SpecflexTM SHP Performance Sprinkler Drops

NATIONAL-FIRE-PRODUCTS-NFP-22-31-Specflex-SHP-Performance-Sprinkler-Drops-01
\(1\)

Standards

National Fire Protection Association (NFPA)

  • NFPA 13: Standard for the installation of sprinkler systems
  • NFPA 13D: Standard for the installation of sprinkler systems in one- and two-family dwellings and manufactured homes
  • NFPA 13R: Standard for installation of sprinkler systems in residential occupancies up to and including four stories in height
  • NFPA 13 Section 9.2.1.3.3.3: No hangers are required for flexible connections as long as the length does not exceed 6ft

American Society for Testing and Methods (ASTM)

  • ASTM C635: Standard specifications for the manufacture, performance and testing of metal suspension systems for acoustical tile and lay-in panel ceilings
    • ASTM C636: Standard practice for installation of metal ceiling suspension systems for acoustical tile and lay-in panels

Factory Mutual (FM), FM Class No, 1637
Approved standard for flexible sprinkler hose with threaded end fittings

  • Underwriter’s Laboratories, Inc. (UL), UL 2443
  • Standard for flexible sprinkler hose with fittings for fire protection service

International Building Code (IBC) Section 1621/American Society of Civil Engineers (ASCE) 7 9.6.2.6.2 & 9.6.2.6.2.2
Flexible sprinkler connections are the alternative solution to install without seismic escutcheons (oops ring)

Features

  • Available lengths: 31″, 36″, 48″, 60″ and 72″
  • Outlet sizes: 1/2″ and 3/4″
  • Includes pre-installation positioning and identification sleeve
  • Max ambient temperature rating: 300° F
  • Max working pressure rating: 300 psi (UL), 225 psi (FM)
  • Minimum bend radius*: UL – 2.5″/FM – 6.5″
  • Connection: Inlet – 1″ MNPT
  • Hose Diameter: I.D. = 1.14″ (29mm)
  • O. D. = 1.38″ (35mm)

Technical data

  • Hose type: Braided
  • Hose: Stainless steel 304
  • Nut and nipple: Zinc-plated steel
  • Sealing gasket: EPDM
  • Press ring (inner and outer): Stainless steel 304
  • Isolation ring: Nylon

Installation

  • Please refer to NFP Specflex Installation Manuals for proper installation guidelines
  • *DO NOT bend within 2.5″ from connection nuts.

SH hose Bracket Approvals

Bracket Approved Bracket assembly

  • NFP240124 FM, UL
  • NFP240724 FM, UL
  • NFP240624 FM, UL
  • NFP240148 FM
  • NFP2403 FM
  • NFP240424 FM

SpecflexTM SHP Performance Sprinkler Drops

BRAIDED FLEXIBLE HOSE

NATIONAL-FIRE-PRODUCTS-NFP-22-31-Specflex-SHP-Performance-Sprinkler-Drops-01
\(2\)

  1. Tube
  2. Isolation ring
  3. Sealing gasket
  4. Nut
  5. Nipple (1″)
  6. Reducer
  7. Braid
  8. Press ring (inner)
  9. Press ring (outer)

Friction Loss Data

Length (in.)| Max| Number UL| of| 90 °| Bends

FM

| Outlet Connection| K-Factor| Equivalent Length UL| of| 1″| Schedule| 40 FM| Pipe (ft)
---|---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | 5.6| 9.0| 3.5
| | | 1/2″| 8.0| | 4.4
31″| 2| 1| 3/4″| 8.0| 16.0| 5.0
| | | | 14.0| | 5.1
36″                  5                     2 8.0| | 5.1
---|---|---
3/4″               8.0| 22.0| 6.0
14.0| | 6.0
1/2″               5.6| 19.0| 6.9
48″                  6                     3 8.0| | 6.6
3/4″               8.0| 34.0| 8.4
14.0| | 8.3
1/2″               5.6| 26.0| 9.4
60″                 10                    4 8.0| | 8.1
3/4″               8.0| 40.0| 10.9
14.0| | 10.6
1/2″               5.6| 37.0| 11.9
72″                 12                    4 8.0| | 9.7
3/4″               8.0| 46.0| 13.4
14.0| | 12.9

  • UL : 2.5″ minimum bend radius, where C=120
  • FM: 6.5″ mimimum bend radius, where C=120