SloanLED SYM-W Symphony Wall Mount Luminaire Installation Guide
- June 4, 2024
- SloanLED
Table of Contents
SloanLED SYM-W Symphony Wall Mount Luminaire Installation Guide
Installation Guide
WARNING: RISK OF FIRE, EXPLOSION, OR ELECTRIC SHOCK
-
This product should be installed, inspected, and maintained by a qualified electrician only.
-
Turn off electrical power before inspection, installation, or removal.
-
Use only UL (or other NTRL) approved wire for input/output connections. Minimum size 18 AWG or 14 AWG for continuous runs.
-
Ensure LEDs and drivers are cool to touch when performing maintenance. Ensure supply voltage is same as rated voltage of luminaire.
-
Do not install in hazardous atmosphere.
-
Do not install in an application where ambient temperature exceeds rated operating temperature.
Before Starting
- Ensure supply power is shut off.
- Unpack fixture and ensure there are no damaged or missing parts.
NOTE: Fixture must be sealed where it contacts mounting surface with a silicone sealant.
Prepare electrical wiring
Electrical requirements
- LED driver must be supplied with voltage specified on product label and connected in accordance with NEC Article 600 and local codes. Use min. 75° C supply.
Grounding instructions
- Grounding and bonding of overall system shall be done in accordance with NEC Article 600 and local codes.
Wiring Diagram
Standard Installation
-
Uninstall Quick Mount Bracket from fixture base plate by unscrewing two (2) hex socket fasteners.
-
Level Quick Mount Bracket to intended altitude. Install Quick Mount Bracket to wall.
-
Lift fixture up and tilt slightly toward wall mounted Quick Mount Bracket as shown. Hook fixture base plate with Quick Mount Bracket.
-
Fasten fixture tightly to Quick Mount Bracket.
Line Voltage Passive Infrared Sensor
WARNING
NOTE: Warm up time is 40 seconds. After the sensor connects input power,
light will stay on 40 seconds, then go to dimming to work normally.
NOTE: Factory default setting: 100% sensitivity. Hold time: 10 seconds.
Daylight sensor: 30 lux. Dimming level: 30%. Dimming time: 60 minutes.
NOTE: When any setting is changed by DIP switch or remote control,
fixture that sensor is connected to will turn ON/OFF as confirmation.
Utilizing Field and Introduction
BRI810-B-M8 is a passive infrared occupancy sensor, as a fixture sensors mounts in indoor light fixture and provides bi-level control. It works by 120-277 VAC power and controls 0-10 VDC LED drivers or dimming ballasts. All controls parameters (Hold time, daylight sensor threshold, stand-by level, stand-by time) are adjustable via DIP switch.
Function and Options
The passive infrared occupancy sensor can achieve tri-level dimming control for some areas that require a light change notice before switching OFF. It offers three levels of light control: 100% – dimming light (0%, 10%, 30%, 50%) – OFF, and two periods of selectable waiting time: motion hold time and stand- by time. Selectable daylight threshold and choice of detection area.
-
With sufficient natural light, light does not switch ON when presence is detected.
-
With insufficient natural light, sensor automatically switches light ON when presence detected.
-
No presence detected, light still dims to 0% / 10% / 30% / 50% (options) stand-by level after hold time.
-
Light automatically switches OFF after stand-by time elapsed.
Specifications
- Power supply 120/277 VAC, 50/60 Hz
- Maximum load @-40° F to +158° F (-40° C to +70° C)
- Resistive/Tungsten – 600 W @ 120 V
- Electronic Ballast (LED) – 800 VA @ 120 V / 1200 VA @ 277 V
- Dim control output 0-10 V, max. 25 mA sinking current
- Detection radius/angle Max. 26 ft (8 m) / 360°
- Mounting height Max. 40 ft
- Humidity Max. 95% RH
- Temperature -40° F to +158° F (-40° C to +70° C)
Sensor Coverage
Parameter Settings by DIP Switch
1, 2 Set sensitivity
3, 4 Set hold time
5, 6 Set lux
7, 8 Stand-by light level
9, 10 Stand-by time
Detection Range Setting (sensitivity)
Detection range can be reduced by selecting combination on DIP switches to fit your specific application.
**sensitivity
**
Hold Time Setting
Lamp can be set to stay ON for any period of time between approximately 10 seconds and a maximum of 15 minutes. Any movement detected within the allotted time will restart timer. It is recommended to select the shortest time for adjusting detection zone and for performing walk test.
**Time
**
Light Control Setting
Chosen lamp response threshold can be infinitely from approximately 10 – 50 lux.
**Light
**
Stand-by Light Level Setting
**Stand By Level
**
Stand-by Time Setting
**Stand by Time
**
Parameter Setting by Remote Control in Manual of RC-100 Installation