VIMAR 02913 Electronic LTE Thermostat Smart Clima Installation Guide
- May 15, 2024
- VIMAR
Table of Contents
SMART CLIMA
02913 – LTE thermostat
02913 Electronic LTE Thermostat Smart Clima
Electronic LTE thermostat for local control and advanced remote temperature
management via View App, heating and air conditioning in ON/OFF and PID mode,
class I temperature control device (contribution 1%) in ON/OFF mode, class IV
(contribution 2%) in PID mode, configuration via View App on standard
Bluetooth technology, 1 additional output and 1 digital input, 1 relay output
5(2) A 240 V~, power supply 100-240 V~ 50/60 Hz, white LED backlighting,
surface mounting, white.
Download the View App from the stores onto the tablet/smartphone you will be
using for configuration.
You will also need:
Amazon Alexa, Google Assistant voice assistants for possible voice operation
CONFIGURATION IN
- Create your Administrator or Installer account on MyVimar (on-line).
- Wire the thermostat.
- Start the View App and log in with the credentials you just created.
- To associate the thermostat:
- In the event of new systems, select “Create a new Smart ecosystem” and give it a name. Select “Vimar Smart Thermostat” “Proceed”
- In the event of an existing system, select the “Smart Devices” ecosystem “Vimar Smart Thermostat” “Proceed”
- Press button B for 5 s; activate the Bluetooth connection on your tablet/smartphone and approach the thermostat
-
Select “Proceed” and enter the APN of your phone operator following the instructions provided by the wizard
Main APNTIM| ibox.tim.it
Vodafone| web.omnitel.it
Wind3| internet.it
Iliad| iliad - ame the thermostat and the actuator of the auxiliary output and then set the time zone
- Go to the “Smart Devices” section and set the thermostat parameters
For details please refer to the manual entitled “Programming thermostats
02912-02913” available for download from
www.vimar.com
OPERATION WITHOUT CONFIGURATION VIA APP.
If configuration is not done via the View App, the thermostat is designed to
accommodate operation in manual mode.
RESETTING THE THERMOSTAT
The reset restores the factory settings. Within the first 5 minutes within
which it is powered, press button B for 30 s.
INSTALLATION RULES.
- Installation and configuration must be carried out by qualified persons in compliance with the current regulations regarding the installation of electrical equipment in the country where the products are installed.
- The C-NO contact of the relay must be protected against overloads by installing a device, fuse or automatic 1-way switch, with a rated current not exceeding 10 A.
- Do not connect a SELV circuit to the NO-C, IN-N and L-1 (auxiliary output) terminals as there is no double insulation compared to the L-N terminals.
- The device must be installed at a height of 1.5 m above floor level, in a suitable position for the correct detection of the room temperature, avoiding installation in recesses, behind doors and curtains, areas affected by heat sources or subject to the flow of forced heating/cooling ventilation sources or affected by atmospheric factors. Avoid in particular installation on perimeter walls or in association with devices which generate heat (e.g. dimmers or lamps).’
IMPORTANT WARNINGS
- The LTE connection varies depending on the phone operator; check in advance the one in your area which guarantees best coverage and purchase the corresponding SIM card.
- We recommend you use a SIM card with a data contract with traffic of at least 50 MB/ month.
- Before inserting the SIM card in the thermostat, disable the PIN code prompt.
- To do this, insert the SIM card in your smartphone and follow the instructions provided to disable the PIN.
CHARACTERISTICS.
-
Rated supply voltage: 100-240 V~, 50/60 Hz.
-
Consumption at 100 V~:
– brightness L1 (low) and relay OFF 0.3 W
– brightness L3 (high) and relay ON 0.85 W -
Consumption at 240 V~:
– brightness L1 (low) and relay OFF 0.5 W
– brightness L3 (high) and relay ON 1 W -
Bluetooth technology:
– RF transmission power: < 100 mW (20 dBm)
– Frequency range: 2400-2483.5 MHz -
Transmission bands:
– B1 (2100MHz)
– B3 (1800MHz)
– B7 (2600MHz)
– B8 (900MHz)
– B20 (800MHz) -
Terminals:
– 2 (L and N) for line and neutral
– 2 for digital input 120 – 240 V~ for alarm signalling (for instance boiler shutdown)
Maximum length of the 30 m contact connection cable
– 2 (NO-C) for relay output with voltage-free contact: 5(2) A 240 V~
– 2 for output 100 mA 120 – 230 V~ to control an auxiliary relay (for instance to switch a boiler or a light on/off) -
2 front buttons with rocking action for control and settings.
-
1 button (positioned at the bottom) for configuration and reset.
-
Side LEDs:
– 2 on the left for signalling Cloud connection and LTE network connection
– 3 on the right for signalling ON/OFF, relay state and auxiliary output state -
White LED display for displaying temperature, set point and configuration state signalling.
-
Current settable setpoint: 4 °C ÷ 40 °C.
-
Temp. measurement precision (integrated probe): 0.5°C between +15°C and 30°C, 0.8°C at the extremes
-
For use for Heating/Air Conditioning (winter/summer).
-
Operating modes: Automatic, Manual, Reduction, Absence, Protection, Off, Timed Manual.
-
Temperature control algorithms: configurable PID or ON/OFF.
-
Operating temperature: T40 (0 °C ÷ +40 °C) (indoor use).
-
Protection degree: IP20.
-
ErP classification (EU Reg. 811/2013): – ON/OFF: class I, contribution 1%. – PID: class IV, contribution 2%.
-
Device in class II
-
Number of manual cycles: 3,000
-
Number of automatic cycles: 100,000
-
Type of contact opening: micro-disconnection
-
Type of action: 1.C
-
Tracking index: PTI175
-
Degree of pollution: 2
-
Rated pulse voltage: 4000 V
-
Software class: A
-
Reading resolution: 0.1 °C
-
Settings resolution: 0.1 °C from App and ± 0.5 °C from device
-
Update of temperature displayed: every 10 s
-
Room temperature display: 0 °C +40 °C
-
Hysteresis adjustable via App: from 0.1 °C to 1 °C
-
Hourly temperature setting (via App)
-
Room temperature during transportation: -25 °C +60 °C
-
Clock error: ≤ 1 s per day
-
Configuration via View App using Bluetooth technology
-
Controllable via View App, Amazon Alexa and Google Assistant voice assistants.
-
Dimensions: 106 x 118 x 23.5 mm.
OPERATION.
Using the View App, making use of the Internet connection the following can be set:
- Time schedules (times and temperature levels T1, T2 and T3)
- Setpoint for all operating modes (Manual, Reduction, Absence, Protection). The operating mode can be changed from the View App after one ON/OFF cycle
- Manual operation time: between 1 min and 23 hours (with 1-min steps); default = 60 min
- Lighting in standby: high, medium, low, off with default = medium
- Temperature calibration for heating: between -5°C and +5°C with default = 0°C
- Temperature calibration for air conditioning: between -5°C and +5°C with default = 0°C
- Relay output status: normally open, normally closed; default = normally open
- Auxiliary output state: ON/OFF, timed.
- Control type: On/Off, PID; default = On/Off
- Hysteresis for On/Off control: between 0.1°C and 1°C; default = 0.2°C
- Proportional band for PID control: between 0.5°C and 5°C; default = 3°C
- Integrative time for PID control: between 5 min and 120 min; default = 20 min
- Derivative time for PID control: between 0 and 255 s, disabled; default = 0
- Cycle time for PID control: between 10 min and 30 min; default = 10 min
In the event of a power outage, once the power is restored, the thermostat restarts with the operating mode prior to the outage. If the mode set was “Automatic” the thermostat will restart in “Manual” mode and the first time it reconnects to the Cloud, it will synchronise the time/date again and then switch to “Automatic” mode.
USE.
The thermostat display shows the current temperature; when you use “ ” and “ ”
the set point being set during the action is displayed.
REGULATORY COMPLIANCE.
RED Directive. RoHS directive. ErP directive.
