VIMAR 01504.2 Line-Field Coupler Installation Guide
- June 5, 2024
- VIMAR
Table of Contents
01504.2 Line-Field Coupler
Installation Guide
product description
The 01504.2 media coupling device can be used as a line coupler, a backbone coupler, or a line repeater. The basic functionality of the 01504.2 is coupling a KNX TP main line with a KNX TP subline. Providing galvanic isolation between the two connected lines enables a data connection between the upper line (mainline or backbone) and the lower line.
Due to its flexibility, the coupler can be used as a line coupler to connect a subline to a mainline or as a backbone coupler to connect a mainline to a backbone line. The main task of the 01504.2 is to filter the traffic according to the installation place in the hierarchy (individually addressed telegrams, in this document named Physical telegrams) or according to the built-in filter tables for group-oriented communication (Group telegrams).
Compared to other similar products the 01504.2 provides outstanding features, for example, its support of long messages (up to 240 byte APDU length) and a configurable one-button activation of the “Manual Function” (transmit all telegrams, transmit Physical telegrams, or transmit Group telegrams). This functionality is helpful during installation, during run time, and for troubleshooting. To easily identify common communication problems due to busload or retransmissions on both lines the high informative 6 duo LED display shows the bus status on each line accurately.
The 01504.2 is also able to link two lines for data transfer. As a line repeater, the 01504.2 still provides galvanic isolation between the connected lines. The result is up to four lines can form a single subline with up to three line repeaters used after the line coupler. Each sub-line segment requires its own KNX power supply unit.
KNX topology
Please note:
Commissioning at delivery status means:
- All telegrams are blocked because the filter table is not defined
- The fallback time after the manual operation is 120 min
- The physical address is 15.15.0
Device frontend
1 Bus state mainline LED | 5 Group address filter table status LED |
---|---|
2 Bus state sub line LED | 6 Physical address filtering status LED |
3 Bus traffic mainline LED | 7 Programming LED |
4 Bus traffic sub line LED | |
A Function button | C KNX mainline |
B Program button | D KNX subline |
Installation example
Operational description
According to either the factory default settings or to the latest parameter settings (downloaded from ETS, also other tools) being in “Normal Mode” the 01504.2 operates as it is supposed to. The default configurations of the “Normal Mode” are set by the mainline and the sub-line parameters.
Normal mode
| Green| Red
---|---|---
LED 1
Bus State Main| Off: mainline error or not connected On: mainline OK| On:
manual overwrite active.
LED 2
Bus State Sub| Off: sub line not connected On: sub line OK| N.A.
LED 3 Traffic Main| Blinking: bus traffic on mainline (only valid telegrams)
Off no traffic on mainline| Blinking: transmission error on mainline
LED 4 Traffic Sub| Blinking: bus traffic on subline (only valid telegrams) Off
no traffic on a subline| Blinking: transmission error on a subline
LED 5
Group Address| Routing of Group telegrams Off main and sub different. On:
Fitter table is active| Block
On with Amber color: route all
LED 6
Physical Address| Routing of Physical telegrams Off main and sub different.
On: Finer table active| On: block
On with Amber color: route all
LED 7 Programming| N.A.| On: device in Program Mode’
Program mode
With the Programming button, the device can be switched between “Normal Mode”
and “Program Mode”. To download the physical address to the device this
unction is essential. After the download, the 01504.2 automatically returns to
the “Normal Mode”.
Programming LED (7):
Off: Normal Mode
On: Program Mode
Function button
The function button is used for two purposes, either to switch to “Manual
Function” or to do a factory reset. Being in “Normal Mode” it depends on the
duration of time the button is being pressed.
Manual function
Long press (≈ 3 sec) in “Normal Mode”
The device activates the “Manual Function” and the LEDs change their status.
Pressing the button again for some seconds deactivates the “Manual Function”.
After the expiration of the Fallback time, the device returns to “Normal Mode”
automatically. To configure the “Manual Function” and set the Fallback time
use the parameter tab “General”.
Please note:
The latest downloaded settings (parameters) and the filter table are still
available after switching back from “Manual Function” to “Normal Mode”.
Factory reset
Very long press (≈ 15 s) in “Normal Mode”
A factory reset is carried out by pressing the button for about 15 seconds
(LEDs 1,2,5,6 light with mixed color). After release, pressing it again for
some seconds resets all the parameters to factory default (incl. physical
address). Subsequently, the LEDs change their status.
Application description line coupler
With the coupler receiving physically addressed telegrams (Physical
telegrams), for example during commissioning, it compares the physical address
of the receiver with its own physical address to decide whether to route the
telegrams or not. On receiving telegrams with group addresses (Group
telegrams) the coupler proceeds in accordance with its parameter settings.
