njoy DDSU666 Smart Meter User Manual

June 15, 2024
NJOY

njoy DDSU666 Smart Meter

njoy-DDSU666-Smart-Meter-PRODUCT

Product Information

Specifications

  • Model: DDSU666
  • Accuracy class : Active Class 1
  • Frequency : 60Hz
  • Reference voltage : 230V
  • Current specification: 5(80)A (Direct connection), 1.5(6)A (Via transformer)
  • Instrument constant : 800imp/kWh (Direct connection), 6400imp/kWh (Via transformer)

Product Usage Instructions

Brief Introduction

The DDSU666 is a bidirectional Smart Meter that records the load curve and controls energy flows. It provides highly accurate measurements and rapid communication through the chosen communication network. This product is compatible with nJoy inverters models:

  • Astris Series Grid-tied inverter Monophase – 2K/3K/4K/5K/6K/7K/8K/10K
  • Ascet Series Hybrid inverter Monophase – 5K/6K

Working Principle

The working principle of the DDSU666 can be understood from the block diagram shown in Figure 2.

Main Technical Performance & Parameters

Model Specification

The model specification of the DDSU666 is as follows:

  • Model: DDSU666.004.0004
  • Accuracy class : Active Class 1
  • Frequency: 60Hz
  • Reference voltage : 230V
  • Current specification: 5(80)A (Direct connection), 1.5(6)A (Via transformer)
  • Instrument constant: 800imp/kWh (Direct connection), 6400imp/kWh (Via transformer)

Please refer to Table 1 for the model specification.

Percentage Error

The percentage error for different current ranges is as follows:

  • Type : Via CT
  • Current range : 0.01InI

FAQ

Q: What should I do if any of the package content is missing or damaged?

A: If any of the package content is missing or damaged, please contact the shop where you have bought the product from.

Before using this product, carefully read all product documentation and retain it for future reference.

Thank you for purchasing our products!

Please read this manual before using the product.

A Smart Meter is a bidirectional device that records the load curve and controls the various energy flows, giving highly accurate measurements and rapid communication through the chosen communication network.

nJoy inverters models that are compatible with this product:

Astris Series Grid-tied inverter Monophase

2K/3K/4K/5K/6K/ 7K/8K/10K

Ascet Series Hybrid inverter Monophase

5k/6K

NOTE

If any of the above package content is missing or is damaged please contact the shop where you have bought the product from.

Brief Introduction

Main application & applicable range

Type DDSU666 single-phase electronic energy meter (din-rail) (hereinafter referred to as the “instrument”) is designed based on power monitoring and energy metering demands for electric power system, communication industry, construction industry, etc. as a new generation of intelligent instrument combining measurement and communication function, mainly applied into the measurement and display for the electric parameters in the electric circuit including voltage, current, power, frequency, power factor, active energy, etc. The network can be realized through RS485 communication interface and external device. Adopting the standard DIN35mm din rail mounting and modular design, it is characterized with small volume, easy installation and easy networking, widely applied into the internal energy monitoring and assessment for industrial and mining enterprises, hotels, schools, large public buildings.

Product Features

  1. Metering the positive and negative active power.
  2. Adopting wide LCD, it has clear vision.
  3. RS485 communication function with communication protocol complied with Modbus-RTU.
  4. Adopting DIN35mm standard din rail mounting, structural modular design, it is characterized with small volume, easy installation and easy networking.

Model composition and meanings

njoy-DDSU666-Smart-Meter-FIG1

Applicable environmental condition.

Regulated working temperature range: -25°~C+60°C
Limited working temperature range : -35°C~+70°C
Relative humidity(Annually average): 75%
Atmospheric pressure :86kPa~106kPa

Working Principle

njoy-DDSU666-Smart-Meter-FIG2

The working principle block diagram of the instrument is shown in figure 2

Main Technical Performance & Parameters

Model specification


Model

| Accuracy class| ****

Frequency

| Reference

voltage

| Current

specification

| Instrument constant| ****

Type

---|---|---|---|---|---|---
DDSU666.004.0004| Active

Class 1

| 60Hz| 230 V| 5(80)A| 800imp/ kWh| Direct

connection

DDSU666.004.0004| Active

Class1

| 60Hz| 230 V| 1.5(6)A| 6400imp/ kWh| Via transformer

NOTE

Please take the physical sign as standard.

Percentage error



Type

| ****


Current range

| ****


Power factor

| Percentage error limit of each class

instrument (%)

---|---|---|---
Class 1



Via CT

| 0.01In≤I<0.05In| 1| ±1.5
0.05In≤I≤Imax| 1| ±1.0
0.02In≤I<0.1In| 0.5L, 0.8C| ±1.5
0.1In≤I≤Imax| 0.5L, 0.8C| ±1.0



Direct connection

| 0.05Ib≤I<0.1Ib| 1| ±1.5
0.1Ib≤I≤Imax| 1| ±1.0
0.01Ib≤I<0.2Ib| 0.5L, 0.8C| ±1.5
0.2Ib≤I≤Imax| 0.5L, 0.8C| ±1.0

Table 2 Percentage error of single phase energy meter not exceeding the below corresponding limited value

NOTE
In: secondary rated current of the current transformer; Ib: calibrated current of the meter;
L : inductive

C : capacitive

Start


Instrument

| Accuracy class of the energy meter| ****

Power factor

---|---|---
Class 1
Direct connection| 0.004Ib| ****

1

Via transformer| 0.002In

Table 3 Under the referenced voltage and Table 4, the energy meter can be started and continuously measure the energy

Deflection

The electric energy meter should have good anti-deflection logic. When the voltage loop with 1.15 times of referenced voltage and the current loop is disconnected, the energy will not produce more than one pulse.

Deflection

Specified operating voltage range 0.9Un~1.1Un
Extended operating voltage range 0.8Un~1.15Un
Ultimate operating voltage range 0 Un~1.15Un
Power consumption of the voltage circuit ≤1W/8VA
Power consumption of the current circuit ≤2.5VA

Table 4 Electrical parameters

Other technical parameters

Measuring range| 0~999999.99 kWh (only display 6 bit, automatic shift

of decimal point)

---|---
Display mode| LCD display
Communication

protocol

| Modbus-RTU protocol

Table 5 Other technical parameters

Adoption for key components

Metering chip SH79F7019
Crystal 32.768kHz
Power transformer ZTY6.170.234

Printed wiring board

| 1.5 (6) A:ZTY8.067.2729V2, ZTY8.067.2731V2, ZTY8.067.2732V2

5 (80) A : ZTY8.067.2729V2, ZTY8.067.2730V2

Current transformer| ZTY6.176.301

Table 6 Adoption for key components

NOTE: The actual plate number is determined according to the actual sample table.

Main functions

Metering function

  1. Accurately metering the positive and negative active power;
  2. The storage data of the electric energy meter will not lost after powering off.

Displayed functionsnjoy-DDSU666-Smart-Meter-FIG3

When the energy meter is in normal working condition (on load state), the positive pulse indicator should be flashed. If long time for no flashing or light for the indicator, please check whether the wiring mode of the energy meter is right or not.

Symbol Meaning
V The unit of the voltage, the display data of indicating LCD is voltage
A The unit of the current, the display data of indicating LCD is current
W The unit of the active power, the display data of indicating LCD is active

power
var| The unit of the reactive power, the display data of indicating LCD is reactive power
Hz| The unit of the frequency, the display data of indicating LCD is frequency
kWh| The unit of the active energy, the display data of indicating LCD is active energy

Table 7 LCD logo meanings

The display time of the measurement data is five seconds and information sample for every page of the measured information of measurement data (if not consistent with the instrument panel, please take the object as standard.) Light time of the background: 1 min.

Display interface Instruction

|

Means the current display voltage is U, the unit is “V”, the left picture is U=220.0V

|

Means the current display current is I, the unit is “A”,

the left picture is I=5.000A.

|

Means the current display is the active power P, the unit is “kW”, the left picture is P=1.100kW.

|

Means the current display is the power factor Ft, the left picture is Ft=1.000.

---|---

|

Means the current display is frequency F, the left picture is F=50.00Hz.

|

Means the current positive active energy EImp, the unit is “kWh”, the left picture is EImp=1.20kWh.

                          |

Means the current negative active energy EExp, the unit is “kWh”, the left picture is EExp=1.00kWh.

|

Means the current combination active energy total ComEp, the unit is “kWh”, the left picture is ComE- p=2.20kWh.

|

Means the current communication protocol is Modbus.

|

Represents 8 data bits, no effect bit and one stop bit of the current communication protocol.

|

Means the current communication address is 11.

|

Means the current communication baud rate is 9600.

