TOSHIBA MMY-MUP1201FT9P-UL VRF Outdoor Unit Instruction Manual

May 15, 2024
Toshiba

TOSHIBA - logoVRF Outdoor Unit
MMY-MUP1201FT9P-UL – Heat Recovery

MMY-MUP1201FT9P-UL VRF Outdoor Unit

Submittal Data

Job Name __
Location
Tag ____

Heat Recovery Features

  • Modules and pairings available from 6 to 30 tons

  • Modules have inverter-driven scroll compressors

  • Direct-drive, inverter-driven outdoor motor

  • Up to 3937 ft actual total system piping (liquid line)

  • 656 ft (200 m) actual piping length from outdoor unit to furthest fan coil

  • Operating temperature range Cooling (db): -10° to 125°F (–15° to 52°C)
    Heating (wb): –22° to 60°F (–25° to 18°C)

  • Protection: high pressure sensor and switch, low pressure sensor and switch, process controller board fuse, inverter overload protection

  • 7-year compressor limited warranty

  • 5-year parts limited warranty

Header Unit Model MMY-MUP1201FT9P-UL

PERFORMANCE
Nominal Cooling Capacity| Btu/h| 120,000
Nominal Heating Capacity| Btu/h| 135,000
Maximum Number of Indoor Units| | 21
SIMULTANEOUS COOLING AND HEATING EFFICIENCYt
SCHE, Ducted FCUs| | 31.0
SCHE, Ductless FCUs| | 35.0
COOLING EFFICIENCYt
EER/IEER, Ducted FCUs| Btu/Wh| 11.6/22.0
Power Consumption, Ducted FCUs| kW| 8.60
EER/IEER, Ductless FCUs| Btu/Wh| 12.1/24.6
Power Consumption, Ductless FCUs| kW| 9.
HEATING EFFICIENCYt
COP at 47°F, Ducted FCUs| | 4.
Power Consumption, Ducted FCUs| kW| 9.
COP at 47°F, Ductless FCUs| | 4.20
Power Consumption, Ductless FCUs| kW| 9.
Fan Type (Qty)| | Propeller (1)
Airflow, Standard Range| CFM| 7416
Sound Pressure| dBA| 60.0
External Static Pressure*| in. wg| 0.321
ELECTRICAL
Power Supply| V/Ph/Hz| 208-230/3/60
Minimum Circuit Amps (MCA)| A| 37.
Maximum Overcurrent Protection (MOCP)| A| 45
COMPRESSORS
Type (Number)| Hermetic Twin| H
Rotary (1)
FAN MOTOR
Motor Output| kW| 0.33 x 2
PHYSICAL DATA
Pipe Connection Size – Liquid (High Pressure)| in.| 1/2 (Brazed)
Pipe Connection Size – Gas (Low Pressure)| in.| 1-1/8 (Brazed)
Discharge – Gas (High/Low Pressure)| | 3/4 (Brazed)
Refrigerant| R-410A
Factory Chargett| lb| 20.
Unit Width| in.| 51-1/2
Unit Height| in.| 66-1/2
Unit Depth| in.| 31-1/4
Net Weight| lb| 675

LEGEND
db — Dry Bulb
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
FCU — Fan Coil Unit
IEER — Integrated Energy Efficiency Ratio
wb— Wet Bulb
SCHE — Simultaneous Cooling and Heating Efficiency

†Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230 Standard.
Cooling: Indoor 80°F (27°C) db/67°F (20°C) wb; Outdoor 95°F (35°C) db
Heating: Indoor 70°F (21°C) db; Outdoor 47°F (8°C) db/43°F (6°C) wb
*Requires setting by menu functions.
††Additional charge required.
NOTE: Unit cabinet and coil slab shall be capable of withstanding 500-hour salt spray test.

DIMENSIONAL DRAWING

OUTDOOR UNIT MMY-MUP1201FT9P-UL

TOSHIBA MMY-MUP1201FT9P-UL VRF Outdoor Unit -
Dimension

www.ahridirectory.org
© 2023 Carrier. All rights reserved.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals