LEDALITE ID-EL EyeLine Wall Light Installation Guide

June 15, 2024
LEDALITE

LEDALITE ID-EL EyeLine Wall Light

Product Information

Specifications

  • Product Name : EyeLine Wall Fixtures
  • Installation Type : Continuous Run and Standalone Luminaire Configurations
  • Installation Steps:
1. Install driver pods
2. Install mounting rails on wall
3. Install luminaires with power connections
4. Install remaining luminaires and join
5. Level row with adjusting screws
  • Recommended Tools : #2 Phillips bit and screwdriver
  • Recommended Personnel: 2 persons for installation

Product Usage Instructions

Step 1: Install Driver Pods
Refer to the ID-DP_DriverPod.PDF for detailed instructions on installing the driver pods.

Step 2: Install Mounting Rails on Wall
For standalone 4ft installations

  1. Align, level, and secure the wall rail to the structure with a minimum of 3 fasteners per 4ft section.
  2. Cut out the section shown in the center of the wall rail for clearance. Cut along the green dots on the top edge with sidecutters and bend the remainder to snap off.

For row installations
Remove spacers from both sides of the wall rail. Bend the portion as shown in the diagram and it will snap off at the green line.

Step 3: Install Luminaires with Power Connections
Remove the knockout on the rail and run DC power feeds through it. Use the appropriate wire supplied by others for the driver pod:

  • Single Driver Pod : CMR/CMP 22/2 AWG or thicker wire required.
  • Dual Driver Pod : CMR/CMP 22/4 AWG or thicker wire required.

Prepare to secure the luminaire to the wall while ensuring that the wiring is clear of the metal components. Use the provided screws to attach the luminaire to the wall rail.

Step 4: Install Remaining Luminaires and Join
Repeat Step 3 to install the remaining luminaires. Join them together securely.

Step 5: Level Row with Adjusting Screws
Use adjusting screws to level the row of luminaires.

FAQ

  • Q: Can I lift the luminaires by the outer rail or lens?
    A: No, you should not lift the luminaires by the outer rail or lens. Ensure proper handling to avoid damage.

  • Q: What type of hardware should I use to secure the wall rail to the structure?
    A: The installer is responsible for using appropriate hardware for the type of structure behind the rail.

  • Q: What are the maximum distances allowed between the driver pod and luminaire?
    A: The maximum distances allowed depend on the gauge of the DC power cable supplied by others. For CMR/CMP 22/2 AWG wire, the max distance is 60ft [18m]. For CMR/CMP 18/2 AWG wire, the max distance is 100ft [30m].

  • Q: Are there any safety precautions to consider during installation?
    A: Yes, it is important to install the EyeLine Wall Fixtures in accordance with national and local building and electrical codes to ensure safety.

EyeLine
Wall LED

Installation Instructions
ID-EL EyeLine Wall

Continuous Run and Standalone Configurations

System Overview

These instructions review how to install EyeLine Wall fixtures. Please refer to layout drawings supplied by Ledalite in conjunction with these installation instructions. The graphics below show the steps required to correctly install EyeLine Wall continuous run and standalone luminaire configurations.

IMPORTANT: Read all instructions including fixture/sensor wiring AND mechanical details before begin-ning installation.

IMPORTANT SAFETY AND HANDLING PROCEDURES

  • DO NOT POWER UP ROW UNTIL ALL FIXTURES ARE INSTALLED AND CONNECTED
  • AVOID HANDLING THE BOTTOM LENS, ONLY LIFT FROM MOUNTING RAIL
  • KEEP LUMINAIRE IN THE BOX UNTIL READY TO BE INSTALLED
  • MAKE SURE ALL LUMINAIRES AND JOINT KITS ARE ACCOUNTED FOR BEFORE BE-GINNING INSTALLATION

CORRECT HANDLING CAUTION: DO NOT PULL ON OUTER RAIL!

Installation Steps Overview

  1. Install driver pods (reference ID-DP_DriverPod.PDF)
  2. Install mounting rails on wall
  3. Install luminaires with power connections
  4. Install remaining luminaires and join
  5. Level row with adjusting screws

TYPICAL INSTALLATION ATTENTION: Install in accordance with national and local building and electrical codes.

CAUTION: DO NOT LIFT BY THE OUTER RAIL OR LENS

NOTES

  • Prior to luminaire installation, lay out fixtures to ensure correct power and non-power sections.
  • Instructions below are based on an example run of 12ft row, refer to layout drawings for each row.
  • Cotton gloves are recommended during installation to avoid fingerprints on lens surface.
  • If cleaning is required, please use warm water and a mild dishwashing soap and a non-abrasive cloth.
  1. SECURE MOUNTING RAIL TO WALL

    1.  2a FOR ROW INSTALLATIONS: REMOVE SPACERS ON RAIL REMOVE SPACERS FROM BOTH SIDES OF WALL RAIL FOR ROW INSTALLATIONS.
      BEND THE PORTION AS SHOWN AND IT WILL SNAP OFF AT THE GREEN LINE.
  2. 2b FOR STANDALONE 4FT INSTALLATIONS: CUT OUT SECTION SHOWN REMOVE SECTION FROM CENTER OF WALL RAIL FOR CLEARANCE.
    CUT GREEN DOTS TOP EDGE WITH SIDECUTTERS, AND BEND THE REMAINDER TO SNAP OFF.

  3. INSTALL DRIVER PODS AND NON-POWERED MOUNTS (SEE ID-DP_DriverPod.PDF)

    • REMOVE KNOCKOUT AND RUN DC POWER FEEDS THROUGH RAIL.
    • NOTE, WIRE SUPPLIED BY OTHERS:
    • SINGLE DRIVER POD: CMR/CMP 22/2 AWG OR THICKER WIRE REQUIRED.
    • DUAL DRIVER POD: CMR/CMP 22/4 AWG OR THICKER WIRE REQUIRED.
  4. PREPARE TO INSTALL LUMINAIRE NOTE : DRIVER POD MAY BE WIRED REMOTELY UP TO 100FT AS PER THE TABLE BELOW. (DC POWER CABLE SUPPLIED BY OTHERS)
    DC Power Cable Gauge| Max Distance Between
    ---|---
    CMR/CMP 22/2 AWG| 60ft [18m]
    CMR/CMP 18/2 AWG| 100ft [30m]

REMOVE SCREWS FROM THE SUPPLIED BAG.
TOOLS NEEDED: #2 PHILLIPS BIT AND SCREWDRIVER
NOTE : RECOMMENDED 2 PERSONS FOR INSTALLATION. THIS IS REQUIRED TO HOLD LUMINAIRE WHILE SECURING TO WALL.

  1. CONNECT DRIVER POD FEED TO LUMINAIRE WITH PROVIDED LEVER-LOCK CONNECTORS

  2. ATTACH FIRST LUMINAIRE TO WALL RAIL

    • INSTALL LUMIMAIRE BY HOOKING ONTO THE WALL RAIL, AND ROTATING DOWN TO LEVEL.
    • ENSURE THAT THE WIRING IS CLEAR OF THE METAL COMPONENTS.
    • CAUTION : ALWAYS HOLD ONTO LUMINAIRE UNTIL ALL FASTENERS ARE INSTALLED
  3. INSTALL LOCKING SCREWS

    • INSERT LOCKING SCREWS AND TIGHTEN ONLY UNTIL FLUSH WITH LUMINAIRE.
      NOTE : THESE WILL BE USED IN LATER STEPS FOR LEVELING.
  4. REPEAT STEPS 4-7 FOR NEXT LUMINAIRE AND SLIDE TOGETHER CAUTION : HOLD ONTO SECOND LUMINAIRE UNTIL ALL FASTENERS ARE INSTALLED

  5. INSERT SUPPLED JOINING SCREW AND TIGHTEN

    • TO CONNECT LUMINAIRES, INSTALL THE REMAINING SUPPLIED JOINER SCREW AND TIGHTEN GENTLY.
    • (NOTE: THIS IS THE SAME TYPE OF SCREW USED ON RAIL)
    • ENSURE THAT THE BOTTOM EDGE OF JOINT IS FLUSH BEFORE FINAL TIGHTENING.
  6. INSTALL JUMPER WIRES PER LAYOUT DRAWINGS

    • JUMPER WIRES ARE SUPPLIED TO ALLOW ONE MODULE TO PROVIDE POWER TO ADDITIONAL PARTS OF THE ROW.
    • THESE MUST BE INSTALLED ACCORDING TO THE LAYOUT DRAWINGS FOR EACH ROW, OR FAILURE COULD OCCUR.
    • CAUTION : DO NOT ENERGIZE CIRCUIT UNTIL ALL JUMPERS ARE INSTALLED
  7. LEVEL ROW BY ADJUSTING SCREWS

    • STARTING AT ONE END OF THE ROW, ADJUST REAR MOUNTING SCREW UNTIL SECTION IS LEVEL.
    • CONTINUE DOWN THE ROW UNTIL ALL SECTIONS ARE LEVEL ON THE TOP PLANE OF LUMINAIRE.
  8. ENERGIZE DRIVER POD AND CHECK SYSTEM NOTE : IF A MODULE DOES NOT ILLUMINATE, CHECK THAT JUMPERS AND POWER FEED LOCATIONS MATCH THE LAYOUT DRAWINGS FOR THE ROW.
    REFER TO LUMINAIRE MAINTINANCE AND CLEANING INSTRUCTIONS IF LENS REQUIRES CLEANING.

Sensor in Rows

Single Sensor Controlling Whole Row

  1. Purple & brown (or purple & grey/pink) control wires MUST be connected between fixtures. Note :

    • A maximum of 8 drivers can be wired to 8 sensors; confirm fixture driver count with factory. Multiple Sensors Controlling Separates Zones in a Row
  2. Purple & brown (or purple & grey/pink) control wires MUST NOT be connected between zones.
    Notes

    • A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.
    • Only one sensor is allowed on a wired zone. (Sensors can be paired together wirelessly via a mobile app).

Sensor Spacing

  • For correct operation, sensor should be placed a minimum distance of 8ft apart.
  • Wireless sensor should be placed no further than 40ft apart for good wireless signal connection.

Important Consideration When Using Sensor in a Row

  • For fixtures with wireless sensors (CS, SB or RA options):
  • DO NOT connect fixture purple and brown (or purple & grey/pink) control wires to an external dimming switch.
  • Fixture mains wiring should not be connected to a circuit with an exter-nal on/off switch.
  • For best aesthetic condition, place sensors at ends of row only so as not to break the continuous lens.
  • For better occupancy coverage in longer rows, sensors may be placed mid run, but keep in mind this will break the continuous lens into dis-crete sections. Alternatively, remote sensors may be used, note the same wiring rules will apply.

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interreference when the equipment is operated in a commer-cial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Occupancy Sensor Coverage
Note: Longer dimension of detection area (Y1, Y2) is parallel to longer dimension of the luminaire.

Daylight Sensor
The light sensor measures the total amount of light in a circular field of approximately 80% of the PIR detection area. The following aspects should be observed during installation:

  • Minimum distance from the window ≥ 2ft (0.6m).
  • Prevent light reflections from outside entering the sensor (for example sunlight re-flection on a car hood) as this will lead to incorrect light regulation.

As a guideline the formula 0.72 X H can be used to calculate the minimum distance be-tween the window and sensor whereby H is the height from the bottom of the window to the sensor.

The detection area for the movement sensor can be roughly divided into two parts;

  • Minor movements (person moving ≤ 3ft/s or 0.9m/s).
  • Major movements (person moving ≥ 3ft/s or 0.9m/s).

Photosensor spatial response

ATTENTION : Install in accordance with national and local building and electrical codes.

© 2023 Signify Holding. All rights are reserved. Reproduction in whole or part is prohibited without the written consent of the copyright owner.

Phone : 604.888.6811
Web: ledalite.com/products

Revision D November 20. 2023 Signify North America Corporation. 400 Crossing Blvd, Suite 600 Bridgewater, NJ 08807. Telephone: 855-486-2216 Signify Canada Ltd. 281 Hillmount Road, Markham, ON, Canada L6C 253. Telephone: 800-668-9008

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

LEDALITE User Manuals

Related Manuals