CASPR TECHNOLOGIES CASPR MEDIK Hospital Grade Air and Surface Purifier Owner’s Manual
- May 15, 2024
- CASPR TECHNOLOGIES
Table of Contents
CASPR TECHNOLOGIES CASPR MEDIK Hospital Grade Air and Surface Purifier
Specifications
- Disinfection Technology: Natural Catalytic Conversion (NCC)
- Disinfection Method: Continuous HVAC Disinfectant
- Pathogens Reduced: MRSA, Norovirus, Aspergillus Niger, VRE, C. difficile, and more
- Replacement Bulbs: 9 Bulb Part Number: BULB-HV-9-002-CASPR, 14 Bulb Part Number: BULB-HV-14-002-CASPR
- Replacement Cells: 9 NCC Cell Part Number: CELL-HV-9-002-CASPR, 14 NCC Cell Part Number: CELL-HV-14-002-CASPR
Installation
-
Ensure the unit is mounted at least 24 inches away from the heat exchanger or heating element.
-
Clean and dry the ductwork around the installation area for proper adhesion.
-
Use the recommended installation tools: Hole Saw Bit, Drill
Bit, Drill/Power Driver, Utility Knife, STET, Phillips Head Screwdriver. -
Install the unit behind the filter in the HVAC system either upstream or downstream of the air handler.
Maintenance
- Disconnect the unit from the power supply before servicing to avoid UV light exposure.
- Regularly check and replace bulbs and NCC cells as needed.
FAQ
Q: How often should I replace the bulbs and NCC cells?
- A: It is recommended to replace the bulbs every [specified time frame] and NCC cells every [specified time frame] to ensure effective disinfection.
Q: Can the CASPR MEDIK unit be used in residential settings?
- A: The CASPR MEDIK unit is designed for commercial use in facilities to reduce microburden facility-wide, but it can also be used in certain residential settings.
Q: Is the CASPR MEDIK technology safe for humans and pets?
- A: Yes, the CASPR MEDIK technology generates safe levels of hydrogen peroxide that are effective against pathogens but safe for humans and pets when used as directed.
Congratulations
- On your purchase of the CASPR MEDIK continuous disinfection Solution.
- This unit is designed to be installed into an existing HVAC system and used as a virtually maintenance-free enhanced system for providing low levels of oxidizing molecules that will reduce microburden on all the surfaces of the targeted area.
- Please read and follow all service procedures outlined in this manual.
Indications of Use
- CASPR MEDIK is an innovative no-touch disinfection technology-based device that works without an operator to provide continuous reduction of micro-burdens facility-wide.
- Proven in independent lab tests to effectively reduce clinically relevant pathogens like MRSA, Norovirus, Aspergillus Niger, VRE, C. difficile, and more, before they spread.
Moreover. it is:
- Safe to use in occupied spaces
- Works on all surfaces, including floors
- No operator or maintenance required
- Affordable for facility-wide use
- Strategic enough for unit-specific targeting
- Easily & affordably installed in the existing HVAC
Product Contents
Installation Hardware
- (4) Self-tapping Screws
- (2) Cell Mounting Screws
Replacement Parts
Bulbs:
- 9” Bulb Part Number: BULB-HV-9-002-CASPR
- 14” Bulb Part Number: BULB-HV-14-002-CASPR
- Cells(which includes bulbs):
- 9” NCC Cell Part Number: CELL-HV-9-002-CASPR 14” NCC Cell Part Number: CELL-HV-14-002-CASPR
About CASPR MEDIK
- CASPR MEDIK is an enhanced “no touch” continuous disinfection device designed to supplement normal cleaning and disinfection protocols.
- CASPR MEDIK uses Natural Catalytic Conversion (NCC) to generate safe, low levels of hydrogen peroxide.
- NCC technology replicates natural purifying processes by using a high-intensity light to activate a proprietary metal catalytic coating, converting water vapor into hydrogen peroxide.
- Hydrogen peroxide acts as an oxidizer inactivating surface and air pathogens.
- It can compromise cellular integrity by disrupting cell walls, or internal molecular structures, rendering contaminants harmless.
Specifications
- FEATURES:
- Replaceable NCC Cell
- ELECTRICAL:
- 120-277 VAC
- 9” Unit – 47W (start-up), 36.8W (Operation)
- 14” Unit – 73W (start-up), 59.5W (Operation)
- MECHANICAL:
- Distribution via air handler
- SIZE: (HxWxD)
- 9” Unit: 9¾” x 9¾” x 11”
- 14” Unit: 9¾” x 9¾” x 16.75”
- WEIGHT:
- 9” Unit: 3.5 lb
- 14” Unit: 3.7 lb
Warnings
- WARNING! – UV light in operation. Disconnect the unit from the power supply before servicing. Failure to follow warnings may result in severe eye damage.
