PS-INV-12.5KW-60A-XX Savant Power Storage User Guide
- June 17, 2024
- SAVANT
Table of Contents
PS-INV-12.5KW-60A-XX Savant Power Storage
User Guide
PS-INV-12.5KW-60A-XX Savant Power Storage
Savant Power Storage [60A]
Quick Reference Guide
Box Contents
(1) Savant Power Inverter (PS-INV-12.5KW-60A-XX)
(8) Power Storage 20 Battery (PS20-BATT-20KWH)
(1) Savant Power Director
(1) Battery Crate (8 x Modules)
(1) Conduit Nipple Kit
(1) Mounting & Installation Kit
(4) M5x12 Screws
(4) M5x10 Screws
(4) M10 Expansion Screws
(4) M6 Expansion Anchor Screw
Specifications
Environmental
Temperature| Inverter: -13°F to 131°F (-25°C to 55°C)
Battery: 32°F to 113°F (0°C to 45°C)
Humidity| 0% to 95% Relative Humidity (non condensing)
Altitude Rating| Less than 9842 ft
Rating| NEMA4X
Dimensions and Weights
Height | Length | Depth | Weight |
---|---|---|---|
85.4 in (216.92 cm) | 25.6 inch (65.02 cm) | 12.2 inch (30.988 cm) | 600 lbs |
(272.15 kg)
Inverter Power
Maximum Output Current| Grid Transfer Time| Maximum Surge Output| Maximum
Passthrough Per Inverter
12.5 kW| < 70ms| 16 kVA, 10s 21 kVA, 20ms| 60A
Battery Power
Battery Capacity | 52 Ah / 20 kWh |
---|---|
Maximum Power | 12.5kW |
Standards
Wi-Fi | 2.4 GHz IEEE 802.11 b/g/n |
---|
Regulatory
Safety and Emissions | FCC Part 15 Class B **** |
---|---|
Contains FCC ID: | 2AA9B10 |
Certifications | UL 1741 SA, UL 1741 PCS, UL9540, UL 1973, UL 1642, UL 1998, |
CSA 22.2
RoHs| Compliant
Inverter Front Panel Right Panel Left Panel
Descriptions
A | Inverter Status LEDs | See Inverter Status LEDs. |
---|---|---|
B | Inverter Front Panel | Remove panel to reveal inverter wiring area. |
C | ON/OFF Button | Power on or off the Savant Power Storage. |
D | Grid Switch | Connect or disconnect the Grid input. |
E | Conduit Knock- outs | Knockouts for AC Conductor Conduits. |
F | Antennas | Wi Fi, GPS, 4G Main, and 4G DIV Antennas |
G | Reset Button | Press to reset inverter status. |
H | PV Switch | Emergency off switch for PV arrays. |
I | Battery and Communication Caps | Waterproof caps. |
J | Network | Network connection for the inverter to communicate with the |
greater Savant Power System.
K| PV Inputs| MPPT Inputs.
L| I/O Ports| See Inverter I/O Ports.
M| Inverter Wiring| Pre-installed inverter wiring.
N| Battery Inputs| Battery power inputs.
O| GRID, LOAD, & GEN Connections| Grid, Load, and Generator connections.
P| Ground| Inverter & battery grounding connections.
Inverter I/O Ports
Front Input/Outputs
A | Status LED Table | See the Status LED table |
---|---|---|
B | Network | RJ45 connection for wired internet connection |
C | USB Ports | Used for local software updating. |
D | SD | Enables local data collection without internet connection. |
E | Reset | Reset button to reset inverter status. |
F | CLED | Power input for LEDs. |
G | GPIO Ports | See the Savant Power Storage 20 Installation Guide. |
H | BCMS | Battery Monitor System Communication Port |
I | RS-485Port | See the Savant Power Storage 20 Installation Guide. |
Inverter Status LEDs
Status LEDs & Inverter States
A| Network| Solid Red: Energy management unit startup in progress.
Blinking Red: Ready for network connection.
Blinking Green: Wi-Fi network and password detected, or Ethernet cable
detected, connecting to router.
Solid White: Connecting to the Internet.
Solid Green: Internet connected successfully.
---|---|---
B| Status| Blinking Blue: System updating.
Blinking Red: Communication fault between energy management unit and battery
system, inverter unit, or PV unit.
Solid Red: Energy management unit internal communication fault.
Blinking Green: System is turned off by energy management unit.
Solid Green: System running normally.
C| Power| On: Grid, Generator, or Load power is normal.
Off: No power input
Blinking: Grid, Generator, or Load power is abnormal.
D| Run| Solid Green: Inverter/PV charging unit running normally
Solid Red: Inverter unit fault.
Solid Yellow: PV charging unit fault, or system into over-temperature
protection.
Blinking Yellow: Inverter/PV charging unit alarming.
