TOSHIBA MMY-MUP1201FT9P-UL VRF Outdoor Unit Instruction Manual
- May 15, 2024
- Toshiba
Table of Contents
VRF Outdoor Unit
MMY-MUP1201FT9P-UL – Heat Recovery
MMY-MUP1201FT9P-UL VRF Outdoor Unit
Submittal Data
Job Name __
Location
Tag ____
Heat Recovery Features
-
Modules and pairings available from 6 to 30 tons
-
Modules have inverter-driven scroll compressors
-
Direct-drive, inverter-driven outdoor motor
-
Up to 3937 ft actual total system piping (liquid line)
-
656 ft (200 m) actual piping length from outdoor unit to furthest fan coil
-
Operating temperature range Cooling (db): -10° to 125°F (–15° to 52°C)
Heating (wb): –22° to 60°F (–25° to 18°C) -
Protection: high pressure sensor and switch, low pressure sensor and switch, process controller board fuse, inverter overload protection
-
7-year compressor limited warranty
-
5-year parts limited warranty
Header Unit Model | MMY-MUP1201FT9P-UL |
---|
PERFORMANCE
Nominal Cooling Capacity| Btu/h| 120,000
Nominal Heating Capacity| Btu/h| 135,000
Maximum Number of Indoor Units| | 21
SIMULTANEOUS COOLING AND HEATING EFFICIENCYt
SCHE, Ducted FCUs| | 31.0
SCHE, Ductless FCUs| | 35.0
COOLING EFFICIENCYt
EER/IEER, Ducted FCUs| Btu/Wh| 11.6/22.0
Power Consumption, Ducted FCUs| kW| 8.60
EER/IEER, Ductless FCUs| Btu/Wh| 12.1/24.6
Power Consumption, Ductless FCUs| kW| 9.
HEATING EFFICIENCYt
COP at 47°F, Ducted FCUs| | 4.
Power Consumption, Ducted FCUs| kW| 9.
COP at 47°F, Ductless FCUs| | 4.20
Power Consumption, Ductless FCUs| kW| 9.
Fan Type (Qty)| | Propeller (1)
Airflow, Standard Range| CFM| 7416
Sound Pressure| dBA| 60.0
External Static Pressure*| in. wg| 0.321
ELECTRICAL
Power Supply| V/Ph/Hz| 208-230/3/60
Minimum Circuit Amps (MCA)| A| 37.
Maximum Overcurrent Protection (MOCP)| A| 45
COMPRESSORS
Type (Number)| Hermetic Twin| H
Rotary (1)
FAN MOTOR
Motor Output| kW| 0.33 x 2
PHYSICAL DATA
Pipe Connection Size – Liquid (High Pressure)| in.| 1/2 (Brazed)
Pipe Connection Size – Gas (Low Pressure)| in.| 1-1/8 (Brazed)
Discharge – Gas (High/Low Pressure)| | 3/4 (Brazed)
Refrigerant| R-410A
Factory Chargett| lb| 20.
Unit Width| in.| 51-1/2
Unit Height| in.| 66-1/2
Unit Depth| in.| 31-1/4
Net Weight| lb| 675
LEGEND
db — Dry Bulb
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
FCU — Fan Coil Unit
IEER — Integrated Energy Efficiency Ratio
wb— Wet Bulb
SCHE — Simultaneous Cooling and Heating Efficiency
†Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230
Standard.
Cooling: Indoor 80°F (27°C) db/67°F (20°C) wb; Outdoor 95°F (35°C) db
Heating: Indoor 70°F (21°C) db; Outdoor 47°F (8°C) db/43°F (6°C) wb
*Requires setting by menu functions.
††Additional charge required.
NOTE: Unit cabinet and coil slab shall be capable of withstanding 500-hour
salt spray test.
DIMENSIONAL DRAWING
OUTDOOR UNIT MMY-MUP1201FT9P-UL
www.ahridirectory.org
© 2023 Carrier. All rights reserved.
Manufacturer reserves the right to discontinue, or change at any time,
specifications or designs without notice and without incurring obligations.