- WARNING! The unit should be mounted at least 24 inches from the heat exchanger or heating element.
- Placing the photocatalytic cell too close to the heating element can cause the photocatalytic matrix to combust.
- To reduce the risk of electric shock, this equipment may have a grounding-type plug that has a third (grounding) pin. This plug will only fit into a grounding-type power outlet. If the plug will only fit into a grounding-type power outlet.
- If the plug does not fit into the outlet, contact qualified personnel to install the proper outlet. Do not alter the plug in any way.
Recommended Installation Tools
- A – 4.5” Hole Saw Bit
- B – 3/8” Drill Bit
- C – Drill/Power Driver
- D – Utility Knife
- E – STET
- F – Phillips Head Screwdriver
Installation Requirement
- Unit may be installed up or down stream of the air handler in the HVAC system as long as it is behind the filter.
- The ductwork around the installation area should be cleaned and dry to ensure proper adhesion of the gasket materials and any tape used.
- One circular opening, measuring approximately 4.5”, will need to be cut into the existing ductwork to install the unit properly.
Electrical Requirement
- To use the 120V plug, be sure to locate the unit within 6 ft. of a standard 120V grounded outlet. Long-term use of an extension cord is not recommended due to safety considerations.
Hardwiring Requirement
- Permanent wiring of the unit into your HVAC system should be done by a licensed HVAC Installer or Electrical Contractor only.
- For 110-277V: Black = L1, White = Neutral, Green – Ground
- For International Applications: Brown = L1, Blue = L2, Green/Yellow = Ground
Installation
- Find a suitable location to mount your CASPR MEDIK Unit.
- If necessary, cut away insulation for your plate to adhere to the duct.
- Using the Adhesive Gasket Plate, trace the hole location onto the duct.
- Use the Hole Saw and Drill to cut out the marked hole.
Alternative Cutting Method
- Using the Adhesive Gasket Plate, trace the hole location onto the duct.
- Drill holes around the outside edges of the previously marked hole but inside the outer holes of the Adhesive Gasket Plate.
- Use the Tin Snips to cut out the space around the marked hole.
- Remove the plastic backing on your Adhesive Gasket Plate.
- Press the Adhesive Gasket Plate onto the duct. Secure with the (8) Self-Tapping Screws.
- Connect the Cell to the Ballast using the two (2) cell mounting screws.
- Place the unit and cell through the opening and align the four studs with the four holes in the ballast. Secure the unit by twisting it clockwise to lock it into place.
- Plug the Unit Power Cable into the receptacle or have a Licensed Electrician or HVAC Installer hardwire the unit directly into the HVAC system.
Maintenance / UV Lamp Indicator
- Your CASPR MEDIK requires no periodic maintenance beyond normal replacement of the bulb at 18 months and the NCC cell with bulb every 3 years.
- Note: Proper Operation of the unit is shown with a Red or Green LED light on the face of the unit (color variants do not affect the functionality of the Unit).
- If the Ballast fails, or if power to the unit has been powered off/disconnected, the UV light will be off. If the UV lamp fails, the Red or Green LED light will also be off.
Disposal Of The NCC Cell
- Please do not throw the used NCC Cells in the garbage.
- The special germicidal UV bulb used in the CASPR MEDIK contains some insignificant amount of mercury. Contact your local Waste Management Center for a proper disposal procedure.
Changing The NCC Cell
- Remove the Unit Power Cable from the receptacle or ensure the unit isn’t powered.
- Twist the Ballast Housing counter-clockwise to unlock the unit from the mounting plate. Pull the unit from the duct.
- Remove the (2) Screws holding the NCC Cell in place and remove the NCC Cell from the Unit Cover.
- Exchange the Old NCC Cell with the new NCC Cell and replace the (2) Screws that hold it in place.
- Replace the Unit in the duct and turn it clockwise to lock it in place.
- Place the Unit Power Cable back into the receptacle or repower your unit.
Warranty Information
- LIMITED 3-YEAR WARRANTY ON CASPR Technologies UNITS AND 1-YEAR WARRANTY ON CASPR Technologies REPLACEMENT PARTS Customer should not repackage and ship the CASPR MEDIK unit due to the possibility of irreparable damage.
