Copeland 4430r0 CRLDS Quantified Refrigerant Test User Manual

May 15, 2024
Copeland

CRLDS Quantified Refrigerant Test
Bump Test Instructions

EQUIPMENT

  • 809-1207 Gas Detector – Calibration Kit For CRLDS Sensor
  • Flow regulator, 0.5 L/min constant flow (L.P.)
  • Gas cylinder
  • Smartphone with CRLDS App Installed (optional)

TEST PROCEDURE

STEP 1:
Attach the provided calibration adapter to the sensor.

STEP 2:
Connect to the CRLDS via Bluetooth and prepare to monitor the sensor while gas is flowing.

  1. Download and install Copeland CRLDS app from the App Store® or Google Play Store.

  2. Activate Bluetooth® on the CRLDS sensor by touching the red magnetic wand to the magnetic switch on top of the enclosure for 5 seconds continuously.

  3. Once Bluetooth® is activated, the green LED will change from solid green to blinking green.

  4. Open the CRLDS app, select Technician and login with password 2222.
    Copeland 4430r0 CRLDS Quantified Refrigerant - TEST
PROCEDURE1

  5. Select on the CRLDS serial number in the device list to connect.
    Copeland 4430r0 CRLDS Quantified Refrigerant - TEST
PROCEDURE2

  6. From the home tab, select the Parameters button.

  7. Select the Output Type 4-20mA, and hit back to save. Change the corresponding zone in the MZLD iPro to be 4-20mA for the analog input.
    Copeland 4430r0 CRLDS Quantified Refrigerant - TEST
PROCEDURE4

STEP 3:

According to EN 14624:2020* in “12.7 Response time” is stated that the response time of the detector must be 30 sec (seconds) or less at a concentration of 1.6 times the preset value.
Choose the gas sensor accordingly.
Note that in cases where semi-conductive sensors are tested, the test gas must be balanced with air.

  • Based on EN 378:2016, 9.3.1
    STEP 4:

Copeland 4430r0 CRLDS Quantified Refrigerant - gas
sensor1

Use the gas regulator with constant flow of 0.5 L /min.
Note that in case of ammonia sensors, the stainless steel regulator must be used.
STEP 5:

Copeland 4430r0 CRLDS Quantified Refrigerant - gas
sensor2

In cases where semi-conductor sensors are tested, moisten the air humidifier with tap water.
STEP 6:

Control if the alarm indication starts within 30 seconds from the start of the gas exposure:
LED indication: Visual inspection
Relay indication:
Sound (relays clicking)
Electrical continuity test on relay terminals
User Manual References:
5.5 Alarm Management
4.3 Installation Instructions and Electrical Connections
URL: https://www.copeland.com/documents/026-1318-crlds-usermanual- en-9291542.pdf

STEP 7:

Copeland 4430r0 CRLDS Quantified Refrigerant - CRLDS mobile
app

Check the CRLDS mobile app home tab to verify the PPM reading and alarm state while gas is flowing.
Verify the desired PPM has been reached and relay states are performing as intended.

Document Part # 026-4430 Rev 0

This document may be photocopied for personal use.
Visit our website at www.copeland.com for the latest technical documentation and updates.
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Copeland.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Copeland reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. ©2023 Copeland is a trademark of Copeland LP.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals