TOSHIBA R32 High Wall Air Conditioner Installation Guide

June 16, 2024
Toshiba

TOSHIBA R32 High Wall Air Conditioner

TOSHIBA R32 High Wall Air Conditioner

ACCESSORY AND INSTALLATION PARTS

Indoor Unit

No.| Part name| No.| Part name
1| Installation plate × 1| 2| Wireless remote controller × 1

3| Battery × 2

| 4| Remote controller holder × 1

5| Toshiba Ultra pure        × 2

| 6| Mounting screw × 10

Accessory And Installation Parts

7| Flat head wood screw × 2

| 8| Screw × 2

9| Owner’s Manual × 1

| 10| Installation Manual × 1

11| Decorative fabric (dark gray) × 1 Decorative fabric (light gray) × 1

| 12| B Label × 2 (for Multi model)

13| Safety Manual × 1

| Outdoor Unit Given Below
14| Drain nipple × 1

| 15| Cap water proof × 2

Air filter

Clean every 2 weeks.

  1. Open the air inlet grille.
  2. Remove the air filters.
  3. Vacuum or wash and then dry them.
  4. Reinstall the air filters and close the air inlet grille.
    Air filter

Filter

Maintenance & Shelf-life
Clean every 3-6 months when dust stuck or covers the filter.

  1. Recommend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter.

  2. If necessary to use water to clean, simply use the plain water to wash the filter, dry with the sunlight for 3-4 hours or until it completely dry.
    Nevertheless, use hair drier to dry it. However, washing with water, it may reduce the performance of the filter.

  3. Replace every 2 years or sooner. (contact your dealer to purchase new filter) (P/N : RB-A622DA)
    Note: Filter life depends on the level of impurities in your operating environment. Higher levels of impurities may require more frequent cleaning and replacement. In all cases, we recommend an additional set of filters to improve the purifying and deodorizing performance of your air conditioner.
    Filter

Decorative fabric

Maintenance & Shelf-life

  • Clean when dust stuck or covers the decorative fabric.
  • Take extra care when cleaning the decorative fabric.
  • Vacuum the decorative fabric with soft brush nozzle that use for cleaning on furniture or curtain.
  • In case of getting heavy dirty on decorative fabric, please use dry cleaning service or wash by hand with warm water separated from other clothes (to avoid color staining), then line dry in the shade.
    Decorative fabric

Note:

  • Switch ‘OFF’ and unplug the air conditioner before removing the grille and decorative fabric.
  • Ensure decorative fabric are completely dry before refitting to the grille.
  • Do not put the decorative fabric in a dishwasher, washing machine, tumble dryer, oven, microwave or near an open flame.

INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS

Installation Diagram Of Indoor And Outdoor Units

Optional Installation Parts
Part code Parts name Q’ty
A Refrigerant piping

Liquid side : Ø6.35 mm Gas side
: Ø9.52 mm
(RAS-B10N4KVRG-E1) (RAS-B13N4KVRG-E)
: Ø12.70 mm
(RAS-B16N4KVRG-E)| One each
B| Pipe insulating material (polyethylene foam, 6 mm thick)| 1
C| Putty, PVC tapes| One each

Fixing bolt arrangement of outdoor unit

  • Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
  • Use Ø8 mm or Ø10 mm anchor bolts and nuts.
  • If it is necessary to drain the defrost water, attach drain nipple 14 and cap water proof 15 to the bottom plate of the outdoor unit before installing it.
    Fixing bolt arrangement of outdoor unit
    When using a multi-system outdoor unit, refer to the installation manual provided with the model concerned.

INDOOR UNIT

Installation Place
  • A place which provides the spaces around the indoor unit as shown in the diagram
  • A place where there are no obstacles near the air inlet and outlet
  • A place which allows easy installation of the piping to the outdoor unit
  • A place which allows the front panel to be opened
  • The indoor unit shall be installed at least 2.5 m height. Also, it must be avoided to put anything on the top of the indoor unit.

CAUTION

  • Direct sunlight to the indoor unit’s wireless receiver should be avoided.
  • The microprocessor in the indoor unit should not be too close to RF noise sources.
    (For details, see the owner’s manual.)

Remote controller

  • A place where there are no obstacles such as a curtain that may block the signal from the indoor unit
  • Do not install the remote controller in a place exposed to direct sunlight or close to a heating source such as a stove.
  • Keep the remote controller at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
  • The location of the remote controller should be determined as shown below.
    Remote controller
Cutting a Hole and Mounting Installation Plate

Cutting a hole

When installing the refrigerant pipes from the rear
Cutting a hole

  1. After determining the pipe hole position on the mounting plate (→ ), drill the pipe hole (Ø65 mm) at a slight downward slant to the outdoor side.

NOTE

  • When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.

Mounting the installation plate

Mounting the installation plate

Space allows under the indoor unit

  • Space allows for moving range of the air inlet grille and horizontal louver in operation above curtain rails, window cornice or other objects.
    Space allows under the indoor unit

CAUTION

  • If have curtain rails, window cornice or other objects, allow space from the indoor unit should be 45 mm or more.
  • If allow space is less than 45 mm, this can affect the opening and closing of the air inlet grille and the horizontal louver.
  • However, there should be no objects in the air outlet position.
    It will block the air flow direction and drop performance.

When the installation plate is directly mounted on the wall

  1. Securely fi t the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
  2. To mount the installation plate on a concrete wall with anchor bolts, use the anchor bolt holes as illustrated in the below figure.
  3. Install the installation plate horizontally in the wall.

CAUTION

When installing the installation plate with a mounting screw, do not use the anchor bolt holes. Otherwise, the unit may fall down and result in personal injury and property damage.
Indoor Unit

CAUTION

Failure to firmly install the unit may result in personal injury and property damage if the unit falls.

  • In case of block, brick, concrete or similar type walls, make 5 mm dia. holes in the wall.
  • Insert clip anchors for appropriate mounting screws 6.

NOTE

  • Secure four corners and lower parts of the installation plate with 4 to 6 mounting screws to install it.
Piping and Drain Hose Installation

Piping and drain hose forming

  • Since dewing results in a machine trouble, make sure to insulate both connecting pipes. (Use polyethylene foam as insulating material.)

  • The connection of pipes can be installed in the following directions.
    Piping and drain hose forming

  • Rear right

  • Rear left

  • Bottom right

  • Bottom left

  1. Die-cutting Front panel slit
    • Cut out the slit on the bottom left or bottom right side of the Front panel for the bottom left or bottom right connection with a coping saw.
  2. Changing drain hose
    • The factory default of the drain hose is installed on the right side.
    • For bottom-leftward connection and rear leftward connection’s piping, it is necessary to change the drain hose and drain cap.

How to cutting the Front panel

  • To connect piping to the bottom side, the Front panel must be cut off.

  • The front panel can be removed by removing 2 screws securing then secure remove the front panel from the main body.
    ❅ Be careful of air inlet grill fall down that may cause of injure or part damage.How to cutting the Front panel

  • The marking for cutting are indicated on the inside of the Front panel in the following positions.
    How to cutting the Front panel

  • Cut off the pipe exist from inside of Front panel using a coping saw or an equivalent tool.

  • The plastic burrs from the cutting process should be removed with a half round fi le or an equivalent tool.
    How to cutting the Front panel

CAUTION
When cutting the Front panel, be careful of cutting tools and any sharp edges of plastic. It can cause injuries.

How to remove the drain hose

  • Removed fixing screw of LED set then pull out it from the main body.

  • Removed 2 screws to fi x drain pan then secure remove the drain pan from the main body.
    How to remove the drain hose

  • The drain hose can be removed by removing the screw securing the drain hose then secure rotate steel plate of drain hose to out of the Drain pan and pulling out the drain hose.
    How to remove the drain hose

How to fi x the drain hose

  • To install the drain hose, insert the drain hose firmly until the connection part contacts with heat insulator, secure push steel plate of drain hose to predetermined position of Drain pan then fi x it by original screw.
    How to remove the drain hose

CAUTION
When removing or install the drain hose, be careful of any sharp edges of steel plate. The edges can cause injuries.

How to remove the drain cap

  • Clip the drain cap by needle-nose pliers and pull out.
    How to remove the drain cap

How to fix the drain cap

  • Insert hexagonal wrench (dia. 4 mm) in a center head.
    How to fix the drain cap

  • Firmly insert the drain cap.
    How to fix the drain cap

CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak

Left-hand connection with piping

  • Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall.
    When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.

Bend the connecting pipe within a radius of 30 mm.

To connect the pipe after installation of the unit (figure)
Bend the connecting pipe within a radius of 30 mm

NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipes to the auxiliary pipes and wrap the facing tape around them.

CAUTION

  • Bind the auxiliary pipes (two), power supply and connecting cable with facing tape tightly.
    Bend the connecting pipe within a radius of 30 mm

  • Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.

  • Carefully connect the auxiliary pipes and connecting pipes to one another and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint; moreover, seal the joint with the vinyl tape, etc.

  • Since dewing results in a machine trouble, make sure to insulate both connecting pipes. (Use polyethylene foam as insulating material.)

  • When bending a pipe, carefully do it, not to crush it.

Indoor Unit Fixing
  1. Pass the pipe through the hole in the wall and hook the indoor unit on the installation plate at the upper hook.

  2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.

  3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.

    • For detaching the indoor unit from the installation plate, pull the indoor unit toward you while pushing its bottom up at the specified parts.
      Indoor Unit Fixing

CAUTION

MOUNTING INDOOR UNIT TO THE INSTALLATION PLATE

  • The lower part of indoor unit may À oat, due to the condition of piping and installer cannot ¿ x it to the installation plate. In that case, use the screws provided to ¿ x the indoor unit with the installation plate.
  • Especially when the pipes are pulled out to the left side, the indoor unit must be screwed to the installation plate.
    Indoor Unit Fixing

DIRECTLY MOUNTING INDOOR UNIT TO THE WALL

  • In case left side or right of indoor unit may À oat, the provided screws should be used to ¿ x the indoor unit directly to the wall at the predetermined position.
  • In the case of block, brick, concrete or similar type wall, determining the mount screw position on the wall can be used symbol (►) on the main body of indoor unit for drill hole to insert clip anchors for appropriate mounting screw.
    Directly Mounting Indoor Unit To The Wall

Drainage

  1. Run the drain hose sloped downwards.
    NOTE

    • The hole should be made at ah slight downward slant on the outdoor side.
      Drainage
  2. Put water in the drain pan and make sure that the water is drained out of doors.

  3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe.
    Drainage

CAUTION

Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.

This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts at a height above the drain guide.

OUTDOOR UNIT

Installation Place
  • A place which provides the spaces around the outdoor unit as shown in the diagram
  • A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration
  • A place where the operation noise and discharged air do not disturb your neighbors
  • A place which is not exposed to a strong wind
  • A place free of a leakage of combustible gases
  • A place which does not block a passage
  • When the outdoor unit is to be installed in an elevated position, be sure to secure its feet.
  • The allowable length of the connecting pipe.
    Model| RAS-10J2AVSG-E1| RAS-13J2AVSG-E1| RAS-16J2AVSG-E1
    ---|---|---|---
    Charge less| up to 15 m| up to 15 m| up to 15 m
    Maximum length| 20 m| 20 m| 20 m
    Additional refrigerant charging| 16 – 20 m (20 g / 1 m)| 16 – 20 m (20 g / 1 m)| 16 – 20 m (20 g / 1 m)
    Maximum refrigerant charging| 0.65 kg| 0.90 kg| 0.90 kg
  • The allowable height of outdoor unit installation site.
    Model| RAS-10J2AVSG-E1| RAS-13J2AVSG-E1| RAS-16J2AVSG-E1
    ---|---|---|---
    Maximum height| 12 m| 12 m| 12 m
  • A place where the drain water does not raise any problems

Precautions for adding refrigerant

Use a scale having a precision with at least 10 g per index line when adding the refrigerant.
Do not use a bathroom scale or similar instrument.