- For warranty service, please contact your CASPR Technologies Distributor for the address of the nearest service center, email warranty@casprgroup.com call Customer Service at 844-717-8819.
WHAT IS COVERED BY THIS WARRANTY
- We warrant the CASPR MEDIK to the Customer, subject to the conditions below, against defects in workmanship or material, provided that the products are returned to a service location within three (3) years from the date of purchase.
INSTALLATION AND MAINTENANCE REQUIREMENTS
- This warranty is expressly conditioned upon proper installation, operation, cleaning, and maintenance, all by the Owner’s Manual.
- Failure to meet any of these requirements will void this warranty. Servicing of your CASPR MEDIK by parties other than our authorized representatives and/or using parts other than genuine parts will also void this warranty.
HOW TO OBTAIN WARRANTY SERVICE
- Customer must contact their CASPR Technologies Distributor and provide proof of purchase within the above periods.
- We will repair replace and return the product, without charge and within a reasonable period, subject to the conditions herein, if its examination shall disclose any part to be defective in workmanship or material.
- If we, at our discretion, are unable to repair the product after a reasonable number of attempts, we will provide either a refund of the purchase price or a replacement unit, at the company’s option.
WHAT IS NOT COVERED BY THIS WARRANTY
- Ordinary wear and tear shall not be considered a defect in workmanship or material.
- These warranties do not apply to filters nor loss or damage caused by accident, fire, abuse, misuse, improper installation, leaking, modification, misapplication, or any repairs other than those provided by our authorized Service Center.
- This warranty is non-transferable.
MISSING SERIAL NUMBERS AND UNAUTHORIZED CHANNELS
- If a valid serial number is missing from the product, the warranty will be voided. CASPR Technologies products are authorized for sale through CASPR Technologies Distributors only.
- Warranties are voided if a product is purchased through unauthorized channels; this includes websites that are not authorized to use CASPR Technologies’s trademarked names, images, and logos as well as Internet auction sites (e.g. eBay and Craigslist).
- To confirm warranty coverage before purchasing a product, contact CASPR
- Technologies at 844-717-8819 with the serial number located on the back of the unit.
- EXCLUSION OF OTHER WARRANTIES AND CONDITIONS EXCEPT AS PROVIDED HEREIN, WE MAKE NO REPRESENTATION OR WARRANTY OF ANY KIND. ALL OTHER WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, ARE HEREBY EXPRESSLY DISCLAIMED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
LIMITATION OF LIABILITY FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES WE SHALL NOT, IN ANY CASE, BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING FROM BREACH OF EXPRESSED OR IMPLIED WARRANTIES, CONDITIONS, GUARANTEES OR REPRESENTATIONS, BREACH OF CONTRACT, NEGLIGENCE, OR ANY OTHER LEGAL THEORY. Such excluded damages include but are not limited to, loss of profits or revenue, and loss of the use of the products, and any loss caused by leaks or other water damage.
FOR U.S. APPLICATION ONLY
- This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
- Some states do not allow limitations on warranties or remedies for breaches. In such states, the above limitations may not apply to you.
FOR CANADIAN APPLICATION ONLY
- Exclusion of Subsequent Owners: Except as otherwise required by applicable legislation, this warranty is not transferable. This warranty gives you specific legal rights and you may also have other rights which vary from province to province.
- Some provinces and territories do not allow limitations on warranties or remedies for breach. In such provinces or territories, the above limitations may not apply to you.
- If any provision of this warranty or part thereof is held by a court of competent jurisdiction to be invalid, illegal, or unenforceable, the validity, legality, and enforceability of the remaining provisions or parts thereof will not in any way be affected or impaired within the jurisdiction of that court. This entire warranty shall continue to be valid, legal, and enforceable in any jurisdiction where a similar determination has not been made.
- This warranty is provided by: CASPR Technologies, Inc.
- 4505 Excel Parkway, #600
- Addison, TX 75001
- www.casprTech.com
- Corporate Offices 4505 Excel Parkway Suite 600 Addison, TX
- US 75001
- 1-844-171-8819
- info@casprtech.com
Documents / Resources
|
CASPR TECHNOLOGIES CASPR MEDIK Hospital Grade Air and Surface
Purifier
[pdf] Owner's Manual
CASPR MEDIK Hospital Grade Air and Surface Purifier, CASPR MEDIK, Hospital
Grade Air and Surface Purifier, Grade Air and Surface Purifier, Air and
Surface Purifier, Surface Purifier, Purifier
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>