At the default setting the coupler only routes those telegrams whose group
addresses have been entered in its filter table.
In case of not receiving an acknowledgment after routing a telegram, due to a
bus transmission error, for example, the coupler repeats the telegram up to
three times (depending on the corresponding parameter that is set by ETS).
With the parameters „Repetitions if errors …“ this function can be adjusted
separately for both connected lines. The default settings of these parameters
should be retained.
ETS-Parameters line coupler
All screenshots in this document describing ETS parameters represent the
Line/Field coupler´s database entry in the ETS5.
Settings
In the properties window, the basic settings of the Line/Field coupler can be
adjusted and checked. Under the Settings tab, the device name and the physical
address (individual address) can be changed/downloaded to the device. When not already configured as “Line coupler”, the
application program for “Line coupler” has to be downloaded to the device.
Under the Information tab, this configuration can be changed by the menu
“Change Application Program”. After changing the configuration the filter
table entries can be added manually. Also updating the application program can
be done here.
General
Mainline
Important note:
The parameter “transmit all” for Group telegrams or Physical telegrams is
intended only for testing purposes. This setting should not be used during
normal operations.
ETS-Parameters line coupler
ETS-Text | Selection [Factory default] | Comment |
---|---|---|
Configuration | groups: filter, physical: block groups, physical: filter |
groups: route, physical: filter groups, physical: route configure [groups,
physical: filter]| – Block: no telegram is routed.
– Filter: only telegrams are routed which are entered in the filter table. _
Route: the telegrams are routed.
– Configure: the following parameters can be set manually. This parameter is
to be set depending on the planned configuration.
Group telegrams| 1. transmit al (not recommended)
2. block
3. filter [filter]| 1. Al group telegrams are transmitted.
2. No group telegram is transmitted.
3. Only Group telegrams entered in the fitter table are routed. ETS3/4
produces the fitter table automatically.
Main group telegrams 14/15| 1. transmit all
2. block [transmit all]| 1. Group telegrams with the sub-group 14 or 15
(e.g. 14/1) are routed.
2. Group telegrams with the sub-group 14 or 15 (e.g. 14/1) are not routed.
Physical telegrams| 1. transmit all (not recommended) 2 blocks.
3. fitter [litter]| 1. Al Physical telegrams are transmitted.
2. No Physical telegram is transmitted.
3. Depending on the physical address only Physical telegrams are routed.
Physical:
Repetition when errors on mainline| 1. no.
2 normal
3 reduced. [normal]| If a transmission error (e.g. due to a missing receiver)
is found after sending a Physical telegram on the main the:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once
Group:
Repetition when errors on mainline| 1. no.
2 normal.
3 reduced [normal]| If a transmission error(e.g. due to a missing receiver) is
found after sending a Group telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.
Telegram confirmations online| 1. if routed
2. always [If routed] (ACK).| 1. Only telegrams that are to be routed are
confirmed on the main Nne
2. Each telegram on the mainline is confirmed (ACK).
Send confirmation on your own telegrams| 1 . yes
2. no [no]| 1. Every telegram on the mainline is confirmed with its own ACK
(from the Line coupler).
2. No confirmation with own ACK 3 See note below.
Please note:
If the parameter “Send confirmation on own telegrams” is set to yes the line
coupler will send an ACK systematically on any own routed telegram.
Subline
ETS-Parameters line coupler-Application description line repeater
ETS-Text | Selection [Factory fau delt] | Comment |
---|---|---|
Configuration | groups: filter, physical: block groups. physical: filter |
groups: route, physical: filter groups, physical: route configure
[groups, physical: filter]| – Block: no telegram is routed.
– Filter: only telegrams are routed which are entered In the filter table. –
Route: the telegrams are routed.
– Configure: the following parameters can be set manually
Group telegrams| 1. transmit all (not recommended)
2. block
3. filter [filter]| 1. All group telegrams are transmitted.
2. No group telegram is transmitted.
3. Only group telegrams entered in the filter table are routed. ETS3/4
produces the fitter table automatically
Subgroup telegrams 14/15| 1. transmit all
2. block [transmit all]| 1. Group telegrams with the sub-group 14 or 15
(e.g. 14/1) are routed.
2. Group telegrams with the sub-group 14 or 15 (e.g. 14/1) are not routed.
Physical telegrams| 1. transmit all (not recommended) 2 blocks.
3. filter [filter]| 1. All Physical telegrams are transmitted.
2. No Physical telegram is transmitted.
3. Depending on the physical address only Physical telegrams are routed.
Physical: Repetition if errors on the subline occur| 1.. no
2. normal
3.reduced [normal]| If a transmission error (e.g. due to a missing receiver)
is found after sending a physical telegram on the main tine:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.
Group: Repetition if errors on the sub-One occur| 1. no.
2 normal.
3 reduced [normal]| If a transmission error (e.g. due to a missing receiver)
is found after sending a group telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once..
Telegram confirmations online| 1. if routed
2. always [if routed] (ACK).| 1. Only telegrams that are to be routed are
confirmed on the subline
2. Each telegram on the sub line is confirmed (ACK).
Send confirmation on your own telegrams| 1. yes
2. no [no]| 1. Even] telegram on the sub line is confirmed with its own ACK
(from the Line coupler).
2.No confirmation with own ACK
Application description line repeater
Line repeaters do not use a filter table. A received telegram is routed to all
lines irrespective of in which line it is processed. It is therefore not
important whether the telegram is triggered within a line or whether it is
sent from an upper line to a lower line via a coupler.
When an error occurs during the transmission of a telegram according to the
physical address of a receiver the line repeater is able to repeat the
telegram. With the parameters „Physical: Repetition if errors on mainline/on
subline“ this function can be set separately for both lines. In the case of
routing a group telegram without not receiving an acknowledgment or in case of
an abused device detecting a transmission error, the line repeater repeats the
telegram three times. With the parameters „Group: Repetition if errors on
main line/on sub line“ this function can be adjusted separately for both
lines.
ETS-Parameters line repeater
Settings
In the properties window, the basic settings of the Line/Field coupler can be
adjusted and checked. Under the Settings tab the device name and the physical
address (individual address) can be changed and downloaded to the
device.
When not already configured as “Line repeater”, the application program for
“Line repeater” has to be downloaded to the device. Under the Information tab,
this configuration can be changed by the menu “Change Application Program”.
After changing the configuration the filter table entries can be added
manually. Also updating the application program can be done here.
General
EIS-Text | Selection [Factory default] | Comment |
---|
Fallback time
for manual operation| 10 min. 1 hour. 4 hours. 8 hours (1 hour]| After this
time period the ‘Manual Function” is switched off automatically.
Manual function| disabled pass all telegrams pass physical telegrams pass
group telegrams [pass all telegrams]| Telegram routing configuration for the
“Manual Function”.
Main line
Important note:
The parameter “transmit all” for Group telegrams or Physical telegrams is
intended only for testing purposes. This setting should not be used during
normal operations.
ETS-Text | Selection [Factory default] | Comment |
---|---|---|
Configuration | groups. physical: route configure [groups, physical: route] | – |
Route: the telegrams are routed.
– Configure: the following parameters can be set manually.
Physical telegrams| 1. transmit all
2. block [transmit all]| 1. All physical telegrams are transmitted.
2. No physical telegram is transmitted.
Physical: Repetition when errors on mainline| 1. no
2. normal
3. reduced [reduced]| If a transmission error (e.g. due to a missing
receiver) is found after sending a Physical telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.
Group: Repetition when errors on mainline| 1.no
2. normal
3. reduced [reduced]| If a transmission error (e.g. due to a missing
receiver) is found after sending a Group telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.
Telegram confirmations online| 1. if routed
2. always [always]| 1. Only telegrams with are to be routed are confirmed on
the mainline (ACK).
2. Each telegram on the man fine is confirmed (ACK).
Send confirmation on your own telegrams| 1. yes
2.no [yes]| If a transmission error (e.g. due to a missing receiver) is found
after sending a group telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once..
Please note:
If the parameter “Send confirmation on own telegrams” is set to yes the line
repeater will send an ACK systematically on any own routed telegram. With the
repeater using no filter table it is useful to send an ACK with every routed
telegram.
Subline
ETS-Text | Selection [Factory default] | Comment |
---|---|---|
Configuration | groups. physical: route configure [groups, physical: route] | – |
Route: the telegrams are routed.
– Configure: the following parameters can be set physically.
Physical telegrams| 1. transmit all
2. block [transmit all]| 1. All physical telegrams are transmitted.
2.No physical telegram is transmitted.
Physical: Repetition If errors on the subline occur| 1.no
2. normal
3. reduced [reduced]| If a transmission error (e.g. due to a missing
receiver) is found after sending a Physical telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.
Group: Repetition if errors on the subline occur| 1.no
2. normal reduced [reduced]| If a transmission error (e.g. due to a missing
receiver) is found after sending a group telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.
Telegram confirmations online| 1. if routed
2. always [always] (ACK).| 1. Only telegrams that are to be routed are
confirmed on the subline
2. Each telegram on the sub line is confirmed (ACK).
Send confirmation on your own telegrams| 1. yes
2.no [yes]| If a transmission error (e.g. due to a missing receiver) is found
after sending a group telegram on the mainline:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once..
01504.2 EN 03 2102
Viale Vicenza 14
36063 Marostica VI – Italy
www.vimar.com