, provincial, and territorial sales laws may govern implied
warranties. This Express Limited Warranty provides the Buyer with specific
assurances regarding repair or replacement of the Product. Other warranties
are expressly negated. Should there be a difference between this Express
Limited Warranty and Canadian law regarding implied warranties, Canadian law
will control.