TOSHIBA MUP1201FT6P-UL VRF Outdoor Unit User Guide
- May 15, 2024
- Toshiba
Table of Contents
TOSHIBA MUP1201FT6P-UL VRF Outdoor Unit
Heat Recovery Features
-
Modules and pairings available from 6 to 30 tons
-
Modules have inverter-driven scroll compressors
-
Direct-drive, inverter-driven outdoor motor
-
Up to 3937 ft actual total system piping (liquid line)
-
656 ft (200 m) actual piping length from outdoor unit to furthest fan coil
-
Operating temperature range
Cooling (db): -10º to 125 ºF (–15º to 52ºC)
Heating (wb): –22º to 60ºF (–25º to 18ºC) -
Protection: high pressure sensor and switch, low pressure sensor and switch, process controller board fuse, inverter overload protection
-
7-year compressor limited warranty
-
5-year parts limited warranty
Header Unit Model: MMY-MUP1201FT6P-UL
PERFORMANCE
Nominal Cooling Capacity | Btu/h | 120,000 |
---|---|---|
Nominal Heating Capacity | Btu/h | 135,000 |
Maximum Number of Indoor Units | 21 |
SIMULTANEOUS COOLING AND HEATING EFFICIENCY†
SCHE, Ducted FCUs | 31.0 | |
---|---|---|
SCHE, Ductless FCUs | 35.0 |
COOLING EFFICIENCY†
EER/IEER, Ducted FCUs | Btu/Wh | 11.6/22.0 |
---|---|---|
Power Consumption, Ducted FCUs | kW | 8.60 |
EER/IEER, Ductless FCUs | Btu/Wh | 12.1/24.6 |
Power Consumption, Ductless FCUs | kW | 9.26 |
HEATING EFFICIENCY†
COP at 47°F, Ducted FCUs | 3.84 | |
---|---|---|
Power Consumption, Ducted FCUs | kW | 8.53 |
COP at 47°F, Ductless FCUs | 4.20 | |
Power Consumption, Ductless FCUs | kW | 8.76 |
Fan Type (Qty) | Propeller (1) | |
Airflow, Standard Range | CFM | 7416 |
Sound Pressure | dBA | 60.0 |
External Static Pressure* | in. wg | 0.321 |
LEGEND
db — Dry Bulb
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
FCU — Fan Coil Unit
IEER — Integrated Energy Efficiency Ratio
wb — Wet Bulb
SCHE — Simultaneous Cooling and Heating Efficiency
ELECTRICAL
Power Supply | V/Ph/Hz | 460/3/60 |
---|---|---|
Minimum Circuit Amps (MCA) | A | 21.3 |
Maximum Overcurrent Protection
(MOCP)
| A| 25
COMPRESSORS
Type (Number) | Hermetic Twin Rotary (1) |
---|
FAN MOTOR
Motor Output | kW | 0.33 x 2 |
---|
PHYSICAL DATA
Pipe Connection Size – Liquid (High Pressure) | in. | 1/2 (Brazed) |
---|---|---|
Pipe Connection Size – Gas (Low Pressure) | in. | 1-1/8 (Brazed) |
Discharge – Gas (High/Low Pressure) | 3/4 (Brazed) | |
Refrigerant | R-410A | |
Factory Charge†† | lb | 19.8 |
Unit Width | in. | 51-1/2 |
Unit Height | in. | 66-1/2 |
Unit Depth | in. | 31-1/4 |
Net Weight | lb | 686 |
†Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230
Standard.
Cooling: Indoor 80°F (27°C) db/67°F (20°C) wb; Outdoor 95°F (35°C) db
Heating: Indoor 70°F (21°C) db; Outdoor 47°F (8°C) db/43°F (6°C) wb
*Requires setting by menu functions.
††Additional charge required.
NOTE: Unit cabinet and coil slab shall be capable of withstanding
500-hour salt spray test.
DIMENSIONAL DRAWING OUTDOOR UNIT MMY-MUP1201FT6P-UL
Note
- If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 78. 7in [2000mm] apart from the obstacle.
- Draw out the pipe procured locally to the front of the outdoor unit horizontally, and keep 19. 7in [500mm] or more between the outdoor unit and traversing pipe if placing pipe transversely.
Customer Support
www.ahirdirectory.org
Variable Refrigerant Flow (VRF) Multi-Split AC and HP AHRI Standard 1230
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Documents / Resources
|
TOSHIBA MUP1201FT6P-UL VRF Outdoor
Unit
[pdf] User Guide
MUP1201FT6P-UL VRF Outdoor Unit, MUP1201FT6P-UL, VRF Outdoor Unit, Outdoor
Unit, Unit
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>