ICM518 Surge Protective Device Installation Guide
- June 17, 2024
- ICM
Table of Contents
ICM518 Surge Protective Device
IMPORTANT SAFETY INFORMATION
ELECTRICAL SHOCK HAZARD! – Before installing this unit, turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position.
- WARNING — No Serviceable Parts (Attention: Aucune pièce replicable ou repairable).
- WARNING — Shock hazard — Do not open (ATTENTION – RISQUE DE CHOC – NE PAS OUVRIR).
Please follow all State, Local and National electrical codes when installing this product. Installation should only be done by a licensed electrician for Type 1 devices or a licensed HVAC technician for Type 2 devices.
INSTALLATION INSTRUCTIONS
The conductors used to connect the SPD shall not be any longer than necessary and shall avoid unnecessary bends.
-
Turn off the main breaker and/or main power to the service disconnect.
-
Verify your mains voltage and match that with the ICM518 ratings.
-
Remove the cover on the service disconnect or the electrical panel.
-
Mount the ICM518 through the 3/4” conduit connection of the electrical panel.
-
Remove the retaining ring and washer on the ICM518.
-
Feed the wires into the electrical panel or service disconnect.
-
Re-secure the retaining ring and washer.
-
Route the white wire to the neutral lug and secure.
Wiring Type 1 installation-
Route the two black wires to the appropriate L1 and L2 connections before the breaker panel as seen in the wiring diagram for Type 1 installation and according to your local, state, and national electrical codes.
-
Connect the white wire to the Neutral Bus.
Wiring Type 2 installation -
Route and connect the two black wires (L1 and L2) to the individual breakers on the circuit breaker panel as seen in the wiring diagram for Type 2 installation and according to your local, state and national electrical codes.
-
Connect the white wire to the Neutral Bus.
-
-
Reinstall the cover on the service disconnect or the electrical panel.
-
Restore power; Green LED should be on indicating full protection.
MAINTENANCE
Periodically check the LED status on the SPD. If the Green Light is OFF, the protection is no longer available and the SPD needs to be replaced immediately. 12 AWG stranded copper wire or larger required. Product contains no serviceable parts. This device features an internal protection that will disconnect the surge protective component at the end of its useful life but will maintain power to the load – now unprotected.
MODE OF OPERATION
The ICM518 is a UL Listed Type 1&2 Surge Protective Device for 240 VAC Split Phase voltage configurations. When a surge occurs, the ICM518 will absorb the surge up to the limits expressed in the specifications section of this guide. The ICM518 incorporates thermal protection on the surge elements (TMOV’s) which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. The ICM518 has a status light on the control which identifies operational status when illuminated. The ICM518 can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications. Suitable for use on a circuit capable of delivering not more than 200kA RMS symmetrical amperes, 240V maximum (Convient à des circuits produisant au plus 200kA RMS A eff.”, 240V maximum).
SPECIFICATIONS
Description | Ratings |
---|---|
Service Voltage | Split Phase 240V AC |
Short Circuit Current Rating (SCCR) | 200kA |
Nominal Discharge
! Current (In)| 20 kA
SPDType| Type 1 (Can also be used in Type 2 application ns)
Surge Protection T echnology| TFMOV
Protection Mode| L1-l 2, ll -N, L2 -N
VPR (Vpk)| VOLTS (V) MODE VPR (Vpk) 240 L-L 1 2 0
0 L-N700
Maximum Continuous Operation Voltage (MCCOY)| L -L: 300
VAC
L-N: 150 VAC
Inpu t . Power Frequency| 50/60Hz
Diagnostics| G reen LED “ndi cat es surge prot ection prese nt
Enclosure Rating| NEMA / Type 4X watertight plastic enclosure for
outdoor and indoors installation
Installation Point| Electrical panel / disconnect
Dimensions| 4 .3″ X 4.1″ X 2.3″
Operating T emperature| -4 0°f to 185°F (-40 °( t o 85°C)
Operating Humidity| Less than 85%, non condensing
Operating Altitude| Less than 2000 meters
Agency Certification and Approvals| ANSA/UL 1449 4th Edition
Listed Device – cULus Listed
WIRING DIAGRAMS – SPLIT PHASE CONFIGURATION
ICM518 is a Type 1 and 2 SPD, designed to be compatible with a 240 VAC Split Phase configuration. Please check your supply voltage configuration and voltage levels before installing the ICM518 per wiring diagrams below.
Type 1 Wiring – Fuse Disconnect
Type 2 Wiring – Circuit Breaker
Note 1:
For the ease of checking the SPD protection status, the LED display should face outwards after installation has been complete.
Note 2:
ICM518 is a Type 1 and 2 SPD, designed to be compatible with 240 VAC Split Phase configuration. Please check your supply voltage configuration and voltage levels before installing the ICM518 per wiring diagram.
Note 3:
- When installing the Surge Protecting Device (SPD), avoid sharp bends in the conduit and long line sets.
- Keep the mounting conduit straight and short in length.
LIMITED LIFETIME PROTECTION WARRANTY
Review enclosed warranty information for full details & registration
information
For warranty registration, please go to
www.icmcontrols.com and click on Warranty
Registration
CUSTOMERS SUPPORT
7313 William Barry Blvd., North Syracuse, NY 13212 800.365.5525
Phone: 315-233-5266 | Fax:
315-233-5276 |
www.icmcontrols.com
LIAF247-1