TOSHIBA MUP1201FT6P-UL VRF Outdoor Unit User Guide

May 15, 2024
Toshiba

TOSHIBA MUP1201FT6P-UL VRF Outdoor Unit

TOSHIBA MUP1201FT6P-UL VRF Outdoor Unit

Heat Recovery Features

  • Modules and pairings available from 6 to 30 tons

  • Modules have inverter-driven scroll compressors

  • Direct-drive, inverter-driven outdoor motor

  • Up to 3937 ft actual total system piping (liquid line)

  • 656 ft (200 m) actual piping length from outdoor unit to furthest fan coil

  • Operating temperature range
    Cooling (db): -10º to 125 ºF (–15º to 52ºC)
    Heating (wb): –22º to 60ºF (–25º to 18ºC)

  • Protection: high pressure sensor and switch, low pressure sensor and switch, process controller board fuse, inverter overload protection

  • 7-year compressor limited warranty

  • 5-year parts limited warranty

Header Unit Model: MMY-MUP1201FT6P-UL

PERFORMANCE

Nominal Cooling Capacity Btu/h 120,000
Nominal Heating Capacity Btu/h 135,000
Maximum Number of Indoor Units 21

SIMULTANEOUS COOLING AND HEATING EFFICIENCY†

SCHE, Ducted FCUs 31.0
SCHE, Ductless FCUs 35.0

COOLING EFFICIENCY†

EER/IEER, Ducted FCUs Btu/Wh 11.6/22.0
Power Consumption, Ducted FCUs kW 8.60
EER/IEER, Ductless FCUs Btu/Wh 12.1/24.6
Power Consumption, Ductless FCUs kW 9.26

HEATING EFFICIENCY†

COP at 47°F, Ducted FCUs 3.84
Power Consumption, Ducted FCUs kW 8.53
COP at 47°F, Ductless FCUs 4.20
Power Consumption, Ductless FCUs kW 8.76
Fan Type (Qty) Propeller (1)
Airflow, Standard Range CFM 7416
Sound Pressure dBA 60.0
External Static Pressure* in. wg 0.321

LEGEND

db — Dry Bulb
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
FCU — Fan Coil Unit
IEER — Integrated Energy Efficiency Ratio
wb — Wet Bulb
SCHE — Simultaneous Cooling and Heating Efficiency

ELECTRICAL

Power Supply V/Ph/Hz 460/3/60
Minimum Circuit Amps (MCA) A 21.3

Maximum Overcurrent Protection

(MOCP)

| A| 25

COMPRESSORS

Type (Number) Hermetic Twin Rotary (1)

FAN MOTOR

Motor Output kW 0.33 x 2

PHYSICAL DATA

Pipe Connection Size – Liquid (High Pressure) in. 1/2 (Brazed)
Pipe Connection Size – Gas (Low Pressure) in. 1-1/8 (Brazed)
Discharge – Gas (High/Low Pressure) 3/4 (Brazed)
Refrigerant R-410A
Factory Charge†† lb 19.8
Unit Width in. 51-1/2
Unit Height in. 66-1/2
Unit Depth in. 31-1/4
Net Weight lb 686

†Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230 Standard.
Cooling: Indoor 80°F (27°C) db/67°F (20°C) wb; Outdoor 95°F (35°C) db
Heating: Indoor 70°F (21°C) db; Outdoor 47°F (8°C) db/43°F (6°C) wb
*Requires setting by menu functions.

††Additional charge required.
NOTE: Unit cabinet and coil slab shall be capable of withstanding 500-hour salt spray test.

DIMENSIONAL DRAWING OUTDOOR UNIT MMY-MUP1201FT6P-UL

Note

  1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 78. 7in [2000mm] apart from the obstacle.
  2. Draw out the pipe procured locally to the front of the outdoor unit horizontally, and keep 19. 7in [500mm] or more between the outdoor unit and traversing pipe if placing pipe transversely.

Dimensional Drawing Outdoor Unit Mmy-mup1201ft6p-ul

Customer Support

Logowww.ahirdirectory.org
Variable Refrigerant Flow (VRF) Multi-Split AC and HP AHRI Standard 1230

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.