Foreword

Dear customer

Thank you for purchasing a high quality Bowman swimming pool heat exchanger.

Bowman have been manufacturing swimming pool heat exchangers for over 60 years and are acknowledged as the brand leader due to their quality, heat transfer performance and durability.

Please read this Installation, Operation & Maintenance guide fully and carefully before installation to ensure your Bowman swimming pool heat exchanger operates efficiently and reliably.

Please keep this guide for future reference to ensure the long term performance of your Bowman swimming pool heat exchanger.

Should you require additional advice or assistance, please contact your Bowman stockiest or dealer.

Installation, Operation & Maintenance guides are also available in:

  • French

  • German

  • Italian

  • Spanish

  • Polish

  • Russian

  • Chinese

If you require a copy of this guide in one of these languages, visit  <https ://ej-bowman.com/downloads>/ where copies are available to download.

All rights reserved

E.J. Bowman (Birmingham) Ltd, reserve the right to change specifications without prior notice. All material contained in this brochure is the intellectual property of EJ Bowman (Birmingham) Ltd. It is protected under copyright and may not be reproduced without prior written consent of the company.

Warranty

All BOWMAN® Swimming Pool Heat Exchangers are guaranteed against manufacturing faults for a period of 12 months from the date of invoice.
Bowman titanium heat exchangers have a full 10 year guarantee on all titanium material in contact with pool water.

For full warranty terms, please see the BOWMAN® Conditions of Sale. A copy of which is available on request or can be downloaded from our website: www.ej- bowman.com

Safety

Hazards When Handling the Heat Exchanger

BOWMAN® “Swimming Pool Heat Exchangers” are constructed in accordance with current practice and recognized safety rules. Hazards may still arise from operation, such as:

  • Injury of the operator or
  • Third parties or
  • Damage to the heat exchanger or
  • Damage to property and equipment

Any person involved with the installation, commissioning, operation, maintenance or repair of the heat exchanger must be:

  • Physically and mentally capable of performing such work
  • Appropriately qualified
  • Comply completely with the installation instructions

The heat exchanger must only be used for this purpose.
In the event of breakdowns which may compromise safety, a qualified plumber must always be contacted.

Safety Instructions

The following symbols are used in these operating instructions:

Danger

This symbol indicates an immediate danger to health. Failure to comply with this instruction may result in severe injury.

Caution

This symbol indicates a possible danger to health. Failure to comply with this instruction may result in severe injury.

Take Care

This symbol indicates a possible risk to health. Failure to comply with this instruction may result in injury or damage to property.

 This symbol indicates important information about correct handling of the equipment Failure to comply with this instruction may cause damage to the heat exchanger and/or its surroundings.

Approved Use

BOWMAN® “Swimming Pool Heat Exchangers” are only approved for heating or cooling pools with boiler water, solar and heat pump systems.Any other use unless agreed by BOWMAN® is not approved. We decline all liability for damage associated or arising from such use.
The maximum working pressure is:
Heating/Cooling Side : 6 bar
Pool Water Side : 6 bar
The maximum working temperature is :
Heating/Cooling Side : 110 ºC
Pool Water Side : 100 ºC

Potential Hazards

Take Care

The heat exchanger may be damaged or leak if the maximum working pressure is exceeded.

Connections on the heating water side of the heat exchanger may reach temperatures as high as 110ºC.

Caution

The heat exchanger may heat up to the flow temperature of the heating water if there is no pool water flowing through the heat exchanger. Any plastic pipe work may be exposed to excessive temperature and suffer damage.

Safety Measures at Installation Site

Take Care

The heat exchanger should be installed in a frost free enclosure.

Ensure the maximum working pressure on either side of the heat exchanger is not exceeded or the heat exchanger or surrounding equipment may be damaged.

While the pool is in operation, weekly inspection of the heat exchanger and its connections should be made to check for leaks and external damage.

Installation

Transport / Storage

The heat exchanger must be drained prior to transportation. Once drained and dry, the heat exchanger must only be stored indoors in a non-aggressive atmosphere.

Installation

The heat exchanger should only be installed in a frost-free, dry area with a non aggressive atmosphere. Ensure easy access for assembly/disassembly.

