INSTALLATION INSTRUCTIONS
EP493
EXPLOSION PROOF / WEATHERPROOF PULL STATION
EMERGENCY DOOR RELEASE

This pull station is suitable for use in hazardous areas including outdoor applications. It is important to read all information pertaining to this device and its application.

Electrical Rating

Contacts: DPDT
Contact Rating: 10 amps @ 125/250VAC
Wiring Connection: Terminal Block (#6-32)
Acceptable Wire AWG: 14 to 22 AWG

SDC EP493 Explosion Proof Emergency Door Release Pull Station - UL
Rating

UL Rating:

Class Group
I B, C, D
II E, F, G
III

Outdoor Rating – NEMA Type 4X

Grounding:

SDC EP493 Explosion Proof Emergency Door Release Pull Station -
Grounding

Wiring Connections:

NOTE: Switch polarity shown with the T-handle in the non-activated (up) position.

SDC EP493 Explosion Proof Emergency Door Release Pull Station - Wiring
Connections

Basic Assembly:

SDC EP493 Explosion Proof Emergency Door Release Pull Station - Basic
Assembly

Before Closing Assembly:

  1. Make sure that mating surfaces are clean and free of debris.
  2. Inspect to assure all O-ring seals arein their place. If not, carefully re-install making sure of proper fit.
  3. Squeeze insulator inward and slide switch assembly over backbox making sure insulator is inside backbox.
  4. Before tightening assembly, check tomake sure of proper seating.

Note: Do not substitute O-rings or cover screws with other hardware, as this may degrade or produce failure of device.

Dimensions:

SDC EP493 Explosion Proof Emergency Door Release Pull Station -
Dimensions

Glass Rod Replacement:
The pull station is shipped with the glass rod removed. It is recommended that the station be activated and tested prior to installation of the glass rod.
To replace a broken glass rod, use the supplied allen wrench to open the front cover. Carefully remove the glass debris from broken rod & reset T-Handle to the normal position.
Insert one end of rod under Spring Tab. Then, lift other end of Spring Tab allowing Glass Rod to slip into place.
Replacement Glass Rod
SDC P/N 492-GL4

Any suggestions or comments to this instruction or product are welcome. Please contact us through our website or email engineer@sdcsecurity.com

SECURITY DOOR CONTROLS
WWW.SDCSECURITY.COM
[t] 800.413.8783
805.494.0622
E-mail:service@sdcsecurity.com
801 Avenida Acaso, Camarillo, CA 93012
PO Box 3670, Camarillo, CA 93011

Documents / Resources

| SDC EP493 Explosion Proof Emergency Door Release Pull Station [pdf] Installation Guide
EP493 Explosion Proof Emergency Door Release Pull Station, EP493, Explosion Proof Emergency Door Release Pull Station, Emergency Door Release Pull Station, Door Release Pull Station, Pull Station, Station
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals