BANNER R95C-8UI-MQ 8 Port Analog In To ModBus Hub User Guide
- June 15, 2024
- BANNER
Table of Contents
BANNER R95C-8UI-MQ 8 Port Analog In To ModBus Hub User Guide
Features
This guide is designed to help you set up and install the R95C 8-Port Analog In to ModBus® Hub. For complete information on programming, performance, troubleshooting, dimensions, and accessories, please refer to the Instruction Manual at www.bannerengineering.com. Search for part number 233568 to view the Instruction Manual. Use of this document assumes familiarity with pertinent industry standards and practices.
Overview
When an analog input value is received by the R95C-8UI-MQ hub, the numerical
representational value is represented via Mod Bus registers.
Analog Ranges
Voltage = 0 mV to 11,000 mV
Current = 0 µA to 24,000 µA
Mechanical Installation
Install the R95C to allow access for functional checks, maintenance, and
service or replacement. Do not install the R95C in such a way to allow for
intentional defeat.
Fasteners must be of sufficient strength to guard against breakage. The use of
permanent fasteners or locking hardware is recommended to prevent the
loosening or displacement of the device. The mounting hole (4.5 mm) in the
R95C accepts M4 (#8) hardware.
CAUTION: Do not overtighten the R95C’s mounting screw during
installation. Overtightening can affect the performance of the R95C.
Status Indicators
The R95C 8-Port Analog In to ModBus® Hub has matching amber LED indicators on both sides for each analog in port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the Mod Bus communication.
Power Indicator Green LED
Indication| Status
Off| Power off
Solid Green| Power on
Modbus Communication Amber LED
Indication| Status
Off| Modbus communications are not present
Flashing Amber (4 Hz)| Modbus communications are active
Solid Amber for 2 Seconds, Then to Off| Modbus communications are lost after
connection
Solid Amber for 2 Seconds, Then to Flashing Amber (4 Hz)| Modbus
communications momentarily lost, but then communication was reestablished
Analog In Amber LED
Indication| Status
Off| Analog current value is less than setpoint SP1 OR analog value is greater
than setpoint SP2
Solid Amber| Analog current value is between setpoint SP1 AND setpoint SP2
Default Current
Values:
SP1 = 0.004 A
SP2 = 0.02 A
| Default Voltage
Values:
SP1 = 0 V
SP2 = 10 V
Specifications
Supply Voltage
12 V DC to 30 V DC at 400 mA maximum
Power Pass-Through Current
500 mA per port maximum
Analog Input Impedance
Current version: Approximately 250 ohms
Voltage version: Approximately 14.3K ohms
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity
400 µA
Indicators
Green: Power
Amber: ModBus communications
Amber: Analog In status
Connections
(8) Integral 4-pin M12 female quick-disconnect connector
(1) Integral 5-pin M12 male quick-disconnect connector
Construction
Coupling Material: Nickel-plated brass
Connector Body: PVC translucent black
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude,
5 minutes sweep, 30 minutes dwell) Meets IEC 60068-2-27 requirements (Shock:
15G 11 ms duration, half sine wave)
Certifications
Banner Engineering BV
Park Lane, Culliganlaan 2F bus 3
1831 Diegem, BELGIUM
Turck Banner LTD Blenheim House
Blenheim Court Wickford, Essex SS11 8YT
SANAP SINAL
Product Identification
Environmental Rating
IP65, IP67, IP68
UL Type 1
Operating Conditions
Temperature: –40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature: –40 °C to +80 °C (–40 °F to +176 °F)
Required Overcurrent Protection
WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.
Overcurrent protection is required to be provided by end product application
per the supplied table.
Overcurrent protection may be provided with external fusing or via Current
Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to
www.bannerengineering.com.
Supply Wiring (AWG)| Required Overcurrent Protection (A)| Supply
Wiring (AWG)| Required Overcurrent Protection (A)
---|---|---|---
20| 5.0| 26| 1.0
22| 3.0| 28| 0.8
24| 1.0| 30| 0.5
Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in
material and workmanship for one year following the date of shipment. Banner
Engineering Corp. will repair or replace, free of charge, any product of its
manufacture which, at the time it is returned to the factory, is found to have
been defective during the warranty period. This warranty does not cover damage
or liability for misuse, abuse, or the improper application or installation of
the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES
WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING
UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of
Banner Engineering Corp., replacement.
IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER
PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR
ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT
DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN
CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR
OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the
design of the product without assuming any obligations or
liabilities relating to any product previously manufactured by Banner
Engineering Corp. Any misuse, abuse, or improper application or
installation of this product or use of the product for personal protection
applications when the product is identified as not intended for such purposes
will void the product warranty. Any modifications to this product without
prior express approval by Banner Engineering Corp will void the product
warranties. All specifications published in this document are subject to
change; Banner reserves the right to modify product specifications or update
documentation at any time. Specifications and product information in English
supersede that which is provided in any other language. For the most recent
version of any documentation, refer to:
www.bannerengineering.com.
For patent information, see
www.bannerengineering.com/patents.
Document title: R95C 8-Port Analog In to ModBus® Hub Quick Start Guide
Part number: 233567
Revision: A
Original Instructions
© Banner Engineering Corp. All rights reserved.