COPELAND 800-2100 Pressure Transducer Installation Guide

June 13, 2024
Copeland

COPELAND 800-2100 Pressure Transducer Installation Guide
COPELAND 800-2100 Pressure Transducer

Description

This bulletin provides technical information about Copeland pressure transducers.

Cautions, Warnings, and Notices

  • CPC transducers require +5VDC power to operate. DO NOT connect this transducer to +12VDC power. Doing so will damage the transducer and void the warranty.
  • Previous transducer models required installation techs to set the input type dip switch to the DOWN position on input boards. The below transducers require you to set the input type dip switch to the UP position.

Part Numbers

Table -1 lists the part numbers for all pressure transducers currently available from Copeland, including the part numbers.

Table -1 – Transducer Part Numbers and Types

Part # Transducer Type Port Status
800-2100 CPC 100PSI 1/8” Male NPT Current
800-2101 CPC 100PSI 1/8” Female NPT Current
800-2200 CPC 200PSI 1/8” Male NPT Current
800-2201 CPC 200PSI 1/8” Female NPT Current
800-2500 CPC 500PSI 1/8” Male NPT Current
800-2501 CPC 500PSI 1/8” Female NPT Current
800-2651 CPC 650PSI 1/8” Female NPT Current
800-2711 CPC 1000PSI 1/8” Female NPT Current
800-2721 CPC 2000PSI 1/8” Female NPT Current

Hardware Specifications

Supply Voltage
Transducers (800-2100, 800-2101, 800-2200, 800-2201, and 800-2500, 800-2501, 800-2651, 800-2711, 800-2721) require an excitation voltage of +5 VDC. This is NOT the same voltage required by the old “standard” transducers, which required +12 VDC.

Important! Do not connect the CPC transducer to +12 VDC. Doing so will damage the transducer and void the warranty.

Operating Temperature Range

The transducers are rated to withstand ambient temperatures from -22°F to 158°F (-30°C to +70°C), and media (refrigerant) temperatures from -40°F to 300°F (-40°C to 149°C).

In ambient temperatures from +90°F to +160°F (+32°C to +71°C), the maximum allowable media temperature is derated from +300°F (149°C) by 2° for every one degree that ambient temperature is above +90°F (+32°C)

Output Signal

The transducer’s output signal voltage varies from 0.5 to 4.5 VDC as the pressure varies from zero to the transducer’s maximum value. When the transducer reads a pressure that is above 110% of its maximum rating, the signal voltage will stop at ~4.9 VDC.

The maximum error between the measured pressure and the pressure signified by the output signal voltage is ±1.5%. This means the output signal will have a maximum error of ±1.5 PSI for the 100PSI transducer, ±3 PSI for the 200PSI transducer, and ±7.5 PSI for the 500PSI transducer.

Fittings

All transducer male and female models have 1/8” NPT fittings. If replacing a standard transducer with 1/4” SAE port and Schrader depressor, the valve fitting will have to be replaced by a female 1/8” NPT port.

Note: On request, Copeland can supply replacements for “standard” transducers equipped with a female 1/4” SAE port with Schrader depressor. Contact Copeland if you require such a transducer.

Transducer Cable

Transducers are supplied with a 20’ cable for connecting the transducer to +5VDC power and an input board point. The cable plugs in to the top of the transducer using a Packard Metri-Pack 12065287 cable connector.

Over pressure , Burst Pressure, and Vacuum Pressure

Table -2 gives the overpressure, burst pressure, and vacuum pressure PSI ratings for each transducer model.

The overpressure rating is the PSI which, when exceeded, will cause the transducer to function incorrectly.

The burst pressure rating is the highest PSI the transducer can withstand without leaking or breaking.

The vacuum pressure is the amount of vacuum the transducer can withstand before the transducer starts to read incorrectly.

Note: The transducer will not be damaged by any amount of applied vacuum. There is no need to close transducer valves or remove transducers when applying vacuum.

Table -2 – Overpressure, Burst Pressure, and Vacuum Ratings

Model Overpressure Burst Pressure Vacuum
CPC 100PSI 300 PSIG 1000 PSIG -10 PSIG
CPC 200PSI 400 PSIG 1000 PSIG -14.7 PSIG
CPC 500PSI 1000 PSIG 2500 PSIG -14.7 PSIG

Installation

  1. Wrap the transducer pipe fitting with Teflon tape to ensure a tight seal.

  2. Screw the transducer on to the access valve. Tighten by using a wrench on the hex nut above the fitting. Do not use the transducer casing to apply torque.

  3. Attach the connector of the cable harness to the port at the top of the transducer.

  4. Connect the cable harness wires to the 16AI or 16AIe board as shown in Figure 1. If connection to the input board requires more than the 20’ of wire included with the cable harness, use Belden #8771 (shielded, 3 conductor, 22AWG) or equivalent to extend the cable.
    Figure 1 – Pressure Transducer Installation
    Pressure Transducer Installation

  5. On switch S1 or S2 on the 16AI or 16AIe, set the input dip switch rocker corresponding to the input number to the UP position. This is different from the required input dip switch setting for all previous transducers. If replacing an old pressure transducer with the new pressure transducer, you must change the input dip switch setting from DOWN to UP.

Controller Programming

When setting up pressure transducer inputs in E2, E3, or Site Supervisor, set the Sensor Type to 5v-100PSI, 5v-200PSI, 5v-500PSI, 5v-650PSI, 5v-1000PSI, or 5v-2000PSI.

Pressure Transducer Output Signal Voltages

Table -3 lists the transducer output voltages and their corresponding pressure readings.

Table -3 – Voltage to Pressure Chart for CPC Transducers

Transducer Voltage| Pressure Value -100PSI Transducer| Pressure Value -200PSI Transducer| Pressure Value -500PSI Transducer
---|---|---|---
0.5 V| 0 PSI| 0 PSI| 0 PSI
0.7 V| 5 PSI| 10 PSI| 25 PSI
0.9 V| 10 PSI| 20 PSI| 50 PSI
1.1 V| 15 PSI| 30 PSI| 75 PSI
1.3 V| 20 PSI| 40 PSI| 100 PSI
1.5 V| 25 PSI| 50 PSI| 125 PSI
1.7 V| 30 PSI| 60 PSI| 150 PSI
1.9 V| 35 PSI| 70 PSI| 175 PSI
2.1 V| 40 PSI| 80 PSI| 200 PSI
2.3 V| 45 PSI| 90 PSI| 225 PSI
2.5 V| 50 PSI| 100 PSI| 250 PSI
2.7 V| 55 PSI| 110 PSI| 275 PSI
2.9 V| 60 PSI| 120 PSI| 300 PSI
3.1 V| 65 PSI| 130 PSI| 325 PSI
3.3 V| 70 PSI| 140 PSI| 350 PSI
3.5 V| 75 PSI| 150 PSI| 375 PSI
3.7 V| 80 PSI| 160 PSI| 400 PSI
3.9 V| 85 PSI| 170 PSI| 425 PSI
4.1 V| 90 PSI| 180 PSI| 450 PSI
4.3 V| 95 PSI| 190 PSI| 475 PSI
4.5 V| 100 PSI| 200 PSI| 500 PSI

Document Part # 026-2105 Rev 1

his document may be photocopied for personal use.
Visit our website at www.copeland.com for the latest technical documentation and updates.
For Technical Support call 833-409-7505 or email [email protected]
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Copeland reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user. ©2023 Copeland is a trademark of Copeland LP.

Document Part # 026-2105 Rev 1
©2023 Copeland Digital Cold Chain, LP. This document may be photocopied for personal use. Visit our website at www.copeland.com for the latest technical documentation and updates.

COPELAND Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Copeland User Manuals

Related Manuals