Fitting

Before fitting, check the heat exchanger for damage, the heat exchanger can be installed above or below the pool water level, positioned horizontally or vertically, as shown below.

Horizontal Mounting
Horizontal Mounting

The heat exchanger may be damaged by chemicals. Dosing systems must be fitted downstream from the heat exchanger incorporating a non return valve. If chemicals are used, gases must be prevented from entering the heat exchanger when the filtration system is not in use.

The heat exchanger should always be installed downstream of the pumping and filtration equipment. The boiler/solar water must be pump assisted and the usual precautions taken to prevent air locks. It is recommended that an inhibitor is added to the boiler circuit to protect the system against corrosion.

The heat source should be controlled by a thermostat in the pool water pipe before the heat exchanger and set at the required pool temperature.

Connecting the Heat Exchanger

Close all isolating valves in the flow and return pipes of both circuits.

Ensure compliance with water quality and maximum permissible pressures.

When fitting the heat exchanger into the pipe work care must be taken to ensure that no debris has been introduced into the heat exchanger.

Please refer to the table below for the pool water and boiler/solar water connections.

Metric| Universal Fit| Individual Fit| | | | |
---|---|---|---|---|---|---|---
Type| EC| FC| FG| GL| GK| JK| PK
Pool Water Connection| Solvent Weld Ø48/Ø50mm (DN40 Pipe)| Solvent Weld Ø60.3/Ø63mm (DN50Pipe)| Threaded 2½” BSP| Threaded 3” BSP| Flanged PN6/10/16 DN100| Flanged PN10/16 DN125| Flanged PN10/16 DN150
Boiler / Solar Water Connection| Threaded 3/4” BSP| Threaded 1” BSP| Threaded 1¼” BSP| Threaded 1½” BSP| Threaded 2” BSP| Threaded2½” BSP Flanged PN6 – DN80| PN6 – DN100

Important pool water connection information

EC heat exchangers; feature ‘Universal Fit’ end covers designed to accommodate both metric and imperial pipe. For metric 50mm (DN40) pipe, there is a 28mm deep recess to secure the pipe to the end cover. For imperial 1½” NPS pipe, there is a 56mm deep recess to secure the pipe to the end cover. When installing 1½” NPS it is important to locate sufficient pipe length into the full recess in order to ensure a water tight seal between the pipe and the end cover. Please refer
connection information

FC heat exchangers; are supplied with adaptors which enable either 63mm (DN50) metric pipe, or 2” NPS(60.3mm) imperial pipe to be used. There is a 38mm deep recess to secure the pipe in the end cover for both pipe sizes. Please refer to diagram for more information.
connection information

FG & GL heat exchangers; when connecting an FG or GL heat exchanger to the pool water, always ensure that sufficient connecting pipe thread goes into the end cover to enable it to engage with the black coated thread. This prevents the uncoated thread being exposed to the pool water.
connection information

Counter flow installation

The heat exchanger must be installed in counter flow – i.e. where the pool water flows in the opposite direction to the heating water as shown below
Counter flow installation

NOTE: failure to install the heat exchanger in this arrangement will reduce the performance.

Integral thermostat pocket

Most Bowman swimming pool heat exchangers have an integral thermostat pocket. To ensure accurate monitoring of the pool water temperature it is important to install the thermostat on the pool water inlet to the heat exchanger.

Operation

It is essential that the following instructions are followed to prevent corrosion/erosion of the heat exchanger:

a) BOWMAN® Stainless Steel heat exchangers should not be used with salt water chlorinators or salt water pools. ( Cupro Nickel or Titanium is available for these applications).

b) Always maintain the water pH to within correct levels. The ideal pool pH should be kept within 7.4 to 7.6. On no account should it fall below 7.2 or rise above 7.8. Checks should be made daily. Recommended chemical limits for BOWMAN® Swimming Pool Heat exchangers are shown below, however any local swimming pool water guidelines should be followed for safe bathing.

Material Cupronickel Stainless Steel Titanium
Free Chlorine 1.0 – 3.0 ppm 1.0 – 3.0 ppm 15.0 ppm max.
pH 7.2 – 7.8 7.2 – 7.8 6.8 – 8.0
Calcium Hardness 200 – 400 ppm 200 – 1000 ppm 200 – 1000 ppm
Alkalinity 100 – 150 ppm 100 – 150 ppm 100 – 150 ppm
Bromine 2.0 – 4.0 ppm 2.0 – 4.0 ppm 15.0 ppm max.
Chloride Less than 150 ppm Less than 350 ppm Less than 3000 ppm

c) If a by-pass is fitted, it is essential that any valves are positioned to allow the recommended pool water flow to pass through the heat exchanger.

d) The filter unit should be checked regularly, especially if sand filters are used. If sand filters are not working correctly, fine particles of sand can flow round the pool circuit causing erosion of the pipe work, heat exchanger and pump

e) Keep the pool free from debris such as leaves, grass cuttings etc. Foreign matter can decay and increase the pH level in the pool.

f) It is essential that the correct amount of chemical is added to the pool. To allow proper dispersion of the dose in the pool water, distribution of the dose should be made to various areas of the pool. Do not dose in one area only, especially adjacent to the pool water return as this will create high acidic areas which can cause corrosion/erosion of the pool equipment.

Commissioning

Take Care

Commissioning of the heat exchanger should not be undertaken until this document has been read and understood.

Danger

Both circuits of the heat exchanger must be connected before commissioning.

Adequate provision should be made to ensure that correct operating equipment along with personal protection (PPE) in accordance with current standards is used.

Maintenance / Repair

Winter Shutdown in Frost Free Areas

When shut down in frost free premises the heat exchanger must be completely full of water and purged of air.

Winter Shutdown in Areas Exposed To Frost

Care should be taken to prevent frost damage from a winter shutdown in premises exposed to frost. We recommend draining the heat exchanger or removing it from the installation for the shutdown period.

General Maintenance

The heat exchanger should require little attention in service, however if cleaning or replacement of the tube stack is necessary the end cover screws should be tightened to the torque figures below. Note, new seals are recommended if the end covers are removed.

Type EC Series FC Series FG Series GL GK JK PK
Screw Size M6 M8 M8 M10 M12 M16 M16
Torque (Nm) 8 16 22 37 54 95 130

Typical performance with boilers

Type| Pool Capacity| Heat Transfer82ºC Boiler Water| Heat Transfer60ºC Boiler Water| Boiler Water Flow| Maximum PoolWater Flow| Weight
---|---|---|---|---|---|---
| m3                             gal| kW            Btu/h| kW Btu/h| m3/h              l/m| m3/h               l/m| kg
EC80-5113-1CEC80-5113-1S/T| 40               8,80050             11,000| 20 68,00025            85,000| 12             41,00016             55,000| 2.1 353.0               50| 9.0               15012.0               200| 3.03.0 / 2.7
EC100-5113-2CEC100-5113-2S/T
| 80             18,00090             20,000| 40 135,00050          170,000| 22             75,00030           102,000| 2.4 403.0               50| 10.2               17012.0               200| 4.54.5 / 4.0
EC120-5113-3CEC120-5113-3S/T| 120             26,000130             28,500| 70          240,00080          270,000| 40           135,00046 157,000| 3.6               604.0               67| 13.5               22515.0 250| 5.55.5 / 4.9
FC100-5114-2CFC100-5114-2S/T
| 170             37,000180             39,500| 100          340,000110          375,000| 55           190,00060 205,000| 5.4               906.0             100| 21.0               35022.8 380| 8.88.8 / 7.8
FG100-5115-2CFG100-5115-2S/T| 230             50,000250             55,000| 170          580,000190          650,000| 100           340,000110 376,000| 7.2             1208.4             140| 28.8               48033.0 550| 1616 / 14
FG160-5115-5S/T
| 320             70,000| 300        1,000,000| 170 580,000| 9.6             160| 39.0               650| 29 / 25
GL140-3708-2CGL140-3708-2T| 455           100,000478           105,000| 300 1,000,000320        1,100,000| 170           580,000180           615,000| 12.6             21013.5             225| 50.4               84054.0 900| 3030 / 27
GK190-5117-3CGK190-5117-3T| 660           145,000750           165,000| 556 1,900,000630        2,150,000| 310        1,060,000360        1,230,000| 19.2 32021.6             360| 75.0             1,25096.0             1,600| 5751
JK190-5118-3CJK190-5118-3T| 1,000           220,0001,230           270,000| 780        2,660,000960        3,280,000| 440        1,500,000540 1,840,000| 28.6             47537.5             625| 114.0 1,900150.0             2,500| 8576
PK190-5119-3CPK190-5119-3T| 1,500           330,0001,680           370,000| 1,055        3,600,0001,170        4,000,000| 585        2,000,000650 2,200,000| 44.0             73049.2             820| 175.0 2,900216.0             3,600| 120106

Add the appropriate suffix indicating tube material when ordering these part numbers (S or T).

C = Cupronickel S = Stainless steel T = Titanium. N.B. Stainless steel heat exchangers should not be used on pools fitted with salt water chlorinators or salt water pools. The performance capabilities of the heat exchangers are based on achieving a pool water temperature of 30ºC.

and with solar panels & heat pumps

T ype| Pool Capacity| Heat Transfer| Solar or Heat PumpWater Flow| Maximum PoolWater Flow| Weight
---|---|---|---|---|---
| m3| gal| kW| Btu/h| m3/h| l/m| m3/h| l/m| kg
| | Hot Water at 70°C| | |
EC120-5113-3C/S/T| 50| 11,000| 30| 102,000| 1.5| 25| 6.2| 104| 5.5 / 5.5 / 4.9
EC160-5113-5C/S/T
| 120| 26,000| 75| 256,000| 3.0| 50| 15.0| 250| 8.5 / 8.5 / 7.3
FC160-5114-5C/S/T| 200| 44,000| 130| 444,000| 4.5| 76| 23.0| 380| 17 / 17 / 15
FG160-5115-5C/S/T
| 300| 66,000| 200| 680,000| 6.6| 110| 29.0| 480| 29 / 29 / 25
| | Hot Water at 60°C| | |
EC120-5113-3C/S/T| 40| 8,800| 20| 68,000| 1.5| 25| 6.2| 104| 5.5 / 5.5 / 4.9
EC160-5113-5C/S/T
| 110| 24,000| 55| 190,000| 3.0| 50| 15.0| 250| 8.5 / 8.5 / 7.3
FC160-5114-5C/S/T| 180| 40,000| 96| 325,000| 4.5| 76| 23.0| 380| 17 / 17 / 15
FG160-5115-5C/S/T
| 230| 50,000| 150| 512,000| 6.6| 110| 29.0| 480| 29 / 29 / 25
| | Hot Water at 45°C| | |
EC120-5113-3C/S/T| 20| 4,400| 10| 34,000| 1.5| 25| 6.2| 104| 5.5 / 5.5 / 4.9
EC160-5113-5C/S/T
| 52| 11,400| 27| 92,000| 3.0| 50| 15.0| 250| 8.5 / 8.5 / 7.3
FC160-5114-5C/S/T| 94| 20,600| 47| 160,000| 4.5| 76| 23.0| 380| 17 / 17 / 15
FG160-5115-5C/S/T
| 140| 30,800| 70| 240,000| 6.6| 110| 29.0| 480| 29 / 29 / 25

Add the appropriate suffix indicating tube material when ordering these part numbers (S or T).

C = Cupronickel S = Stainless steel T = Titanium. N.B. Stainless steel heat exchangers should not be used on pools fitted with salt water chlorinators or salt water pools. The performance capabilities of the heat exchangers are based on achieving a pool water temperature of 30ºC.

Spare Parts List

We keep a comprehensive stock of spare parts. Please contact our sales department for details.
Spare Parts List

EC Spare Parts

Type| End CoverAssembly (A)| ‘O’ Seals(B)| Mounting Brackets (C)| Body(D)| Tube Stack (E)
---|---|---|---|---|---
EC80-5113-1C| | | | | 5095-1TNP
EC80-5113-1S| 5030-1| AN12NT| 5032-1| EC69-5568-1CI| 5095-1STP
EC80-5113-1T| | | | | 5095-1TIP
EC100-5113-2C| | | | | 5095-2TNP
EC100-5113-2S| 5030-1| AN12NT| 5032-1| EC70-4568-2CI| 5095-2STP
EC100-5113-2T| | | | | 5095-2TIP
EC120-5113-3C| | | | | 5095-3TNP
EC120-5113-3S| 5030-1| AN12NT| 5032-1| EC71-4568-3CI| 5095-3STP
EC120-5113-3T| | | | | 5095-3TIP
EC160-5113-5C| | | | | 5095-5TNP
EC160-5113-5S| 5030-1| AN12NT| 5032-1| EC73-4568-5CI| 5095-5STP
EC160-5113-5T| | | | | 5095-5TIP

FC Spare Parts
Spare Parts List

Ty pe| End CoverAssembly (A)| ‘O’ Seals(B)| MountingBrackets (C)| Body(D)| Tube Stack (E)
---|---|---|---|---|---
FC100-5114-2C| | | | | 5096-2TNP
FC100-5114-2S| 5031| OS46NT| 5032-2| FC70-4668-2CI| 5096-2STP
FC100-5114-2T| | | | | 5096-2TIP
FC160-5114-5C| | | | | 5096-5TNP
FC160-5114-5S FC160-5114-5T| 5031| OS46NT| 5032-2| FC73-4668-5CI| 5096-5STP5096-5TIP
| | | A| B| D|

FG, GL, GK, JK & PK Spare Parts
Spare Parts List

T ype| Non DrainEnd Cover (A)| ‘O’ Seals(B)| MountingBrackets (C)| Body(D)| Tube Stack (E)| End Cover Screws (F)| Drain End Cover (G)
---|---|---|---|---|---|---|---
FG100-5115-2C FG100-5115-2S FG100-5115-2T| FG7-2802CIC-DR| OS52NT| 5032-2| FG10-1650-2CI| 5090-2TN1P5097-2STP5097-2TIP| HS08X35DP| FG7-2802CIC-DR
FG160-5115-5CFG160-5115-5S FG160-5115-5T| FG7-2802CIC-DR| OS52NT| 5032-2| FG16-1650-5CI| 5090-5TN1P5097-5STP5097-5TIP| HS08X35DP| FG7-2802CIC-DR
GL140-3708-2C GL140-3708-2T| GL37-3140CIC| OS63NT| —| GL15-3136NF-2CI6| 3447-2TN1B5367-2TI4B| HS10X40DP| GL37-3140CIC-DR
GK190-5117-3C GK190-5117-3T| GK65-5255CIC| OS69NT| —| GK19-2865NF-3CI7| 3448-3TN1B5369-3TI4B| HS12X50DP| GK65-5255CIC-DR
JK190-5118-3JK190-5118-3T| JK4-3331CIC| OS74NT| —| JK19-3332NF-3CI8| 3450-3TN1B5371-3TI4B| HS16X70DP| JK4-3331CIC-DR
PK190-5119-3 PK190-5119-3T| PK4-2926CIC| OS81NT| —| PK19-2920HF-3CI0| 3449-3TN1B5373-3TI4B| HS16X70DP| PK4-2926CIC-DR
When an end c| over is removed| for cleaning or| maintenance,| a new ‘O’ seal sh| ould be fitted.| |

When an end cover is removed for cleaning or maintenance, a new ‘O’ seal should be fitted.

Bowman heat transfer solutions

Bowman is now established as the leading manufacturer of swimming pool heat exchangers. With tens of thousands of units operating reliably and efficiently throughout the world, you can have complete confidence when you specify Bowman heat exchangers.

Additionally, Bowman heat exchangers and oil coolers can be found in Active Fire Protection Systems, Automotive Engine Testing, Combined Heat & Power, Hydraulic Systems, Marine Engineering, plus Mining Equipment and Machinery, in a range that includes:

  • Exhaust Gas Heat Exchangers

  • Hydraulic Oil Coolers

  • Charge Air Coolers

  • Stainless Steel Heat Exchangers

  • Header Tank Heat Exchangers

  • Plate Heat Exchangers
    Bowman heat transfer solutions

  • Transmission Coolers

  • Engine Oil Coolers

EJ Bowman (Birmingham) Ltd
Chester Street, Birmingham B6 4AP, UK
Tel: +44 (0) 121 359 5401
Fax : +44 (0) 121 359 7495
Email: sales@ej-bowman.com
www.ej-bowman.com

Company Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals