TASK Power LP36HR18NDWWT27 Lighted Power Strip Instruction Manual

June 17, 2024
TASK power

TASK Power LP36HR18NDWWT27 Lighted Power Strip

TASK-Power-LP36HR18NDWWT27-Lighted-Power-Strip-PRODUCT

General Guidelines

  • The power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI prior to the connection at LPS.
  • All wiring must meet NEC® and local codes.
  • Light valance is recommended.
  • Firmly insert the plug straight into the receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed

Turn power off at the panel. Carefully pry open each piece with a tool (provided). Insert the Romex connector into the knockout hole inside of the back frame. Pull wires into LPS.

Wiring for Combined Light and Receptacle Circuit – Non-Dimmable

TASK-Power-LP36HR18NDWWT27-Lighted-Power-Strip-FIG1

  • Step 1 : Secure LPS to wall by screwing into wall studs or use the anchors provided. If running two circuits, one for receptacles, one for lighting, connect fixture wires to appropriate Romex wires. BLACK to BLACK. WHITE to WHITE. Ground all GREEN wires to PEM studs inside of back frame.
  • Step 2 : When connecting 2 or more LPS fixtures, run Romex from fixture to fixture. Ground each section to the next.
  • Step 3: To terminate last LPS, use wire nuts on ends of the wires.
  • Step 4: Snap cover in place and turn the power on.

Wiring for Separate Light and Receptacle Circuits

TASK-Power-LP36HR18NDWWT27-Lighted-Power-Strip-FIG2

Step 1: Secure LPS to the wall by screwing into wall studs or use the anchors provided. If running two circuits, one for receptacles, one for lighting, connect fixture wires to appropriate Romex wires. BLACK to BLACK. WHITE to WHITE. Ground all GREEN wires to PEM studs inside of back frame.
Step 2: When connecting 2 or more LPS fixtures, run Romex from fixture to fixture. Ground each section to the next.
Step 3 : To terminate last LPS, use wire nuts on the ends of the wires.
Step 4: Snap the cover in place and turn the power on.

Wiring Diagram for Combined Light & Receptacle Circuit – Non-Dimmable 

TASK-Power-LP36HR18NDWWT27-Lighted-Power-Strip-FIG3

Wiring Diagram for Separate Light & Receptacle Circuits 

TASK-Power-LP36HR18NDWWT27-Lighted-Power-Strip-FIG4

General Guidelines

  • The power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI prior to the connection at LPS.
  • All wiring must meet NEC® and local codes.
  • Light valance is recommended.
  • Firmly insert the plug straight into the receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed.

Turn the power off at the panel. Carefully pry open each piece with tool (provided). Insert the Romex connector into the knockout hole inside of the back frame. Pull wires into LPS.

TASK-Power-LP36HR18NDWWT27-Lighted-Power-Strip-FIG6

TASK-Power-LP36HR18NDWWT27-Lighted-Power-Strip-FIG7

Remote Power Supply- 120V Entry

  • Step 1 : Secure LPS to the wall by screwing into wall studs or use the anchors provided. Connect BLACK to BLACK, WHITE to WHITE. Ground all GREEN wires to PEM studs inside of the back frame.
  • Step 2: When connecting two LPS, run Romex from fixture to fixture. Ground each section to the next.
  • Step 3: To terminate the last LPS, use wire nuts on the ends of the wires.

Remote Power Supply-Low Voltage Entry

  • Step 4: Using an appropriate knockout hole, pull low voltage wire from the remote power supply into the low voltage space, connect the BLACK wire (negative) to the BLACK wire from the lights and the RED wire (positive) to the RED wire.
  • Step 5 : Snap the cover in place and turn the power on.
  • Customer Service: 800.445.6404

Design Services

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

TASK power User Manuals

Related Manuals