Product Information
Specifications
- Product Name: SpecflexTM SH Sprinkler Drops
- Figure Number: 21
- Model Number: NFP21XXX
- Standards: NFP21XXX
- Maximum Length: 6ft
- Outer Diameter: 1.10 (28mm)
Features
- Braided flexible hose design
- Includes tube, isolation ring, sealing gasket, nut, nipple, reducer, braid, press ring (inner), and press ring (outer)
- Approved bracket assembly: NFP240124, NFP240724, NFP240624, NFP240148, NFP2403, NFP240424
Technical Data
- K-Factor: 5.6 (for outlet size 1/2), 8.0 (for outlet size 3/4)
- Equivalent Length of 1 Schedule 40 Pipe: UL – 27.0ft to 90.5ft, FM – 33.1ft to 72.5ft
Installation
- Ensure the length of the sprinkler drop does not exceed 6ft.
- Do not bend the sprinkler drop within 2.5 inches from the connection nuts.
Outlet Connection Options
- 1/2 outlet connection
- 3/4 outlet connection
Ordering Code Matrix
Model | Length | Outlet Size |
---|---|---|
NFP 21 | 31 | 1/2 |
NFP 21 | 36 | 1/2 |
NFP 21 | 48 | 3/4 |
NFP 21 | 60 | 1/2 |
NFP 21 | 72 | 3/4 |
Product Usage Instructions
Step 1: Installation
To install the SpecflexTM SH Sprinkler Drops, follow these steps:
- Ensure the length of the sprinkler drop does not exceed 6ft.
- Choose the appropriate outlet connection size (1/2 or 3/4).
- Attach the sprinkler drop to the outlet using the provided nut and nipple.
- If needed, use a reducer to connect the sprinkler drop to a different pipe size.
- Secure the sprinkler drop using the approved bracket assembly (NFP240124, NFP240724, NFP240624, NFP240148, NFP2403, NFP240424).
Step 2: Positioning
Position the sprinkler drop in the desired location, ensuring it is properly aligned with the target area to be covered by the sprinkler system.
Step 3: Testing
Once the sprinkler drop is installed and positioned, test the system to ensure proper water flow and coverage. Adjust the water pressure if necessary.
Step 4: Maintenance
Regularly inspect the sprinkler drop for any signs of damage or leaks. Replace any damaged components and tighten any loose connections as needed.
FAQ
- Q: What is the maximum length of the SpecflexTM SH Sprinkler Drops?
- A: The maximum length is 6ft.
- Q: Can I bend the sprinkler drops near the connection nuts?
- A: No, avoid bending the sprinkler drops within 2.5 inches from the connection nuts.
- Q: What are the available outlet connection sizes?
- A: The available outlet connection sizes are 1/2 and 3/4.
Standards
National Fire Protection Association (NFPA)
- NFPA 13: Standard for the installation of sprinkler systems
- NFPA 13D: Standard for the installation of sprinkler systems in one- and two-family dwellings and manufactured homes
- NFPA 13R: Standard for installation of sprinkler systems in residential occupancies up to and including four stories in height
- NFPA 13 Section 9.2.1.3.3.3: No hangers are required for flexible connections as long as the length does not exceed 6ft
American Society for Testing and Methods (ASTM)
- ASTM C635: Standard specifications for the manufacture, performance and testing of metal suspension systems for acoustical tile and lay-in panel ceilings
- ASTM C636: Standard practice for installation of metal ceiling suspension systems for acoustical tile and lay-in panels
Factory Mutual (FM), FM Class No, 1637
- Approved standard for flexible sprinkler hose with threaded end fittings
Underwriter’s Laboratories, Inc. (UL), UL 2443
- Standard for flexible sprinkler hose with fittings for fire protection service
International Building Code (IBC) Section 1621/American Society of Civil Engineers (ASCE) 7 9.6.2.6.2 & 9.6.2.6.2.2
- Flexible sprinkler connections are the alternative solution to install without seismic escutcheons (oops ring)
Features
- Available lengths: 31″, 36″, 48″, 60″ and 72″*
- Outlet sizes: 1/2″ and 3/4″
- Includes pre-installation positioning and identification sleeve
- Max ambient temperature rating: 225° F (UL/FM)
- Max working pressure rating: 175 psi (UL/FM)
- Minimum bend radius**: UL – 4″ / FM – 8″
- Connection: Inlet – 1″ MNPT
- Hose Diameter: I.D. = 0.85″ (21.5mm) O.D. = 1.10″ (28mm
technical data
- Hose type: Braided
- Hose: Stainless steel 304
- Nut and nipple: Zinc-plated steel
- Sealing gasket: EPDM
- Press ring (inner and outer): Stainless steel 304
- Isolation ring: Nylon
Installation
- Please refer to NFP Specflex Installation Manuals for proper installation guidelines
- 31″ and 72″ currently only available with 1/2″ outlet
- DO NOT bend within 2.5″ from connection nuts.
SH hose Bracket Approvals
BRAIDED FLEXIBLE HOSE
- Tube
- Isolation ring
- Sealing gasket
- Nut
- Nipple (1″)
- Reducer
- Braid
- Press ring (inner)
- Press ring (outer)
Friction Loss Data
- UL: 4″ minimum bend radius, where C=120
- FM: 8″ minimum bend radius, where C=120
Ordering Code Matrix