Setting up the RS485 communication parameters

njoy-DDSU666-Smart-Meter-FIG16

2 communication parameters can be changed on the smart meter: parity and channel. For this, you need to long press the button until it will show 2 alternating screens: 8n1 (parity) and 001 (channel). Those 2 screens will alternate every 2-3s for a while, after this the smart meter will return to its default state showing the power, voltage, etc. For changing the parity, when the parity screen (8n1) is showed up, a short press will switch to the next setting (8E1) and so on, cycling through the 4 possible settings wich are:
8n1 – 8 data bits, no parity, 1 stop bit: 8E1 – 8 data bits, even parity, 1 stop bit
8n2 – 8 data bits, no parity, 2 stop bits : 8o1 – 8 data bits, odd parity, 1 stop bit
When the channel screen shows up, you can short-press the button to increment the channel number by 1. Pressing long the button will cause the channel number to increase faster. Upon reaching 099 next short press will bring the channel number back to 001. When all settings are good, wait until the display returns to the default,  showing power, voltage etc. Now the new settings are saved and active.

Communication function

njoy-DDSU666-Smart-Meter-FIG17

The instrument adopts RS485 communication mode with baud rate to be set as 1200, 2400bps, 4800bps and 9600bps.For the same communication circuit, it can at most be connected with thirty-two instruments at the same time, with each instrument to be set as their communication address. For the communication connection, it should use shielded twisted pair with copper mesh with wire diameter not below 0.5mm2. On wiring arrangement, the communication line shall be away from strong cable or other strong electric field with the maximum transmission distance to be 1200m. For the typical networking connection mode, please see the below figure, users can select other suitable connection mode based on detailed conditions.

Parameter address| P ar am e t er code| Instruction of the

parameters

| Type of data| Length of data

Word

| Read&write attributes
---|---|---|---|---|---
0000H| UCode| P r o gr amming

password codE

| 16-bit with

symbols

| 1| R/W
0001H| REV.| Reserved, actual

read is the

version number

| 16-bit with

symbols

|

1

|

R

0002H| ClrE| Electric energy zero clearing CLr.E(1:zero clearing)| 16-bit with

symbols

|

1

|

R/W

0003H| RESERVED| RESERVED| 16-bit with

symbols

| 1|
0004H| RESERVED| RESERVED| 16-bit with

symbols

| 1|
0005H| ChangePro- tocol| Protocol      chang-

ing-over

| 16-bit with

symbols

| 1| R/W
0006H| Addr| Communication address Addr| 16-bit with

symbols

| 1| R/W
---|---|---|---|---|---
0007H| Urat| RESERVED| 16-bit with

symbols

| 1|
0008H| Irat| RESERVED| 16-bit with

symbols

| 1|
0009H| RESERVED| RESERVED| 16-bit with

symbols

| 1|
000AH| RESERVED| RESERVED| 16-bit with

symbols

| 1|
000BH| RESERVED| RESERVED| 16-bit with

symbols

| 1|
000CH| BAud| Communication baud rate

bAud

| 16-bit with

symbols

|

1

|

R/W

000DH| RESERVED| RESERVED| 16-bit with

symbols

| 1|
000EH| RESERVED| RESERVED| 16-bit with

symbols

| 1|
000FH| RESERVED| RESERVED| 16-bit with| 1|
0010H| RESERVED| RESERVED| 16-bit with| 1|
2000H| U| Voltage| single precision

floating decimal

| 2| R
2002H| I| Current| single precision

floating decimal

| 2| R
2004H| P| Conjunction active power, the unit is KW| single precision

floating decimal

|

2

|

R

2006H| Q| Conjunction reactive power, the unit is Kvar| single precision

floating decimal

|

2

|

R

2008H| RESERVED| RESERVED| single precision

floating decimal

| 2| R
200AH| RESERVED| Conjunctioon power factor| single precision

floating decimal

| 2| R
200CH| RESERVED| RESERVED| single precision

floating decimal

| 2| R
200EH| Freq| Frequency| single precision

floating decimal

| 2| R
2010H| RESERVED| RESERVED| single precision

floating decimal

| 2| R
Electrical data of the secondary side
4000H| Ep| Active in electric- ity| single precision

floating decimal

| 2| R

When the instrument is set to be ModBus-RTU transmission mode, ModBus-RTU communication protocol adopts host-slave response in one communication line. Firstly, the host computer’s signal will seek for a terminal device (slave) with only one address, then the terminal device will produce response signal and transmit to the host computer in opposite direction, that is, half duplex working mode. This protocal only allows communication between the host (PC, PLC, etc.) and the terminal device, rather than data exchanges between the independent terminal devices. Thus, each terminal device will not occupy the communication circuits in their initialization, and only be limited to response the query signal to the host computer. The instrument can provide ModBus-RTU communication protocol (see appendix A), for the parameter information to be read or modified by the communication, please see the below table.

