NATIONAL FIRE PRODUCTS NFP2401XX Bracket Suspended Hard Lid Ceilings Instruction Manual

June 17, 2024
National Fire Products

NATIONAL FIRE PRODUCTS NFP2401XX Bracket Suspended Hard Lid Ceilings

NATIONAL FIRE PRODUCTS NFP2401XX Bracket Suspended Hard Lid
Ceilings

NFP2401XX Figure Number

Installation instructions

Product Information

SpecflexTM Bracket for Suspended and Hard Lid Ceilings

The SpecflexTM Bracket is designed for use in suspended and hard lid ceilings. It is used to support the Specflex sprinkler drop system components. The bracket is compatible with NFP2401XX Figure Number.

Specifications

  • Required system parts: Flexible Hose (Braided) NFP2401, Pre-Assembled Bracket
  • Required Tools: Pipe Wrench, Screwdriver, PTFE Tape

Product Usage Instructions

WARNING

  • You must read and understand all instructions and warnings before attempting to install any Specflex sprinkler drop system components.
  • Failure to follow these instructions can lead to improper operation, resulting in serious injury, death or property damage.
  • We recommend wearing safety glasses or goggles, a hard hat and shoes with foot protection during installation.

REQUIRED system parts

  • Flexible Hose (Braided)
  • NFP2401 Pre-Assembled Bracket

REQUIRED Tools

  • Pipe Wrench, Screwdriver
  • PTFE Tape

ferguson.com/nfp

Installation instructions

1. Inspect the Specflex sprinkler drop system components for any sign of physical damage. Make sure all components are included and in the proper order.

2. Disconnect the inlet nipple and outlet reducer from the flexible hose and check that each sealing gasket is in place properly. Reconnect outlet reducer to the flexible hose.

3. Ensure that both end threads are clean without any damage. Apply PTFE tape to the inlet nipple threads. Use a pipe wrench to connect the inlet nipple to the branch line.

4. Use a pipe wrench to connect the flexible hose to the inlet nipple. Torque range should be a minimum of 50 to a maximum of 58 ft-lbs.

DO NOT use PTFE tape on the inlet nipple thread to connect to the Flexible hose.

5. Place the NFP2401 bracket at the desired position on the ceiling grids.

If distance between the T-bar grids is smaller or bigger than 24″, loosen the wing bolt and latch on the adjustable end bracket and adjust the width.

6. Press the bracket down against the T-bar grid to position the leg of the bracket to be fully seated on the grid without any spacing.

7. Tighten the wing bolts to secure the end brackets onto the grid. The recommended torque is 1.40–1.48 ft-lbs (190-200cN • m).

DO NOT overtighten the wing bolt with tools. This may cause damage to the wing bolt.

8. Press the release pin and open the center bracket.

Load the flex hose on the proper height position in accordance with the type of sprinkler head used.
Close the gate of the center bracket from left to right and firmly push the lever toward the stock bar until it clicks to secure the outlet reducer.

9. Verify the location marking on the outlet reducer and match the outlet location for the remaining head installations.

©2023 Ferguson Enterprises, LLC 1023 4902543

FAQ

Q: Where can I find the required system parts?

A: The required system parts, including the Flexible Hose (Braided) NFP2401 and Pre-Assembled Bracket, can be found at ferguson.com/nfp.

Q: What tools are required for installation?

A: The installation requires a Pipe Wrench, Screwdriver, and PTFE Tape.

Q: Can I use PTFE tape on the inlet nipple thread to connect to the

flexible hose?

A: No, PTFE tape should not be used on the inlet nipple thread to connect to the flexible hose.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

National Fire Products User Manuals

Related Manuals