Standards EN 60730-2-7, EN IEC 60730-2-9, EN 300 328, EN 301 489-17, EN 301
908-13, EN 301 489-52, EN 62311, EN IEC 63000.
Temperature control device regulation (EU) no. 811/2013.
Vimar SpA declares that the radio equipment complies with Directive
2014/53/EU. The full text of the EU declaration of conformity is on the
product sheet available on the following website: www.vimar.com
REACH (EU) Regulation no. 1907/2006 – Art.33. The product may contain traces
of lead.
WEEE – User information
**** The crossed bin symbol on the appliance or on its packaging indicates
that the product at the end of its life must be collected separately from
other waste. The user must therefore hand the equipment at the end of its life
cycle over to the appropriate municipal centres for the differentiated
collection of electrical and electronic waste. As an alternative to
independent management, you can deliver the equipment you want to dispose of
free of charge to the distributor when purchasing a new appliance of an
equivalent type. You can also deliver electronic products to be disposed of
that are smaller than 25 cm for free, with no obligation to purchase, to
electronics distributors with a sales area of at least 400 m2. Proper sorted
waste collection for subsequent recycling, processing and environmentally
conscious disposal of the old equipment helps to prevent any possible negative
impact on the environment and human health while promoting the practice of
reusing and/ or recycling materials used in manufacture.
The Apple, iPhone and iPad logos are trademarks of Apple Inc., registered in
the United States and in other Countries and Regions. App Store is a service
trademark of Apple Inc.
Google is a trademark of Google LLC.
Amazon, Alexa and all related logos are trademarks of Amazon.com, Inc. or its
affiliates.
VIEWS
| • Short press = adjustment of set point from 4°C to 40°C in steps of 0.5°C
• Long press (5 s) = if on standby the thermostat is switched off; if switched
OFF the thermostat is switched on
---|---
A| Display
• bt = thermostat in Bluetooth configuration
• off = thermostat off; on = thermostat on
• °C = degrees Celsius; °F = degrees Fahrenheit
• animation from the bottom up = Heating
• animation from the top down = Air conditioning
• Rst = thermostat reset
• PIN = PIN entry prompt
• Alr, Con, Cld, ltE, etc. = alarms
B| • Short press = degrees Celsius/Fahrenheit selection
• Long press (5 s) = the thermostat enters the configuration phase (bt)
• Prolonged press (30 s) within the first 5 min of powering = thermostat reset
(Rst)
Alarms
Alr | Alarm generated by the wired contact (for instance Boiler shutdown) |
---|---|
Con | No connection to the GSM network |
Cld | No connection to the Cloud |
ltE | • SIM missing |
• SIM PIN request
• SIM credit depleted
LED indications
| • ON green = Cloud correctly connected
• ON red = Cloud not connected
---|---
| • ON green = LTE network connected
• ON red = LTE network not connected
| • ON green = ON thermostat
• OFF = OFF thermostat
| • ON white = Active relay
| • ON white = Auxiliary output active
CONNECTION WITH CIRCULATION PUMPS, BURNERS, SOLENOID VALVES * Generates an alarm notification but does not deactivate the output relay (NO-C)
TYPES OF INSTALLATION
INSTALLATION
Using a screwdriver, detach the thermostat from the bracket as shown in the
figure. Make the connections and fix the bracket to
the wall. N.B.: When the thermostat is being
disassembled, to change the SIM card, wait for the red LED beside it to be
turned off.
Insert the SIM card
Caution: Tighten the wall bracket screws, applying sufficient torque
without exaggerating, in order to avoid warping it.Fix the thermostat to the bracket using the dedicated attachments
shown in the figure.
www.vimar.com
Viale Vicenza 14
36063 Marostica VI – Italy
02913 04 2303
Documents / Resources
|
VIMAR 02913 Electronic LTE Thermostat Smart
Clima
[pdf] Installation Guide
02913 Electronic LTE Thermostat Smart Clima, 02913, Electronic LTE Thermostat
Smart Clima, Thermostat Smart Clima, Smart Clima
---|---
References
Read User Manual Online (PDF format)