TASK power DV Series Lighted Power Strip Instruction Manual
- October 30, 2023
- TASK power
Table of Contents
TASK power DV Series Lighted Power Strip
Product Information
The Lighted Power Strip is a product that provides lighting and power outlets under cabinets or shelves. It comes in two series, the DV Series with a built- in power supply and the RM Series without a built-in power supply. The DV Series has factory-wired circuits for combined light and receptacle or separate light and receptacle circuits. On the other hand, the RM Series requires a remote power supply for operation.
Product Usage Instructions
Installation Instructions for LPS WITH Built-In Power Supply
- Step 1: Turn off power at the panel. Using the tool provided, carefully pry open each piece of the Lighted Power Strip. Insert Romex connector into the knockout hole inside the back frame. Pull wires into LPS.
- Step 2: Secure LPS to the wall by screwing into wall studs or use anchors provided. Connect BLACK Romex wire to BLACK wire from receptacles and switch. Connect WHITE Romex wire to WHITE wire from receptacles and driver. Ground all GREEN wires to PEM studs inside of back frame.
- Step 3: When connecting 2 or more LPS fixtures, run Romex from fixture to fixture. Ground each section to the next.
- Step 4: To terminate last LPS, use wire nuts on the ends of the wires. Snap the cover in place and turn the power on.
Installation Instructions for LPS WITHOUT Built-In Power Supply
- Step 1: Turn off the power at the panel. Using the tool provided, carefully pry open each piece of the Lighted Power Strip. Insert the Romex connector into the knockout hole inside the back frame. Pull wires into LPS.
- Step 2: Secure LPS to the wall by screwing into wall studs or use the anchors provided. Connect BLACK to BLACK, WHITE to WHITE. Ground all GREEN wires to PEM studs inside of the back frame.
- Step 3: When connecting two LPS, run Romex from fixture to fixture. Ground each section to the next.
Wiring Diagram for 18-1/2 LPS WITH Built-In Power Supply
The wiring diagram shows the positive and negative terminals of the driver,
back frame, divider plate, and cover. It also indicates that the 120V
receptacle circuit must be GFCI protected. The wiring diagram illustrates the
factory-wired circuits for combined light and receptacle or separate light and
receptacle circuits.
Installation instructions
Lighted Power Strip DV Series
Installation Instructions for LPS WITH Built-In Power Supply
General Guidelines
- The power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI prior to the connection at LPS.
- All wiring must meet NEC® and local codes.
- Light valance is recommended.
- Firmly insert plug straight into the receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed.
Turn power off at panel. Carefully pry open each piece with tool (provided). Insert Romex connector into knockout hole inside of back frame. Pull wires into LPS.
Wiring for Combined Light and Receptacle Circuit – Non Dimmable
-
Step 1
Secure LPS to wall by screwing into wall studs or use anchors provided. Connect BLACK Romex wire to BLACK wire from receptacles and switch. Connect WHITE Romex wire to WHITE wire from receptacles and driver. Ground all GREEN wires to PEM studs inside of back frame. -
Step 2 When connecting 2 or more LPS fixtures, run Romex from fixture to fixture. Ground each section to the next.
-
Step 3 To terminate last LPS, use wire nuts on ends of wires.
-
Step 4 Snap cover in place and turn power on.
Wiring for Separate Light and Receptacle Circuits
- Step 1 Secure LPS to wall by screwing into wall studs or use anchors provided. If running two circuits, one for receptacles, one for lighting, connect fixture wires to appropriate Romex wires. BLACK to BLACK. WHITE to WHITE. Ground all GREEN wires to PEM studs inside of back frame.
- Step 2 When connecting 2 or more LPS fixtures, run Romex from fixture to fixture. Ground each section to the next.
- Step 3 To terminate last LPS, use wire nuts on ends of wires.
- Step 4 Snap cover in place and turn power on.
Wiring Diagram for Combined Light & Receptacle Circuit – Non Dimmable
Wiring Diagram for Separate Light & Receptacle Circuits
General Guidelines
- Power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI prior to the connection at LPS.
- All wiring must meet NEC® and local codes.
- Light valance recommended.
- Firmly insert plug straight into receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed.
- Turn power off at panel. Carefully pry open each piece with tool (provided). Insert Romex connector into knockout hole inside of back frame. Pull wires into LPS.
Remote Power Supply- 120V Entry
-
Step 1 Secure LPS to the wall by screwing into wall studs or use the anchors provided. Connect BLACK to BLACK, WHITE to WHITE. Ground all GREEN wires to PEM studs inside of back frame.
-
Step 2 When connecting two LPS, run Romex from fixture to fixture. Ground each section to the next.
-
Step 3 To terminate the last LPS, use wire nuts on the ends of the wires.
Remote Power Supply-Low Voltage Entry -
Step 4 Using the appropriate knockout hole, pull a low voltage wire from the remote power supply into the low voltage space, connect the BLACK wire (negative) to the BLACK wire from the lights and RED wire (positive) to RED wire.
-
Step 5 Snap the cover in place and turn the power on.
Customer Service: 800.445.6404
- Design Services/Technical Support: 866.848.9094
- TaskLighting.com
References
- Task Lighting | Task Lighting Under Cabinet | Bathroom Lighting
- Task Lighting | Task Lighting Under Cabinet | Bathroom Lighting
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>