NATIONAL FIRE PRODUCTS NFP1102B Three-Way Brass Valve Owner’s Manual

June 13, 2024
National Fire Products

Three-Way Brass Valve
Figure 1102 NFP1102B

Installation

Make sure the valve is installed according to the flow indication arrow that has been cast into the valve body. The most common installation allows for a 1/4” IPS nipple between the valve and the water supply being measured. This ensures there will be adequate spacing for the sprinkler system gauge from the riser. Use either PTFE Pipe Thread Sealing Tape or a suitable pipe thread sealant when installing the valve.
CAUTION: DO NOT OVERTIGHTEN THREADS.
OVERTIGHTENING MAY CAUSE VALVE FAILURE.

Features & Benefits

  • Size: 1/4″ IPS
  • Working pressure: 300 WOG
  • Used to facilitate the installation of sprinkler system pressure gauges
  • One female inlet and two female outlets
  • Enables system gauge replacementwithout system shutdown

Technical data

  • Testing pressure:
    – Body 80 PSI air
    – Seat 80 PSI air

  • Threads: ANSI B1.20.1 (NPT)

Dimension (inches)

Part # Size A B C
NFP1102B 1/4″ 1.77 1.97 2.13

Material Chart

NO. PART NAME MATERIAL
1 Body Cast bronze B584 C84400
2 Packing nut Brass B16 C36000
3 Washer 304 Stainless steel
4 Packing PTFE teflon
5 Stem Brass B16 C36000
6 Handwheel Cast iron
7 Nameplate Aluminum
8 Handwheel nut Steel A29 GR1010

ferguson.com/nfp
©2022 Ferguson Enterprises, LLC 1122 4542590