CAUTION
When the outdoor unit is installed in a place where the drain water might cause any problems, Seal the water leakage point tightly using a silicone adhesive or caulking compound.

Precautions about Installation in Regions with Snowfall and Cold Temperatures

  • Do not use the supplied drain nipple for draining water. Drain the water from all the drain holes directly.
  • To protect the outdoor unit from snow accumulation, install a holding frame, and attach a snow protection hood and plate.
  • Do not use a double-stacked design.
    Precautions about Installation in Regions with Snowfall and Cold
Temperatures

CAUTION

  1. Install the outdoor unit without anything blocking the air discharging.

  2. When the outdoor unit is installed in a place always exposed to strong wind like a coast or on a high story of a building, secure the normal fan operation using a duct or a windshield.

  3. In particularly windy areas, install the unit such as to avoid admission of wind.

  4. Installation in the following places may result in trouble.
    Do not install the unit in such places.

    • A place full of machine oil
    • A saline-place such as the coast
    • A place full of sulfide gas
    • A place where high-frequency waves are likely to be generated as from audio equipment, welders, and medical equipment
Draining the Water
  • Holes are provided on the base plate of the outdoor unit to ensure that the defrost water produced during heating operations is drained off efficiently.
    If a centralized drain is required when installing the unit on a balcony or wall, follow the steps below to drain off the water.

    1. Proceed with water-proofing by installing the water-proof rubber caps in the 2 elongated holes on the base plate of the outdoor unit.
      [How to install the water-proof rubber caps] 1) Place four fingers into each cap, and insert the caps into the water drain holes by pushing them into place from the underside of the base plate.
  1. Press down on the outer circumferences of the caps to ensure that they have been inserted tightly. (Water leaks may result if the caps have not been inserted properly, if their outer circumferences lift up or the caps catch on or wedge against something.)
    Draining the Water

    1. Install the drain nipple and a commercially available drain hose (with 16 mm inside diameter), and drain off the water. (For the position where the drain nipple is installed, refer to the installation diagram of the indoor and outdoor units.)
    • Check that the outdoor unit is horizontal, and route the drain hose at a downward sloped angle while ensuring that it is connected tautly.
      Draining the Water

Do not use ordinary garden hose, but one can flatten and prevent water from draining.

Refrigerant Piping Connection

Flaring

  1. Cut the pipe with a pipe cutter.
    Flaring

  2. Insert a flare nut into the pipe and flare the pipe.

    • Projection margin in flaring : A (Unit : mm)

RIDGID (clutch type)

Outer dia. of copper pipe Tool used Conventional tool used
Ø6.35 0 to 0.5 1.0 to 1.5
Ø9.52 0 to 0.5 1.0 to 1.5
Ø12.70 0 to 0.5 1.0 to 1.5
Pipes thickness 0.8 mm or more

IMPERIAL (wing nut type)

Outer dia. of copper pipe Tool used
Ø6.35 1.5 to 2.0
Ø9.52 1.5 to 2.0
Ø12.70 2.0 to 2.5
Pipes thickness 0.8 mm or more

CAUTION

  • Do not scratch the inner surface of the flared part when removing burrs.
  • Flare processing under the condition of scratches on the inner surface of flare processing part will cause refrigerant gas leak.

Tightening connection

Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
Tightening connection

CAUTION

Do not apply excess torque. Otherwise, the nut may crack depending on the conditions.

Outer dia. of copper pipe Tightening torque
Ø6.35 mm 14 to 18 (1.4 to 1.8 kgf·m)
Ø9.52 mm 30 to 42 (3.0 to 4.2 kgf·m)
Ø12.70 mm 50 to 62 (5.0 to 6.2 kgf·m)
  • Tightening torque of flare pipe connections
    The operating pressure of R32 is higher than that of R22 (approx.
    1.6 times). It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but also damage to the refrigeration cycle.

Evacuating

After the piping has been connected to the indoor unit, you can perform the air purge together at once.

AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit.
For details, see the manual of the vacuum pump.

Using a vacuum pump

Be sure to use a vacuum pump with counter-À ow prevention function so that inside oil of the pump does not À ow backward into pipes of the air conditioner when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R32, refrigeration cycle trouble may result.)

  1. Connect the charge hose from the manifold valve to the service port of the packed valve at gas side.
  2. Connect the charge hose to the port of the vacuum pump.
  3. Open fully the low pressure side handle of the gauge manifold valve.
  4. Operate the vacuum pump to start evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) (assuming a pump capacity of 27 liters per minute) Then confirm that the compound pressure gauge reading is –101 kPa (–76 cmHg).
  5. Close the low pressure side valve handle of the gauge manifold valve.
  6. Open fully the valve stem of the packed valves (both gas and liquid sides).
  7. Remove the charging hose from the service port.
  8. Securely tighten the caps on the packed valves.
    Using a vacuum pump

CAUTION

  • KEEP IMPORTANT 7 POINTS FOR PIPING WORK.
    1. Take away dust and moisture (inside of the connecting pipes).
    2. Tighten the connections (between pipes and unit).
    3. Evacuate the air in the connecting pipes using a VACUUM PUMP.
    4. Check gas leak (connected points).
    5. Be sure to fully open the packed valves before operation.
    6. Reusable mechanical connectors and À arid joints are not allowed indoors. When mechanical connectors are reused indoors, sealing parts shall be renewed. When À arid joints are reused indoors, the À are part shall be refabricated.
    7. Don’t operate air conditioner in case no refrigerant in the system.

Packed valve handling precautions

  • Open the valve stem all the way out, but do not try to open it beyond the stopper.
Pipe size of Packed Valve Size of Hexagon wrench
12.70 mm and smallers A = 4 mm
15.88 mm A = 5 mm

Pump down process

  1. Turn off the Air Conditioner system.

  2. Connect the charge hose from the manifold valve to the service port of the packed valve at gas side.

  3. Turn on the Air Conditioner system in cooling operation more than 10 minutes.

  4. Check the operating pressure of the system should be normal value.
    (Ref. with product specification)

  5. Release the valve rod cap of both service valves.

  6. Use the Hexagon wrench to turning the valve rod of Liquid side fully close. (*Make sure no entering air into the system)

  7. Continue operate Air Conditioner system until the gauge of manifold dropped into the range of 0.5 – 0 kgf/cm2.

  8. Use the Hexagon wrench to turning the valve rod of Gas side fully close.
    And turn off the Air Conditioner system immediately thereafter.

  9. Remove the gauge manifold from the service port of the packed valve.

  10. Securely tighten the valve rod cap to the both service valves.

CAUTION
Should be check the compressor operating condition while pumping down process. It must not any abnormal sound, more vibration.
It is abnormal condition appears and must turn off the Air Conditioner immediately.

  • Securely tighten the valve cap with torque in the following table:
Cap Cap Size (H) Torque
Valve Rod Cap H17 – H19 14~18 N·m (1.4 to 1.8 kgf·m)
H22 – H30 33~42 N·m (3.3 to 4.2 kgf·m)
Service Port Cap H14 8~12 N·m (0.8 to 1.2 kgf·m)
H17 14~18 N·m (1.4 to 1.8 kgf·m)

Pump down process

ELECTRICAL WORKS

Model RAS-B10N4KVRG-E1 RAS-B13N4KVRG-E RAS-B16N4KVRG-E
Power source 50Hz, 220 – 240V Single phase
Maximum running current 6.75A 7.60A 9.50A
Circuit breaker rating 15A 15A 15A
Power supply cable H07RN-F or 60245 IEC66 (1.25 mm2 or more) H07RN-F or

60245 IEC66 (1.5 mm2 or more)
Connecting cable

Indoor unit

Wiring of the connecting cable can be carried out without removing the front panel.

  1. Remove the air inlet grille.
    Open the air inlet grille upward and pull it toward you.

  2. Remove the terminal cover and cord clamp.

  3. Insert the connecting cable (according to the local cords) into the pipe hole on the wall.

  4. Take out the connecting cable through the cable slot on the rear panel so that it protrudes about 20 cm from the front.

  5. Insert the connecting cable fully into the terminal block and secure it tightly with screws.

  6. Tightening torque : 1.2 N·m (0.12 kgf·m)

  7. Secure the connecting cable with the cord clamp.

  8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor
    Electrical Works

How to install the air inlet grille on the indoor unit

  • When attaching the air inlet grille, the contrary of the removed operation is performed.
    How to install the air inlet grille on the indoor unit

Outdoor unit

  1. Remove the valve cover, the electric parts cover and the cord clamp from the outdoor unit.

  2. Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of indoor and outdoor unit.

  3. Insert the power cord and the connecting cable carefully into the terminal block and secure it tightly with screws.

  4. Use vinyl tape, etc. to insulate the cords which are not going to be used.
    Locate them so that they do not touch any electrical or metal parts.

  5. Secure the power cord and the connecting cable with the cord clamp.

  6. Attach the electric parts cover and the valve cover on the outdoor unit.
    Outdoor unit

In Case of Indoor Unit Connect With 1:1 Outdoor Unit

The power supply can be selected to connect to indoor unit or outdoor unit. Choose proper way and connect the power supply and connecting cable by follow the instruction as following.

Power Supply Input at Outdoor Unit Terminal Block (Recommend)

Indoor Unit

Connecting cable Connecting cable connect to 123
Indoor Unit Outdoor Unit

Stripping length of the connecting cable

Outdoor Unit

Outdoor Unit

Power Supply Input at Indoor Unit Terminal Block (Optional)

Indoor Unit

Power supply cable Power supply cable connect to LN
Indoor Unit

Stripping length of the power supply cable

Connecting cable Connecting cable connect to 123

Indoor Unit

Stripping length of the connecting cable

Outdoor Unit

Outdoor Unit

Power supply input Wiring Diagram for 1:1 Outdoor Unit

Power input at Outdoor Terminal Block (Recommend)

Power supply input Wiring Diagram for 1:1 Outdoor Unit

Power input at Indoor Terminal Block (Optional)

Power supply input Wiring Diagram for 1:1 Outdoor Unit

CAUTION

  1. The power supply must be same as the rated of air conditioner.
  2. Prepare the power source for exclusive use with air conditioner.
  3. Circuit breaker must be used for the power supply line of this air conditioner.
  4. Be sure to comply power supply and connecting cable for size and wiring method.
  5. Every wire must be connected firmly.
  6. Perform wiring works so as to allow a general wiring capacity.
  7. Wrong wiring connection may cause some electrical part burn out.
  8. Incorrect or incomplete wiring is carried out, it will cause an ignition or smoke.
  9. This product can be connected to main power supply.
    Connection to fixed wiring : A switch which disconnects all poles and has a contact separation at least 3 mm must be incorporated in the fixed wiring.

In Case of Indoor Unit Connect With Inverter Multi System (IMS)

Power Supply Input at Outdoor Unit Terminal Block

Indoor Unit

Connecting cable Connecting cable connect to 123

In Case of Indoor Unit Connect With Inverter Multi System
\(IMS\)

Stripping length of the Connecting cable

Stripping length of the Connecting cable

Outdoor Unit

Outdoor Unit

Power supply input Wiring Diagram for Inverter Multi System (IMS)

Power input at Outdoor Terminal Block

Power supply input Wiring Diagram for Inverter Multi System
\(IMS\)

CAUTION

  1. The power supply must be same as the rated of air conditioner.
  2. Prepare the power source for exclusive use with air conditioner.
  3. Circuit breaker must be used for the power supply line of this air conditioner.
  4. Be sure to comply power supply and connecting cable for size and wiring method.
  5. Every wire must be connected firmly.
  6. Perform wiring works so as to allow a general wiring capacity.
  7. Wrong wiring connection may cause some electrical part burn out.
  8. Incorrect or incomplete wiring is carried out, it will cause an ignition or smoke.
  9. This product can be connected to main power supply.
    Connection to fixed wiring : A switch which disconnects all poles and has a contact separation at least 3 mm must be incorporated in the fixed wiring.

OTHERS

Gas Leak Test

  • Check the flare nut connections for the gas leak with a gas leak detector or soap water.
    Gas Leak Test

Remote Control A-B Selection

  • When two indoor units are installed in the same room or adjacent two rooms, if operating a unit, two units may receive the remote control signal simultaneously and operate. In this case, the operation can be preserved by setting either one remote control to B setting. (Both are set to A setting in factory shipment.)
  • The remote control signal is not received when the settings of indoor unit and remote control are different.
  • There is no relation between A setting/B setting and A room/B room when connecting the piping and cables.

To separate using of remote control for each indoor unit in case of 2 air conditioner are installed near.

Remote Control B Setup.

  1. Press [RESET] button on the indoor unit to turn the air conditioner ON.

  2. Point the remote control at the indoor unit.

  3. Push and hold [CHECK] button on back side of Remote Control. “00” will be shown on the display (Picture 1).
    Remote Control B Setup.

  4. Press [MODE] during pushing [CHECK]. “B” will show on the display and “00” will disappear and the air conditioner will turn OFF. The Remote Control B is memorized (Picture 2).

Note :

  1. Repeat above step to reset Remote Control to be A.
  2. Remote Control A have not “A” display.
  3. Default setting of Remote Control from factory is A.

Test Operation

To switch the TEST RUN (COOL) mode, press [RESET] button for 10 seconds. (The beeper will make a short beep.)
Test Operation

Auto Restart Function Setting

This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.

Information

The product was shipped with Auto Restart function in the OFF position. Turn it ON as required.

How to turn ON the Auto Restart Function

  • Press and hold the [OPERATION] button on the indoor unit for 3 seconds (3 Beep sound and OPERATION lamp blink 5 time/sec for 5 seconds).

How to turn OFF the Auto Restart Function

  • Press and hold the [OPERATION] button on the indoor unit for 3 seconds (3 Beep sound but OPERATION lamp does not blink).

NOTE

  • In case of ON timer or OFF timer are set, AUTO RESTART OPERATION does not activate.

Decorative Fabric Installation

The decorative fabric for cover on the air inlet grille of indoor unit was put in the accessories. User can use it as required.
The method of installation is as follows.

  1. Remove the air inlet grille.
    Open the air inlet grille upward and pull it toward you.
    As shown on figure as below.
    Decorative Fabric Installation

  2. Prepare the fabric that you choose for install.

  3. Insert the fabric into the left and right side of the air inlet grille and adjust corner position of decorative fabric is smooth.
    Attach the hook and loop of velcro tape fully together.
    As shown on figure as below.
    Decorative Fabric Installation

  4. . Insert the fabric into the top and bottom side of the air inlet grille.
    Attach the hook and loop of velcro tape fully together.
    As shown on figure as below.
    Decorative Fabric Installation

  5. Reassembly the air inlet grille by reverse process of 1.

NOTE

  • The tightness of the fabric depends on attaching the hook and loop of velcro around the air inlet grille, take appropriate action.

CAUTION

  • If clean decorative fabric by washing, it may affect to appearance and fitting of the decorative fabric.
  • Recommend to use vacuum cleaner to removing the dusts from decorative fabric

APPENDIX

Work instructions

The existing R22 and R410A piping can be reused for inverter R32 product installations.

WARNING

Confirming the existence of scratches or dents on the existing pipes and confirming the reliability of the pipe strength are conventionally referred to the local site.
If the specified conditions can be cleared, it is possible to update existing R22 and R410A pipes to those for R32 models.

Basic conditions needed to reuse existing

pipes

Check and observe the presence of three conditions in the refrigerant piping works.

  1. Dry (There is no moisture inside of the pipes.)
  2. Clean (There is no dust inside of the pipes.)
  3. Tight (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should not be reused as they are. Clean the existing pipes or exchange them with new pipes.

  1. When a scratch or dent is heavy, be sure to use new pipes for the refrigerant piping works.

  2. When the existing pipe thickness is thinner than the specified “Pipe diameter and thickness,” be sure to use new pipes for the refrigerant piping works.
    The operating pressure of R32 or R410A is high (1.6 times that of R22). If there is a scratch or dent on the pipe or a thinner pipe is used, the pressure strength may be inadequate, which may cause the pipe to break in the worst case.
    ** * Pipe diameter and thickness (mm)
    **
    Pipe outer diameter| Ø6.4| Ø9.5| Ø12.7
    ---|---|---|---
    Thickness| R32, R410A| 0.8| 0.8| 0.8
    R22

  3. When the outdoor unit was left with the pipes disconnected, or the gas leaked from the pipes and the pipes were not repaired and refilled.

    • There is the possibility of rain water or air, including moisture, entering the pipe.
  4. When refrigerant cannot be recovered using a refrigerant recovery unit.

    • There is the possibility that a large quantity of dirty oil or moisture remains inside the pipes.
  5. When a commercially available dryer is attached to the existing pipes.
    There is the possibility that copper green rust has been generated.

  6. When the existing air conditioner is removed after refrigerant has been recovered.
    Check if the oil is judged to be clearly different from normal oil.

    • The refrigerator oil is copper rust green in color:

    • There is the possibility that moisture has mixed with the oil and rust has been generated inside the pipe.
      There is discolored oil, a large quantity of residue, or a bad smell.

    • A large quantity of shiny metal dust or other wear residue can be seen in the refrigerant oil.

  7. When the air conditioner has a history of the compressor failing and being replaced.

    • When discolored oil, a large quantity of residue, shiny metal dust, or other wear residue or mixture of foreign matter is observed, trouble will occur.
  8. When temporary installation and removal of the air conditioner are repeated such as when leased etc.

  9. If the type of refrigerator oil of the existing air conditioner is other than the following oil (Mineral oil), Sunnis, Freon-S, MS (Synthetic oil), alkyl benzene (HAB, Barrel-freeze), ester series, PVE only of ether series.

    • The winding-insulation of the compressor may deteriorate.

NOTE

The above descriptions are results have been confirmed by our company and represent our views on our air conditioners, but do not guarantee the use of the existing pipes of air conditioners that have adopted R32 or R410A in other companies.

Curing of pipes

When removing and opening the indoor or outdoor unit for a long time, cure the pipes as follows:

  • Otherwise rust may be generated when moisture or foreign matter due to condensation enters the pipes.
  • The rust cannot be removed by cleaning, and new pipes are necessary.
    Placement location| Term| Curing manner
    ---|---|---
    Outdoors| 1 month or more| Pinching
    Less than 1 month| Pinching or taping
    Indoors| Every time

APPENDIX

CUSTOMER SUPPORT

Scan QR CODE to access installation and owner’s manual on website. https://www.toshiba-carrier.co.th/manuals/default.aspx
Manual are available in AR/BG/CZ/DA/DE/EL/EN/ES/ET/FI/FR/ HR/HU/IT/LT/LV/NL/NO/PL/PT/RO/RU/SK/SL/SV.

QR Code

Indoor unit
RAS-B10N4KVRG-E1
RAS-B13N4KVRG-E
RAS-B16N4KVRG-E
Outdoor unit
RAS-10J2AVSG-E1
RAS-13J2AVSG-E1
RAS-16J2AVSG-E1Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals