TASK Power 2700K Lighted Power Strip Instruction Manual
- May 15, 2024
- TASK power
Table of Contents
- General Guidelines
- Wiring for Combined Light and Receptacle Circuit – Non Dimmable
- Wiring for Separate Light and Receptacle Circuits
- Wiring Diagram for Combined Light & Receptacle Circuit – Non Dimmable
- Wiring Diagram for Separate Light & Receptacle Circuits
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TASK Power 2700K Lighted Power Strip Instruction Manual
Customer Service: 800-445-6404 www.TaskLighting.com Design Services & Tech Support: 866-848-9094 DesignAndSupport@TaskLighting.com
General Guidelines
- Power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI prior to the connection at LPS.
- All wiring must meet NEC® and local codes.
- Light valance recommended.
- Firmly insert plug straight into receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed.
Turn power off at panel. Carefully pry open each piece with tool (provided). Insert Romex connector into knockout hole inside of back frame. Pull wires into LPS.
Wiring for Combined Light and Receptacle Circuit – Non Dimmable
Step 1 Secure LPS to wall by screwing into wall studs or use anchors provided.
Connect BLACK Romex wire to BLACK wire from receptacles and switch. Connect
WHITE Romex wire to WHITE wire from receptacles and driver. Ground all GREEN
wires to PEM studs inside of back frame.
Step 2 When connecting 2 or more LPS fixtures, run Romex from fixture to
fixture. Ground each section to the next.
Step 3 To terminate last LPS, use wire nuts on ends of wires.
Step 4 Snap cover in place and turn power on.
Wiring for Separate Light and Receptacle Circuits
Step 1 Secure LPS to wall by screwing into wall studs or use anchors provided.
If running two circuits, one for receptacles, one for lighting, connect
fixture wires to appropriate Romex wires. BLACK to BLACK. WHITE to WHITE.
Ground all GREEN wires to PEM studs inside of back frame.
Step 2 When connecting 2 or more LPS fixtures, run Romex from fixture to
fixture. Ground each section to the next.
Step 3 To terminate last LPS, use wire nuts on ends of wires.
Step 4 Snap cover in place and turn power on.
Wiring Diagram for Combined Light & Receptacle Circuit – Non Dimmable
Wiring Diagram for Separate Light & Receptacle Circuits
General Guidelines
- Power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI prior to the connection at LPS.
- All wiring must meet NEC® and local codes.
- Light valance recommended.
- Firmly insert plug straight into receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed.
Remote Power Supply- 120V Entry
Step 1 Secure LPS to wall by screwing into wall studs or use anchors provided.
Connect BLACK to BLACK, WHITE to WHITE. Ground all GREEN wires to PEM studs
inside of back frame.
Step 2 When connecting two LPS, run Romex from fixture to fixture. Ground each
section to the next.
Step 3 To terminate last LPS, use wire nuts on ends of wires.
Remote Power Supply-Low Voltage Entry
Step 4 Using appropriate knockout hole, pull low voltage wire from remote
power supply into the low voltage space, connect BLACK wire (negative) to
BLACK wire from lights and RED wire (positive) to RED wire.
Step 5 Snap cover in place and turn power on.
Customer Service: 800.445.6404 · Design Services/Technical Support: 866.848.9094 · TaskLighting.com