Copeland 4430r0 CRLDS Quantified Refrigerant Test User Manual
- May 15, 2024
- Copeland
Table of Contents
CRLDS Quantified Refrigerant Test
Bump Test Instructions
EQUIPMENT
- 809-1207 Gas Detector – Calibration Kit For CRLDS Sensor
- Flow regulator, 0.5 L/min constant flow (L.P.)
- Gas cylinder
- Smartphone with CRLDS App Installed (optional)
TEST PROCEDURE
STEP 1:
Attach the provided calibration adapter to the sensor.
STEP 2:
Connect to the CRLDS via Bluetooth and prepare to monitor the sensor while
gas is flowing.
-
Download and install Copeland CRLDS app from the App Store® or Google Play Store.
-
Activate Bluetooth® on the CRLDS sensor by touching the red magnetic wand to the magnetic switch on top of the enclosure for 5 seconds continuously.
-
Once Bluetooth® is activated, the green LED will change from solid green to blinking green.
-
Open the CRLDS app, select Technician and login with password 2222.
-
Select on the CRLDS serial number in the device list to connect.
-
From the home tab, select the Parameters button.
-
Select the Output Type 4-20mA, and hit back to save. Change the corresponding zone in the MZLD iPro to be 4-20mA for the analog input.
STEP 3:
According to EN 14624:2020* in “12.7 Response time” is stated that the
response time of the detector must be 30 sec (seconds) or less at a
concentration of 1.6 times the preset value.
Choose the gas sensor accordingly.
Note that in cases where semi-conductive sensors are tested, the test gas
must be balanced with air.
- Based on EN 378:2016, 9.3.1
STEP 4:
Use the gas regulator with constant flow of 0.5 L /min.
Note that in case of ammonia sensors, the stainless steel regulator must
be used.
STEP 5:
In cases where semi-conductor sensors are tested, moisten the air humidifier
with tap water.
STEP 6:
Control if the alarm indication starts within 30 seconds from the start of the
gas exposure:
LED indication: Visual inspection
Relay indication:
Sound (relays clicking)
Electrical continuity test on relay terminals
User Manual References:
5.5 Alarm Management
4.3 Installation Instructions and Electrical Connections
URL: https://www.copeland.com/documents/026-1318-crlds-usermanual-
en-9291542.pdf
STEP 7:
Check the CRLDS mobile app home tab to verify the PPM reading and alarm state
while gas is flowing.
Verify the desired PPM has been reached and relay states are performing as
intended.
Document Part # 026-4430 Rev 0
This document may be photocopied for personal use.
Visit our website at www.copeland.com for the
latest technical documentation and updates.
For Technical Support call 833-409-7505
or email
ColdChain.TechnicalServices@Copeland.com
The contents of this publication are presented for informational purposes only
and they are not to be construed as warranties or guarantees, express or
implied, regarding the products or services described herein or their use or
applicability. Copeland reserves the right to modify the designs or
specifications of such products at any time without notice. Responsibility for
proper selection, use and maintenance of any product remains solely with the
purchaser and end-user. ©2023 Copeland is a trademark of Copeland LP.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>