Blinking Green: Inverter unit/PV charging unit updating.
BMS Access Panel
A | 12V DC | Battery enclosure 12VDC connection. |
---|---|---|
B | REF, BAT+ & BAT- | Positive, negative, and REF battery connections. |
C | Ground | Ground connection to Power Storage 20. |
D | CAN | CANBUS Port to communicate with the Savant inverter. |
E | Fuse Box | Overcurrent protection for battery modules. |
F | System SoC | Total system State of Charge in 25% increments. |
G | Battery System Status Indicator | Blinking Yellow: Battery System is |
starting up or an update in progress.
Blinking Blue: Battery System is in SelfInspecting mode.
Solid Green: Running normally.
Solid Yellow: An alarm has been raised.
Solid Red: A fault has been detected.
Battery Access Panel
A | Power Switch | Toggle ON or OFF all batteries. |
---|---|---|
B | Reset Button | Press to restart battery system. |
C | Status LED | Blinking Yellow: Startup or update in |
progress
Blinking Blue: Self-inspecting
Solid Green: Running normally
Solid Yellow: Alarming
Solid Red: Protection/Fault
D| Start Button| Press to start battery system.
E| Battery Status LED| Blinking Yellow: Startup or update in progress
Blinking Blue: Battery Module is in SelfInspecting mode.
Solid Green: Running normally.
Solid Yellow: An alarm has been raised.
Solid Red: A fault has been detected.
Bracket Installation
- Open the battery enclosure with a PH2 Philips screwdriver and remove the accessories kit.
- Assemble the bracket as shown using M5x12 screws.
- Attach the bracket to the back side of the battery system with M5x12 machine screws. Tighten to 26.5 in-lbs torque.
- Drill a 1/2 in (12mm) hole with a 2.75 in (70mm) depth into the floor. Embed the anchor expansion bolts and affix the cabinet to the ground.
- Install the bracket on the wall with M6x50 tapping screws.
IMPORTANT NOTES:
– When installing it on a concrete wall, properly drill into the wall with M6x50 expansion anchor screws.
– If Savant Power Inverter is installed separately from battery system, install the bracket on a surface capable of supporting its weight using M6x50 tapping screw. Then hang Savant Power inverter on the bracket, and fasten it with M4x16 screws.
Inverter Installation
-
Remove the battery seal cap marked BAT/COM on the bottom left of the Savant Power Inverter.
-
Remove the Battery Status panel side communication cable panel.
-
Hang the inverter on the bracket.
-
Fasten the Savant Power Inverter and the bracket with M5x12 machine screws. (Torque: 26.5 in-lbs).
-
Fasten Savant Power Inverter and the battery cabinet with conduit and screw kit, as shown.
-
Number all battery labels with a number 1-8.
-
Install battery 8 in the bottom battery slot. Then continue to install all batteries in ascending slots in reverse numerical order, with battery 8 on the bottom and battery 1 in the top. See the diagram to the right for reference.
NOTE: Always keep the batteries connected in the order that they were originally installed. -
Fasten all modules on both sides using M4x8 screws (Torque: 10.5 in-lbs).
Inverter Installation
- Connect battery system to the Savant Power Inverter with ground wire.
- Make the REF, BAT- , BAT+ connections from the inverter through the conduit to the corresponding connections in the battery access panel through the conduit.
- Connect the DC 12V wire between the inverter and the battery battery access panel.
- Connect the BCMS port of the Savant Power Inverter to the CANBUS connection of the Battery Status Panel.
- Make all connections between the inverter and the electrical system. For more information, see the Savant Power Storage 20 Deployment Guide.
- (Optional) Connect Savant Power Storage 20 to photovoltaic array. NOTE: The diagram below represents DC coupled PV arrays.
- Connect Savant Power Storage 20 to the same network switch as the Power Director OR the network port of the Power
- Director itself using a CAT5 or higher Ethernet cable.
More Information
To continue deployment and configure the Savant Power Storage 20, see the
following documentation.
Savant Power Storage App Setup Guide
|
Savant Power Storage 20 Installation Guide
---|---
|
<https://support.savant.com/redirect?qrParm=SPS20-Commissioning-Guide>
|
<https://support.savant.com/redirect?qrParm=PowerStorage20_Install-Manual>
Copyright © 2023 Savant Systems, Inc
090523 009-2396-00
Savant Power Storage QRG [60A]
45 Perseverance Way, Hyannis MA 02601
www.savantpower.com | 508.683.2500
Documents / Resources
|
SAVANT PS-INV-12.5KW-60A-XX Savant Power
Storage
[pdf] User Guide
PS-INV-12.5KW-60A-XX Savant Power Storage, PS-INV-12.5KW-60A-XX, Savant Power
Storage, Power Storage, Storage
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>