Danfoss IMI TRV-3 Mio Presetting Installation Guide
- June 16, 2024
- Danfoss
Table of Contents
Danfoss IMI TRV-3 Mio Presetting
Product Information
Specifications :
- Valve Type : Danfoss Mio
- Presetting Instructions: Yes
- Reference Mark : 2 1
Capacities (l/h) Setting:
| DN10| DN15| DN20
---|---|---|---
IMI TRV-3 (all size/pattern)| 13| 13| 32
IMI V-exact II (all size/pattern)| 16| 16| 20
Oventrop AV9 (all size/pattern)| 28| 28| 51
Resideo V2000SX (all size/pattern)| 29| 28| 30
(8) N| 137| 166| 225
(9) x| x| x| x
Valve Kv-values Adjustment:
The Kv-values can be adjusted on the valve’s head, ‘N’ (fully open), using
the valve protective cap tool. The tool can be turned through 180 degrees
clockwise to increase the Kv-value and counterclockwise to decrease it.
Product Usage Instructions
-
Step 1: Installation
Follow the installation guide provided with the product to properly install the Danfoss Mio valve. -
Step 2: Presetting the Valve
-
Identify the desired capacity setting based on the DN size of your valve and the specific model (IMI TRV-3, IMI V-exact II, Oventrop AV9, or Resideo V2000SX).
-
Using the valve protective cap tool, turn it clockwise to fully open the valve (‘N’ position).
-
Gradually turn the tool counterclockwise to preset the desired capacity setting according to the provided capacities table.
Note: For Kv-values adjustment, refer to the “Valve Kv-values Adjustment” section above.
FAQ (Frequently Asked Questions)
-
Q: How do I determine the appropriate capacity setting for my valve?
A: Refer to the capacities table provided in the user manual. Find the DN size of your valve and the corresponding model (IMI TRV-3, IMI V-exact II, Oventrop AV9, or Resideo V2000SX) to identify the recommended capacity setting. -
Q: Can I adjust the Kv-values of the valve?
A: Yes, the Kv-values can be adjusted using the valve protective cap tool. Refer to the “Valve Kv-values Adjustment” section for detailed instructions. -
Q: How do I install the Danfoss Mio valve?
A: Follow the installation guide provided with the product for step-by-step instructions on how to properly install the valve.
Installation Guide
Danfoss Mio presetting instructions
Capacities (l/h)
Setting| Danfoss Mio with Danfoss React ™ , Danfoss Regus ®
& Danfoss Redial ®| IMI TRV 3 (all size/
pattern)| IMI V-exact II (all size/ pattern)| Oventrop
AV9 (all size/ pattern)| Resideo V2000SX (all size/
pattern)
DN10| DN15| DN20
1| 13| 13| 32| 3| 16| 16| 20
2| 28| 28| 51| 12| 29| 28| 30
3| 49| 50| 75| 23| 47| 44| 51
4| 74| 76| 100| 29| 84| 63| 89
5| 87| 98| 122| 45| 104| 82| 136
6| 102| 116| 147| 82| 149| 101| 171
7| 110| 132| 177| 123| 187| 136| x
(8) N| 137| 166| 225| 164| 212| 180| x
9| x| x| x| x| x| 215| x
The Kv-values can be set on the valve’s head, ‘N’ (fully open) using the valve protective cap tool. This can be turned through 1800C
Danfoss A/S
Climate Solutions danfoss.com +45 7488 2222
- Any information, including, but not limited to information on the selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogs descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
- All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
© Danfoss Climate Solutions
2023.11 AN463237568408en-000101 1