ChangeProtocol such as protocol switching, data for 2 for Modbus RTU protocol -, data to 1 for DL/T 645-2007;
The CLr. E power reset write 1 removal of total power; BAud rate: 1:2400bps; 2:4800bps; 3:9600bps;

Outline &Mounting Dimension

Outline dimension: 36mm×98mm×65mm Din rail mounting dimension: 35mm, with configuration to be shown as figure 4njoy-DDSU666-Smart-Meter-
FIG18

Installation & Operation Instruction

Inspection

  1. Before installation, firstly check whether the model No. and specification of the product on the package is the same as the object. If not, please contact the supplier.
  2. Check whether the product shell in the carton is damaged, if is, please contact the supplier.

Installation

Directly clip the instrument on the rail and install it on the distribution box.

  1. When installing, firstly clip one terminal of the slot and then clip to the rail with power.
  2. When disassembling, press the movable card with a screwdriver and take out the instrument.

Wiring mode

Instruction of wiring terminal

njoy-DDSU666-Smart-Meter-FIG19

Before powering, you must check whether the wiring mode of the instrument is correct, and the wiring diagram is shown as below:

Diagnosis, analysis and elimination of common faults

Fault phenomenon Analysis of causes Troubleshooting Remark

Display fault

| The wiring may not connected according to the wiring diagram of the meter| Check if the actual connection is the same as the requirement of the wiring diagram. Pay special attention to “N” position of the voltage, the high&low end of the current and terminal labeling are different from actual number.| While checking the connection, be sure the meter is in the state of disconnection, guarantee the safety of human life.

Communication

fault

| The communi- cation setting information of the meter may be incorrect| Check if the communication setting information such as comunication address, baud rate, verification mode is the same as the PC settings.|

If the above method cannot eliminate the fault, please contact with the aftersale  service of digital meter from Zhejiang CHINT Instrument Co., Ltd.
Transportation & Storage

The package of the instrument shall adopt materials complied with environmental protection, under package condition, the instrument and accessories shall be stored in the dry and ventilated places, to avoid humidity and corrosive gas erosion, with the limited environmental temperature for storage to be -40°C!+70°C and relative humidity not exceeding 75%. The package of the instrument shall comply with the provisions of GB/T 13384- 2008 of General specifications for packings of mechanical and electrical products with the environmental temperature requirement and transportation for the normal storage complied with the provisions of GB/T 25480-2010 of Basic environmental conditions and testing methods for instruments transportation and storage

Complete set of package for single product, including:

  1. One set of instrument
  2. One operation manual
  3. One bag of desiccant
  4. Certificate

Maintenance & Service

Start| Address code| Function

code

| Data field| CRC check

code

| End
---|---|---|---|---|---
More than 3.5-character dead time|

1 character

|

1 character

|

n characters

|

2 characters

| More than 3.5-character dead time

Appendix A: MODBUS-RTU Communication Protocol

Communication format

Information transmission adopts asynchronous mode, taking byte as the unit. The communication date transmitted between the host and slave computer is the format of 10-digit characters, including one start bit(0), 8 data bits without check bit, two stop bits(1)(other format can be customized). Format of information frame:

Communication information transmitting procedure

When communication command is transmitted from the host computer to the slave computer, the slave computer which matches the address code sent by the host computer receives the communication command. If CRC checks without any fault, then the corresponding operation will be carried out, after that the implement result (date) is returned to the host computer. The returned information contains address code, function code, implement date and CRC check code.

Address code

The address code is the first byte of each communication frame, with the range from 1 to 247. Each slave must have an exclusive address code in the bus, only the slave computer which matches the address code sent by the host computer can respond returned information. When the slave computer returns the information, the returned data will begin with their respective address codes. The address code sent from the host computer indicates the slave address, the returned address code from the slave computer indicates the slave address, while the corresponding address code indicates where the information comes from.

Function code

It’s the second byte of each communication frame. It’s sent by the host and tells the slave computer what actions should be carried out through function code. The slave will respond, and the functional code is the same as that sent by the host computer, which indicates that the slave computer has responded the host and complemented the relative operation. The instrument supports the following two function codes:

Function

code

| Definition| Operation
---|---|---
03H| Read register| Read one or several register data
10H| Write multichannel

register

| Write n 16-bit binary data into n continuous registers

A.2.3 Data area

The data field will be different based on different function codes. These data can be numerical values, reference addresses and so on. For different slave computers, both the address and data information are different, and the communication information table should be provided. The host utilizes communicate command (function code 03H and 10H) to read and modify the data registers of the slave freely. But the data length which is read or write at one time should not be out of the effective range of the data register’s address.

A.3 Brief introduction of function code

A.3.1 Function code 03H: Read register

For example : The slave address which the host intends to read is 01H, the start register address is two register data of 0CH, sent by the host:

The host sends Send message
Address code 01H
Function code 03H
Start register address High byte
low byte 0CH

Register number

| High byte| 00H
low byte| 02H

CRC

| low byte| 04H
High byte| 08H

If the data of the slave register 0CH, 0DH is 0000H, 1388H, the slave will return:

The slave returns Return message
Address code 01H
Function code 03H
Bytes 04H

Register 0CH data

| High byte| 00H
low byte| 00H

Register 0DH data

| High byte| 13H
low byte| 88H

CRC check code

| low byte| F7H
High byte| 65H

A.3.2 Function code 10H: Write multi-port register

For example: The host intends to save data of 0002H, 1388H, 000AH into the slave address of 01H, the start register address is the three registers of 00H, sent by the host:

The host sends Send message
Address code 01H
Function code 10H

Register 0CH data

| High byte| 00H
low byte| 00H

Register 0DH data

| High byte| 00H
low byte| 03H
Write bytes| 06H
The data to be written

in 00H register

| High byte| 00H
low byte| 02H
The data to be written

in 01H register

| High byte| 13H
low byte| 88H
The data to be written

in 02H register

| High byte| 00H
low byte| 0AH

CRC check cod

| low byte| 9BH
High byte| E9H

Returned by the slave

The slave returns Return message
Address code 01H
Function code 10H

Start register address

| High byte| 00H
low byte| 00H

Register number

| High byte| 00H
low byte| 03H

Register number

| low byte| 80H
High byte| 08H

A.4 16-digit CRC check code

The host or slave computer can be judged by the check code to see if the received information is correct or not. The interruption by electronic noises or other factors may cause errors during information transmission. 16-digit CRC check code is calculated by the host, located at the end of the transmit information frame. The slave recalculates the received information of CRC and compares if the calculated CRC goes in line with the received CRC, if not, there is an error. Only 8 data bits are used during CRC calculation, both the start bits and the stop bits are not involved in the calculation.

The calculation method of CRC check code is stated as follows:

  1. Pre-arrange one 16-digit register as a hexadecimal FFFF ( i.e. fully 1), the register is called CRC register;
  2. Make the first 8-digit binary data ( the first byte of the communication information frame) with the lower 8 digits of the 16-digit CRC register by XOR calculation, the result is placed in CRC register;
  3. Shift the content of CRC register rightward by one digit (towards the lower digit) and fill in the highest digit with 0, check the shift-out digit after rightward shifting;
  4. If the shift-out digit is 0: repeat step 3) (shift rightward one digit again); If the shift-out digit is 1: make CRC register with multinomial A001 by XOR calculation
  5. Repeat step 3) and 4) until shift rightward for 8 times, then all the 8 digits are processed;
  6. Repeat step 2) and 5), process the next byte of the communication information frame;
  7. After calculating all the bytes of the communication information frame (exclude CRC check code) according to the above steps, the content of the CRC register to be get is: 16-digit CRC check code

A.5 Error handling

When the meter detects other errors except the error of CRC check code, the information will be returned to the host, the highest digit of the function code is 1, i.e. the function code returned to the host from the slave is adding 128 base on the function code sent from the host. The error returned from the slave is as follows:

Address code| Addr Function code(top digit is 1)| Error code| CRC check code low byte| CRC check code High byte
---|---|---|---|---
1 byte| 1 byte| 1 byte| 1 byte| 1 byte

Error code is as follows:

01H| Illegal function code| The function code received is not supported by the instrument
---|---|---
02H| Illegal register address| The register address received is out of the register

address range

03H| Illegal data value| The data value received is out of the corresponding

address data range

Before using this product, carefully read all product documentation and retain it for future reference.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>