Deye SUN-K-GP-EU-AM-LV Grid Connected PV Inverter User Manual
- June 15, 2024
- Deye
Table of Contents
- Introduction
- Safety warnings and instructions
- Operation Interface
- Product installation
- Electrical Connection
- Start up and Shut off
- Zero-export function via energy meter
- General Operation
- Repair and Maintenance
- Error information and processing
- Specification
- EU Declaration of Conformity
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Grid-connected PV Inverter
SUN-60K-G01P3-EU-AM8-LV
SUN-70K-G01P3-EU-AM8-LV
SUN-75K-G01P3-EU-AM8-LV
User Manual
About This Manual
The manual mainly describes the product information, guidelines for
installation, operation and maintenance. The manual cannot include complete
information about the photovoltaic (PV) system.
How to Use This Manual
Read the manual and other related documents before performing any operation on
the inverter.
Documents must be stored carefully and be available at all times.
Contents may be periodically
updated or revised due to product development. The information in this manual
is subject to change without notice. The latest manual can be acquired via
service@deye.com.cn
Introduction
1.1 Appearance Introduction
On-grid inverter can convert solar panel DC power into AC power which can
directly input to the grid. Its appearance is shown below. These models
contain SUN-60K-G01P3-EU-AM8-LV, SUN-70K-GO1P3-EU-AM8-LV, SUN-75K-GO1P3-EU-
AM8-LV.
The following is collectively referred to as “inverter” 1.2 Parts list
Please check the following table, to see whether all the parts are included in
the package:
1.3 Product handling
requirements
Four people stand on both sides of the machine, holding one handles to lift
the machine.
Safety warnings and instructions
Improper use may result in potential electric shock hazards or burns. This
manual contains important instructions that should be followed during
installation and maintenance. Please read these instructions carefully before
use and keep them for future reference.
2.1 Safety signs
Safety symbols used in this manual, which highlight potential safety risks and
important safety information, are listed as follows:
Warning:
Warning symbol indicates important safety instructions, which if not correctly
followed, could result in serious injury or death.
Shock Hazard:
Caution, risk of electric shock symbol indicates important safety
instructions, which if not correctly followed, could result in electric shock.
Safety Hint:
Note symbol indicates important safety instructions, which if not correctly
followed, could result in some damage or the destruction of the inverter.
High Temperature Hazard:
Caution, hot surface symbol indicates safety instructions, which if not
correctly followed, could result in burns.
2.2 Safety instructions
Warning:
Electrical installation of the inverter must conform to the safety operation
rules of the country or local area.
Warning:
Inverter adopts non-isolated topology structure, hence must insure DC input
and AC output are electrical isolated before operating the inverter.
Shock Hazard:
Prohibit disassembling inverter case, there existing shock hazard, which may
cause serious injury or death, please ask qualified person to repair.
Shock Hazard:
When PV module is exposed to sunlight, the output will generate DC voltage.
Prohibit touching to avoid shock hazard.
Shock Hazard:
While disconnect the input and output of the inverter for maintenance, please
waits for at least 5 mins until the inverter discharge the remnant
electricity.
High Temperature Hazard:
Local temperature of inverter may exceed 80℃ while under operating.
Please do not touch the inverter case.
2.3 Notes for using
The single phase string power inverter is designed and tested under related
safety regulations. It can ensure the personal safety of the user. But as a
electric device, it may cause shock or injury by incorrect operation. Please
operate the unit under below requirements:
- Inverter should be installed and maintained by qualified person under local standard regulations.
- Must disconnect the AC side first, then disconnect DC side while doing installation and maintenance, after that, please wait at least 5 mins to avoid getting shocked.
- Local temperature of the inverter may exceed 80 ℃ while under operating.Do not touch to avoid getting injured.
- All electrical installation must be in accord with local electrical standards, and after obtaining the permission of the local power supply department, the professionals can connect the inverter to the grid.
- Please take appropriate anti-static measure.
- Please install where children can not touch.
- The steps to start the inverter:1) switch on the AC side circuit breaker, 2) Switch on the DC side circuit breaker of the PV panel. 3) Turn on the DC switch of the inverter. The steps to stop the inverter:4) switch off the AC side circuit breaker, 5) witch off the DC side circuit breaker of the PV panel. 6) Turn off the DC switch of the inverter.
- Don’t insert or remove AC and DC terminals when the inverter is in normal operation.
- The DC input voltage of the inverter must not exceed the maximum value of the model.
Operation Interface
3.1 Interface View
3.2 Status
Indicator
The inverter panel has 4 indicators, the left one is dc output indicators,
green indicates normal DC input. Beside is the AC indicator, green indicating
normal ac connection. Beside the AC indicator is the operating indicator,
green indicating normal output. The right indicator is alarm. red indicates
alarming.
Indicator | status | Explanation |
---|---|---|
DC | on | Inverter detects DC input |
off | Low DC input voltage | |
AC | on | Grid Connected |
off | Grid Unavailable | |
NORMAL | on | Under normal operating |
off | Stop operating | |
ALARM | on | Detected faults or report faults |
off | Under normal operating |
Table 3.1 Status indicator lights
3.3 Buttons
There are four buttons on the inverter panel: Above is Up and increase
button(UP), Below is down and decrease button(DOWN), Left is ESC button(ESC),
Right is Enter button(ENTER).
Achieving below functions by the four buttons:
- Page turning (use UP and DOWN button)
- Modify adjustable parameters (use ESC and ENTER button)
3.4 LCD Display
Three phase string inverter use 256*128 dot formation display, Display below content:
- Inverter operation status and information;
- Operating information;
- Warning message and malfunction display.
Product installation
4.1 Select installation location
To select a location for the inverter, the following criteria should be
considered:
WARNING: Risk of fire
- Do not install the inverter in areas containing highly flammable materials or gases.
- Do not install the inverter in potentially explosive atmospheres.
- Do not install in small closed spaces where air can not circulate freely. To avoid overheat- ing, always make sure the flow of air around the inverter is not blocked.
- Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting. It is recommended that inverter installed to avoid direct sunlight or raining.
- To avoid overheating ambient air temperature must be considered when choosing the inverter installation location. It is recommended that using a sun shade minimizing direct sunlight when the ambient air temperature around the unit exceeds 104°F/40°C.
- Install on a wall or strong structure capable of bearing the weight.
- Install vertically with a maximum incline of +/-15°. If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
- If install more than one inverter, must leave at least 500mm gap between each inverter. And each inverter must be at least 500mm above and below.And must install the inverter at the place where children cannot touch. Please see picture 4.3.
- Consider whether the installation environment is helpful to see the inverter LCD display and indicator status clearly.
- Must offer a ventilate environment if inverter installed in the airtight house.
Safety Hint:
Do not place or store any items next to the inverter.
|
---|---
4.2 Mounting bracket of inverter
4.3
Inverter Installation
The inverter should be mounted in a vertical position. The steps of mounting
are as follows
- For brick walls, the position of the holes should be suitable for the expansion bolts.
- Make sure the bracket is horizontal and the mounting holes are in the correct points. Drilling the holes on the wall according the marks.
- Using the expansion bolts to fix the bracket to the wall.
Electrical Connection
5.1 DC input terminal connection
- Switch the Grid Supply Main Switch(AC)OFF.
- Switch the DC lsolator OFF.
- Assemble PV input connector to the inverter.
Warning:
When using PV modules, please ensure the PV+ & PV- of solar panel is not
connected to the system ground bar.
Safety Hint:
Before connection, please make sure the polarity of the output voltage of PV
array matches the “DC+” and “DC-” symbols.
Warning:
Before connecting inverter, please make sure the PV array open circuit
voltage is within the 800V of the inverter.
Safety Hint:
Please use approved DC cable for PV system.
Cable type | Cross section(mm²) |
---|---|
Range | Recommended value |
Industry generic PV cable (model: PV1-F) | 4.1~6.0 (12~10AWG) |
Table 5.1 DC Cable Specifications
The steps to assemble the DC connectors are listed as follows:
a) Strip off the DC wire about 7 mm, disassemble the connector cap nut (see
picture 5.3).b) Crimping metal terminals with crimping pliers as shown in picture
5.4.c) Insert the contact pin to the top part of the connector and screw
up the cap nut to the top part of the connector. (as shown in picture
5.5).d)
Finally insert the DC connector into the positive and negative input of the
inverter, shown as picture 5.6.
Warning:
Sunlight shines on the panel will generate voltage, high voltage in series may
cause danger to life. Therefore, before connecting the DC input line, the
solar panel needs to be blocked by the opaque material and the DC switch
should be ‘OFF’, otherwise, the high voltage of the inverter may lead to
lifethreatening conditions.
Warning:
Please use its own DC power connector from the inverter accessories. Do not
interconnect the connectors of different manufacturers.Max. DC input current
should be 20A. if exceeds, it may damage the inverter and it is not covered by
Deye warranty.
5.2 AC terminal connection
Model| Wire Size| Cable(mm²)| Torque value(max)| Max
cable length
---|---|---|---|---
SUN-60K-G01P3-EU-AM8-LV| 0AWG| 53.5mm²| 20.3Nm| O(u3tLs+idNe)2c0amble
SUN-70K-G01P3-EU-AM8-LV| 3/0AWG| 85mm²| 28.2Nm
SUN-75K-G01P3-EU-AM8-LV| 4/0AWG| 107mm²| 28.2Nm
Table 5.2 Recommened cable specifications
Warning:
The AC cable line L1 is connected to socket 1; L2 is connected to socket 2; L3
is connected to socket 3, the PE line is connected to the earth , the N wire
is connected to the socket of N.
AC wire installation method:
- Remove the 8 fixing screws on the AC junction box of the inverter as shown in Pic 5.7. After removing the junction box, you can see the terminals of the inverter. The default is 4 digits as shown in Pic 5.8.
- Connect the cable through the junction box, waterproof jacket, and insert into the terminal (The picture Pic 5.9 shows the connection mode of three phase lines connected to the junction box, ground wire screwed on the inverter shell), and use hexagon screwdriver to presses the wiring harness to the connect terminal as shown in Pic 5.10.
- Screw the AC connection cover back to the shell and tighten all the screws to tighten the waterproof protection connector, as shown in Pic 5.11.
5.2.1 Recommended current protector specifications
Inverter| Rated voltage| Rated output powe(r KW)| Current protection device
(A)
---|---|---|---
SUN-60K-G01P3-EU-AM8-LV| 127| 60| 200
SUN-70K-G01P3-EU-AM8-LV| 127| 70| 240
SUN-75K-G01P3-EU-AM8-LV| 127| 75| 260
Table 5.3 Recommended current protector specifications
5.3 Connection of the ground line
Good grounded is important for resist the surge voltage shock and improve
EMI’s performance.
So before the connection of AC, DC, communication connections, inverter needs
to ground first.
For a single system, just ground the PE cable; For multiple machine systems,
all PE cables of the inverter need to be connected to the same grounding
copper platoon to ensure the equipotent connection. The installation of the
shell ground wire is shown as Pic 5.12 The external protective earthing
conductor is made of the same metal as the phase conductor.
Model | Wire Size | Cable(mm²) | Torque value(max) |
---|---|---|---|
SUN-60K-G01P3-EU-AM8-LV | 3AWG | 26.7mm² | 16.9Nm |
SUN-70K-G01P3-EU-AM8-LV | 0AWG | 53.5mm² | 20.3Nm |
SUN-75K-G01P3-EU-AM8-LV | 2/0AWG | 67.4mm² | 20.3Nm |
Table 5.3 Recommened cable specifications
Warning:
Inverter has built-in leakage current detection circuit, If an external
leakage current protection device is connected, its operating current must be
greater than 300mA or higher, otherwise inverter may not work properly.
5.4 Inverter monitoring connection
Inverter has the function of wireless remote monitoring inverter. The inverter
has Wifi function and Wifi Plug in the accessories is used to realize the
connection between the inverter and the network. The operation, installation,
networking, APP download are detailed in the WIFI PLUG instructions. Figure
5.13 is the Internet monitoring solution.
5.4.1 Installation of datalogger
When installing the WiFi stick, tear off the sealing strip on the inverter. Insert the datalogger into the interface and fix it with a screw. The configuration of the datalogger needs to be performed after various electrical connections have been completed and the inverter DC power on. When the inverter is on the DC power, it is determined whether the datalogger is normally electrified (The LED light shines out of the shell).
5.4.2 Configuration of datalogger
For the configuration of datalogger, please refer to illustrations of the
datalogger.
Start up and Shut off
Ensure that the inverter meets the following conditions before starting the
inverter, otherwise it may cause fire or damage to the inverter without quality
assurance, at the same time the situation on our company does not undertake
any responsibility. At the same time, to optimize the system configuration, it
is recommended that the two inputs be connected to the same number of PV
modules.
a). The maximum open circuit voltage of each set of PV modules shall not
exceed 800 Vdc under any conditions.
b). Each input of the inverter better use the same type of PV module in
series.
c). Total output power of PV shall not exceed the maximum input power of
inverter, each PV modules shall not exceed the rated power of each channel.
6.1 Start up the inverter
When starting up the inverter, should fellow steps below:
- Starting switch on the AC breaker.
- Turn on the DC switch of the PV module, and if the panel provides sufficient starting voltage and power, the inverter will start.
- The inverter will first check the internal parameters and the grid parameters, while the liquid crystal will show that the inverter is self-checking.
- If the parameter is within acceptable range, the inverter will generate energy. NORMAL indicator light is on.
6.2 Shut off the inverter
Must follow below steps while Shutting down the inverter:
- Switch off the AC breaker.
- Wait for 30 seconds, turn off the dc switch (if any), or simply disconnect the dc input connector. The inverter will close the LCD and all led within two minutes.
Zero-export function via energy meter
There’re four kinds of energy meters for this series inverter. First type is
Eastron SDM630-Modbus V2 which is able to measure the Max. 100A current
directly. More details please refer to Pic 7.1& 7.4. For the Eastron SDM630
MCT 40mA, it needs external CT to measure the current. The CT power range is
from 5A-2000A. More details about the Eastron SDM630 MCT, please refer to Pic
7.5 & 7.8. Also, the CHNT meter DTSU666 is supported, it can measure the Max.
80A current directly. More details about the DTSU666, please refer to Pic 7.9
– 7.16.
When you are reading this, we believe that you have completed the connection
according to the requirements of chapter 5, if you have been running your
inverter at this time, and you want to use the zero-export function, please
turn off AC and DC switch of the inverter, and wait for 5 minutes until the
inverter completely discharged.
For system wiring diagram, the red line refers to L line (L1, L2, L3), the
black line refers to the neutral line (N). Connecting energy meter RS485 cable
to inverter’s RS485 port. It’s recommended to install an AC switch between the
inverter and the utility grid, the specs of the AC switch are determined by
the power of load.
If there is no integrated DC switch inside the inverter you purchased, we
commend you to connect the DC switch. The voltage and current of the switch
depend on the PV array you access.
Warning:
In final installation, breaker certified according to IEC 60947-1 and IEC
60947-2 shall be installed with the equipment.
|
---|---
|
|
|
Safety Hint:
Ensuring grid input cables connect 1/4/7/10 port of energy meter, and inverter
AC output cables connect 3/6/9/10 port of energy meter when connecting.
- Press Enter button on the LCD panel in the main interface into the menu options, select [parameter setting] to enter setup submenu, and then select [run param], at this time please input the default password 1234 through pressing the button (up down, enter], enter the operation parameter setting interface, shown as picture 7.17.
- Operate the button [up down], move setting cursor to energy meter and press the button [enter]. At this time you can turn on the energy meter by choosing [up down] button, please press [enter] button to confirm when setting done.
- Move the cursor to [OK], press [enter] to save the settings and exit the running parameters page, otherwise the settings are invalid.
- lf set up successfully, you can return to the menu interface, and display the LCD to (home page] by press the [up down] button. If it displays {meter power XXW], the zero-export function setting is completed. Shown as picture 7.18.
- Meter power 428 W shows positive means grid is supplying the load, and no power fed into grid. if meter power shows negative, it means PV energy is being sold to grid or energy meter wiring conncetion has problem.
- After properly connection is done, wait for inverter starting. If the power of the PV array meets the current power consumption, the inverter will keep a certain output to counteract the power of the grid without backflow .
7.1 Multiple strings and parallel connection meters
This application is that when the string inverters work in parallel, there is
only one power grid and one load, and only one meter can be connected to
prevent reverse current, so only this many-to-one anti-reverse current
connection can be connected.
If there’re several inverters parallelling operation in a plant, also it can
use 1 pcs meter to realize zero export function.For example, if there’re 3 pcs
inverters parallelling operation in the system with 1 pcs meter.We need to
setup 1 pcs inverteras the master and others setup as slaves. And, all of them
need to connect to the meter via RS485 .Below is the system diagram and
configuration of the system.![Deye SUN-K-GP-EU-AM-LV Grid Connected PV Inverter
- Meter function](https://manuals.plus/wp-content/uploads/2023/12/Deye-SUN-K -GP-EU-AM-LV-Grid-Connected-PV-Inverter-Meter-function.jpg)
Name | Description | Range |
---|---|---|
Exp_Mode | AVG: Average power of three phase is zero exported. |
MIN: Phase with minimum load power is zero exported, while the other two phase
may be in purchase mode.| AVG/MIN
CT_Ratio| CT ratio of power grid side meter when extern CT is applied.| 1-1000
MFR| Manufacturer of the grid side meter. Modbus Address of it should be set
as 01.| AUTO/CHNT/ EASTRON
Feedin| Percentage of the Feed in power exported to the grid.| 0-110%
Shunt| Parallel mode. Set one inverter as Master, others are Slave. ONLY need
to set the master, Slave will follow the settings in the master.| OFF/Master/
Slave
ShuntQTY| Number of inverters in parallel| 1-16
Generator| DG side meter function Enable/Disable| ON/OFF
G.CT| CT ratio of power DG side meter when extern CT is applied.| 1-1000
G.MFR| Manufacturer of the DG side meter. Modbus Address of it should be set
as 02.| AUTO/CHNT/ EASTRON
G.Pout| Output power percentage of the DG.| 0-110%
G.Cap| Capacity of the DG.| 1-999kW
Note: Select Meter option in Run Param and long press ENTER button to enter this Meter Setting page.
|
---|---
|
|
|
7.2 How to browse the load power of your PV grid-tie plant on monitoring
platform?
if you want to browse load power of the system and how much energy (KWH)
does it export to grid(inverter output power is used to power the load firstly
and then the surplus energy will feed into grid). You also need to connect the
meter according to above diagram. After the connection completed successfully,
the inverter will show the load power on the LCD. But please don’ tsetup
“Meter ON” . Also, you will be able to browse the load power on the monitoring
platform. The plant setting method as below description. Firstly, go to the
solarman platform(https://pro.solarmanpv.com, this link is for solarman
distributor account; or https://home.solarmanpv.com, this link is for
solarman end user account;) plant home page and click “edit”Secondly, go to plant page, if it shows the PV power, load power
and grid power, which means the configuration is correct.
General Operation
During normal operation, the LCD shows the current status of the inverter, including the current power, total generation, a bar chart of power operation and inverter ID, etc. Press the Up key and the Down key to see the current DC voltage, DC current, AC voltage, AC current, inverter radiator temperature, software version number and Wifi connection state of the inverter. E-Day
|
---|---
|
8.1 The initial interface
From the initial interface, you can check power, daily generation, gross
generation, invertert ID , model and time.Press UP or Down you can check inverter DC voltage, DC current, AC
voltage, AC current, inverter temperature, software version information.You can check the PV information,
the number of strings input, MPPT voltage and MPPT current.You can check the three phase voltage, current, and grid
frequency.
You can check the inverter
LCD software Ver0196 and Control Software Version Ver1400.
There are two black spot in the bottom right corner. The first flash means
inverter is communicating with LCD. The second flash means LCD is communicating
with wifi plug.
8.1.1 Main Menu
There are four submenu in the Main Menu. 8.2 Statistics information
There are five submenu in the statistics.Into each submenu through cursor.
|
---|---
This information is for technician’s reference.
8.3 Fault Record
Only can keep four fault record in the menu include time, customer can deal
with it depends on the error code.
8.4 ON/OFF setting
Into each submenu through cursor.
8.5 Parameter setting
Setting includes system param, run param, protect param, comm.. param. All of
these information for maintenance reference. 8.5.1 System Param
8.5.1.1 Time Set
8.5.1.2 Language Set
8.5.1.3 Display Set
8.5.1.4 Factory data reset 8.5.1.5 Setting Restore
Warning:
Password required– only for access-authorized engineer. Un-authorized access
may avoid the warranty. The initial password is 1234.
8.5.2 Run Param
Name | Description | Range |
---|---|---|
ActiveP | Adjust the output active power in % | 0-1 10% |
QMode | Multiple reactive power control modes | OFF/Q(P)/PF(P) /Q(U)/PF/PER |
ReactP | Adjust reactive power output in % | -100%-+100% |
PF | Power Fator | -1-0.8~+0.8-1 |
Fun ISO | Insulation resistance detection | ON/OFF |
Fun_RCD | Residual current detection | ON/OFF |
Self-check | Inverter’s self-check time.The default value 60s | 0-1000s |
Island | Anti-islanding protection | ON/OFF |
Meter | Energy meter.lf inverter will connect meter,then set here to ON | ON/OFF |
Feed_IN % | It is used to deploy how much power can be feed in to grid when the |
inverter works under zero export mode.(For example,Feed_in=50% of the 75KW modeland loadpower is 36KW. which means Max 37.5KW power can befeed into grid after inverter providing 36Kw to the load firstly.| 0-100%
Warning:
Engineer Only.
We will set the param depends on the safety requirements, so customers don’t
need to reset it.
The password is same as 8.23 Running param
Name | Description | Range |
---|---|---|
ARC | Arc-fault detection function | ON/OFF/Clear |
WGra | Active power response to over frequency | 0-100% Pmax/Hz |
OFDerate | Active power response to under frequency | 0-100% Pmax/Hz |
UFUprate | power response to grid voltage deviation | ON/OFF |
PU | Active power ramp rate (% Pnom/Sec) | 0.1%~50% |
WGraStr | Active power ramp rate at first start (% Pnom/Sec) | 0.1%-50% |
Vref | Grid reference voltage for functions including Q(U),PF(P),P(U)etc. |
80-260V
PowerLimit| Hard/soft export limit control| ON/OFF
VoltageRT| voltage ride through function| ON/OFF
DRM| Demand Response Modes| ON/OFF
Sunspec| Sunspec Function| ON/OFF
Pic 8.24 Run Param
8.5.2.1 Over-frequency Response
This series inverter provides “over-frequency response” function.
Long pressing the “OFD Derate” to enter the “over-frequency response” setting
menu.
Definition of Over-frequency Response Parameters
Parameter | Range | Description |
---|---|---|
StartPoint | 45HZ-65HZ | The Start frequency value for over-frequency response. |
StopPoint | 45HZ-65HZ | The Stop frequency value for over-frequency response. |
RecoverPoint | 45HZ-65HZ | In hysteresis mode, power is restored only when it is |
below this frequency
RecoverGradient| 0.3%¬300% P/min| Ramp rate of power recovery
RecoverDelay| 0-1000s| Time Delay of power recovery in hysteresis mode
ResponseDelay| 0-2000S| Response delay time after entering active power
frequency mode
For example, StartPoint: 50.5Hz, StopPoint: 51.5Hz, RecoverPoint: 50.1Hz, when the grid frequency increases beyond StartPoint: 50.5Hz, the inverter will linearly reduce the power output with a gradient of 100% Pmax/Hz until it reaches StopPoint: 51.5Hz.![Deye SUN-K-GP-EU-AM-LV Grid Connected PV Inverter
- Conditions](https://manuals.plus/wp-content/uploads/2023/12/Deye-SUN-K-GP- EU-AM-LV-Grid-Connected-PV-Inverter-Conditions.jpg)
When the frequency exceeds StopPoint: 51.5Hz, the inverter output should stop
(ie 0 W).
When the frequency is lower than StopPoint: 51.5 Hz, the inverter will
linearly increase the power output with a gradient of 100% Pmax/Hz until it
reaches StopPoint: 50.5 Hz.
In the hysteresis mode, when the frequency is lower than StopPoint: 51.5 Hz,
the inverter will not increase the power output until it is lower than
RecoverPoint: 50.1 Hz.The inverter provides a reactive
power regulation function.
Tap Reactive Power Regulation Mode to select proper regulation mode and set
the corresponding parameters.
-
“OFF” Mode
The reactive power regulation function is disabled. The PF is fixed at +1.000 -
ReactiveP
Adjust reactive power output in %. -
“PF” Mode
The power factor (PF) is fixed and the reactive power is regulated by the parameter PF. The PF ranges from 0.8 leading to 0.8 lagging.
Leading: the inverter is sourcing reactive power to the grid.
Lagging: the inverter is injecting reactive power into the grid. -
“Q(U)” Mode
The reactive power output of the inverter varies in response to the grid voltage. -
“Q(P)” Mode
The reactive power output by the inverter is controlled by the active power of the inverter.
“Q(U)” Mode
Parameter | Range | Description |
---|---|---|
Start | 0%430% Rate out power | The QU mode starts when the active power is |
greater than this value
Stop| 0%430% Rate out power| The QU mode stops when the active power is less
than this value
RMpTime| 40005| Increase or decrease the time required for the reactive power
to reach the specified value of the curve.
PtUsed| 2-6| Point number used In QU Curve
Curve| | QU Curve
Q1| -60% -60% Q/Pn| Value of Q/Pn at point (U1,Q1) on the Q(U) mode curve
1/1| 0-110% VRated| Grid voltage limit at point (U1,Q1) on the Q(U) mode curve
Q2| -60% -60% Q/Pn| Value of Q/Pn at point (U2,Q2) on the Q(U) mode curve
V2| 0-110% VRated| Grid voltage limit at point (U2,Q2) on the Q(U) mode curve
Q3| -60% -60% Q/Pn| Value of Q/Pn at point (U3,Q3) on the Q(U) mode curve
V3| 0-110% VRated| Grid voltage limit at point (U3,Q3) on the Q(U) mode curve
Q4| -60% -60% Q/Pn| Value of Q/Pn at point (U4,Q4) on the Q(U) mode curve
V4| 0-110% VRated| Grid voltage limit at point (U4,Q4) on the Q(U) mode curve
Q5| -60% -60% Q/Pn| Value of Q/Pn at point (U5,Q5) on the Q(U) mode curve
V5| 0-110% VRated| Grid voltage limit at point (U5,Q5) on the Q(U) mode curve
Q6| -60% -60% Q/Pn| Value of Q/Pn at point (U6,Q6) on the Q(U) mode curve
V6| 0-110% VRated| Grid voltage limit at point (U6,Q6) on the Q(U) mode curve
“Q(U)” Mode Parameters Explanation
“Q(P)” Mode
The reactive power output by the inverter is controlled by the active power of
the inverter.
Parameter | Range | Descrption |
---|---|---|
P1 | 0%400% Pn | Value of Q/Pn at point (P1,Q1) on the Q(P) mode curve |
Q1 | -60% -60% Q/Pn | Reactive power value at point (P1,Q1) on the Q(P) mode |
curve
P2| 0%-100% Pn| Value of Q/Pn at point (P2,Q2) on the Q(P) mode curve
Q2| -60% -60% Q/Pn| Reactive power value at point (P2,Q2) on the Q(P) mode
curve
P3| 0%-100% Pn| Value of Q/Pn at point (P3,Q3) on the Q(P) mode curve
Q3| -60% -60% Q/Pn| Reactive power value at point (P3,Q3) on the Q(P) mode
curve
P4| 0%-100% Pn| Value of Q/Pn at point (P4,Q4) on the Q(P) mode curve
Q4| 60% 60% Q/Pn| Reactive power value at point (P4,Q4) on the Q(P) mode curve
P5| 0%-100% Pn| Value of Q/Pn at point (P5,Q5) on the Q(P) mode curve
Q5| -60% -60% Q/Pn| Reactive power value at point (P5,Q5) on the Q(P) mode
curve
P6| 0%-100% Pn| Value of Q/Pn at point (P6,Q6) on the Q(P) mode curve
Q6| -60% -60% Q/Pn| Reactive power value at point (P6,Q6) on the Q(P) mode
curve
“Q(P)” Mode Parameters Explanation
“PU” Mode
The active power output of the inverter varies in response to the grid
voltage
Parameter | Range | Description |
---|---|---|
P1 | 0%-110% Pn | Value of P/Pn at point (P1,U1) on the PU mode curve |
Ul | 0% -150% Vref | Grid voltage limit at point (P1,U1) on the PU mode curve |
P2 | 0%-110% Pn | Value of P/Pn at point (P2,U2) on the PU mode curve |
U2 | -0% 150% Vref | Grid voltage limit at point (P2,U2) on the PU mode curve |
P3 | 0%-110% Pn | Value of P/Pn at point (P3,U3) on the PU mode curve |
U3 | 0% -150% Vref | Grid voltage limit at point (P3,U3) on the PU mode curve |
P4 | 0%-110% Pn | Value of P/Pn at point (P4,U4) on the PU mode curve |
U4 | 0% -150% Vref | Grid voltage limit at point (P4,U4) on the PU mode curve |
“PU” Mode Parameters Explanation
“PF(P)” Mode
Parameter | Range | Description |
---|---|---|
P1 | 0-110% Pn | Power value at point (PF1,P1) on the PF(P) Curve |
PF1 | 0.8 leading – 0.8 lagging | PF value at point (PF1,P1) on the PF(P) Curve |
P2 | 0-110% Pn | Power value at point (PF2,P2) on the PF(P) Curve |
PF2 | 0.8 leading – 0.8 lagging | PF value at point (P2,PF2) on the PF(P) Curve |
P3 | 0-110% Pn | Power value at point (P3,PF3) on the PF(P) Curve |
PF3 | 0.8 leading – 0.8 lagging | PF value at point (P3,PF3) on the PF(P) Curve |
P4 | 0-110% Pn | Power value at point (P4,PF4) on the PF(P) Curve |
PF4 | 0.8 leading – 0.8 lagging | PF value at point (P4,PF4) on the PF(P) Curve |
P5 | 0-110% Pn | Power value at point (P5,PF5) on the PF(P) Curve |
PF5 | 0.8 leading – 0.8 lagging | PF value at point (P5,PF5) on the PF(P) Curve |
P6 | 0-110% Pn | Power value at point (P6,PF6) on the PF(P) Curve |
PF6 | 0.8 leading – 0.8 lagging | PF value at point (P6,PF6) on the PF(P) Curve |
RMpTime | 0-1000s | The time of the PFF Curve in seconds (time to accomplish a |
change of 95%).
8.5.3 Protect Param
Warning:
Engineer only.
|
---|---
|
8.5.4 Comm. Param
Repair and Maintenance
String type inverter doesn’t need regular maintenance. However, debris or dust will affect heat sink’s thermal performance. It is better to clean it with a soft brush. If the surface is too dirty and affect the reading of LCD and LED lamp, you can use wet cloth to clean it up.
High Temperature Hazard:
When the device is running, the local temperature is too high and the touch
can cause burns. Turn off the inverter and wait for it cooling, then you can
clean and maintain.
Safety Hint:
No solvent, abrasive materials or corrosive materials can be used for cleaning
any parts of the inverter.
Error information and processing
Inverter has been designed in accordance with international grid tied standards for safety, and electromagnetic compatibility requirements. Before delivering to the customer the inverter has been subjected to several tests to ensure its optimal operation and reliability.
10.1 Error code
If there is any failure,the LCD screen will display an alarm message. In this
case, the inverter may stop feeding energy into the grid. The alarm
description and their corresponding alarm messages are listed Table 10.1.
Error code | Description | Ongrid – Three Phase |
---|---|---|
F01 | DC input polarity reverse fault | Check the PV input polarity. |
F02 | DC insulation impedance permanent fault | Check the grounding cable of |
inverter.
F03| DC leakage current fault| Hardly appear the code. Never ever happened so
far.
F04| Ground fault GFDI| Check the solar panel output connection.
F05| Read the memory error| Failure in reading memory (EEPROM). Restart the
inverter if the fault still exists, contact your installer or Deye service.
F06| Write the memory error| Failure in writing memory (EEPROM). Restart the
inverter if the fault still exists, contact your installer or Deye service.
F07| GFDI blown fuse| Hardly appear the code. Never ever happened so far.
F08| GFDI grounding touch failure| Hardly appear the code. Never ever happened
so far.
F09| IGBT damaged by excessive drop voltage| Hardly appear the code. Never
ever happened so far.
F10| Auxiliary switch power supply failure| 1. It tells the DC 12V is not
existed.
2. Restart the inverter, if the fault still exists, please contact your
installer.
F11| AC main contactor errors| Hardly appear the code. Never ever happened so
far.
F12| AC auxiliary contactor errors| Hardly appear the code. Never ever
happened so far.
F13| reserved| 1. Loss of one phase or AC voltage detection part failure or
relays not closed.
2. Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F14| DC firmware over current| Hardly appear the code. Never ever happened so
far.
F15| AC firmware over current| 1. The internal AC sensor or detection circuit
on control board or connection wire may loose.
2. Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F16
| GFCI(RCD) Ac leakage current fault| 1. This fault means the average leakage
current is over 300mA. Check whether DC power supply or solar panels is ok,
then check ‘Test data’-> ‘diL’value is about 40; Then check the leakage
current sensor or circuit (the following picture). Checking test data needs
using big LCD.
2. Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F17| Three phase current, over-current fault| Hardly appear the code. Never
ever happened so far.
F18| AC over current fault of hardware| 1. Check AC sensor or detection
circuit on control board or connection wire.
2. Restart the inverter or factory reset, if the error still exists, please
contact your installer or Deye service.
F19| All hardware failure synthesis| Hardly appear the code. Never ever
happened so far.
F20| DC over current fault of the hardware| 1. Check whether solar panel
output current is within the allowed range.
2. Check DC current sensor and its detection circuit.
3. Check if the inverter FW version is suitable for the hardware.
4. Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F21| DC leakage flow fault| Hardly appear the code. Never ever happened so
far.
F22| Crash stop (if there is a stop button)| Contact your installer for help.
F23| AC leakage current is transient over current| 1. This fault means the
leakage current is above 30mA suddenly. Check whether DC power supply or solar
panels is ok, then check ‘Test data’-> ‘diL’value is about 40; Then check the
leakage current sensor or circuit. Check test data needs using big LCD.”
2. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F24| DC insulation impedance failure| 1. Check Vpe resistance on main board
or detection on control board. Check PV panels is OK. Many times this issue is
the PV problem.
2. Check whether the PV panel (aluminum frame) is grounded well and inverter
is grounded well. Open the cover of inverter and then check the inside ground
cable is fixed well on the shell.
3. Check if the AC/DC cable, terminal block are shorted to ground or the
insulation is damaged.
4. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F25| DC feedback fault| Hardly appear the code. Never ever happened so far.
F26| The DC busbar is unbalanced| 1. Check whether the ‘BUSN’ cable or driver
board power supply cable is loose.
2. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F27| DC end insulation error| Hardly appear the code. Never ever happened so
far.
F28| Inverter 1 DC high fault| Hardly appear the code. Never ever happened so
far.
F29| AC load switch failure| Hardly appear the code. Never ever happened so
far.
F30| AC main contactor failure| 1. Check relays and AC voltage of relays.
2. Check relays driver circuit. Check if the software is not suitable for
this inverter. (Old inverter not have relays detection function)
3. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F31| Relay open circuit fault| 1. At least one Relay can’t be closed. Check
relays and its driver signal. (Old inverter not have relays detection
function)
2. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F32| Inverter 2 dc high fault| Hardly appear the code. Never ever happened so
far.
F33| AC over current| Hardly appear the code. Never ever happened so far.
F34| AC current over load| Hardly appear the code. Never ever happened so far.
F35| No AC grid| 1. Check AC grid voltage. Check AC voltage detection
circuit. Check if the AC connector in good condition. Check whether the AC
grid is normal in voltage.
2. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F36| AC grid phase error| Hardly appear the code. Never ever happened so far.
F37| AC three-phase voltage unbalance failure| Hardly appear the code. Never
ever happened so far.
F38| AC three-phase current unbalance failure| Hardly appear the code. Never
ever happened so far.
F39| AC over current(one cycle)| 1. Check AC current sensor and its circuit.
2. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F40| DC over current| Hardly appear the code. Never ever happened so far.
F41| AC Line W,U over voltage| Check the AC voltage protection setting. And
Check if the AC cable is too thin.Check the voltage difference between LCD and
meter.
F42| AC Line W,U low voltage| Check the AC voltage protection setting. Check
the voltage difference between LCD and meter. Also need to check whether AC
cables are all firmly and correctly connected.
F43| AC Line V,W over voltage| Check the AC voltage protection setting.And
Check if the AC cable is too thin.Check the voltage difference between LCD and
meter.
F44| AC Line V,W low voltage| Check the AC voltage protection setting. Check
the voltage difference between LCD and meter. Also need to check whether AC
cables are all firmly and correctly connected.
F45| AC Line U,V over voltage| Check the AC voltage protection setting.And
Check if the AC cable is too thin.Check the voltage difference between LCD and
meter.
F46| AC Line U,V low voltage| Check the AC voltage protection setting.
F47| AC Over frequency| Check the frequency protection setting.
F48| AC lower frequency| Check the frequency protection setting.
F49| U phase grid current DC component over current| Hardly appear the code.
Never ever happened so far.
F50| V phase grid current DC component over current| Hardly appear the code.
Never ever happened so far.
F51| W phase grid current DC component over current| Hardly appear the code.
Never ever happened so far.
F52| AC inductor A, phase current DC current high| Hardly appear the code.
Never ever happened so far.
F53| AC inductor B, phase current DC current high| Hardly appear the code.
Never ever happened so far.
F54| AC inductor C, phase current DC current high| Hardly appear the code.
Never ever happened so far.
F55| DC busbar voltage is too high| 1. Check PV voltage and Ubus voltage and
its detection circuit. If the PV input voltage exceeds the limit, please
reduce the number of solar panels in series.
2. For Ubus voltage, please check the LCD display.
F56| DC busbar voltage is too low| 1. It tells the PV input voltage is low
and it always happens in the early morning.
2. Check PV voltage and Ubus voltage. When inverter is running, then showing
F56, maybe Loss of driver or need update firmware.
3. Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F57| AC reverse irrigation| AC reverse irrigation.
F58| AC grid U over current| Hardly appear the code. Never ever happened so
far.
F59| AC grid V over current| Hardly appear the code. Never ever happened so
far.
F60| AC grid W over current| Hardly appear the code. Never ever happened so
far.
F61| Reactor A phase over current| Hardly appear the code. Never ever happened
so far.
F62| Reactor B phase over current| Hardly appear the code. Never ever happened
so far.
F63| ARC fault| 1. Check PV module cable connection and clear the fault;
2. Seek help from us, if can not go back to normal state.
F64| IGBT heat sink high temperature| 1. Check temperature sensor. Check if
firmware is suitable for the hardware. Check if the inverter is its right
model.
2. Restart the inverter, if the fault still exists, contact your installer.
Table10.1 Error codes and their solutions
Safety Hint:
If your string inverter has any of the fault information shown in Table 10-1,
and when you reset the machine and still don’t solve the problem, please
contact our distributor and provide the below details:
- Serial number of the inverter;
- The distributor/dealer of the inverter(if available);
- Installation date;
- The discription of problem(include LCD’error code and LED starus indicator lights);
- Your contact details.
Specification
Model| SU-NEU-6-OAKM-8G-OL1VP3| SU-NEU-7-OAKM-8G-OL1VP3|
SUN-E-U75-AKM-G8O-L1VP3
---|---|---|---
Input Side
Max.DC Power(kW)| 90kW| 105kW| 112.5kW
Max.DC Input Voltage(V)| 800V
Start-up DC Input Voltage(V)| 250V
MPPT Operating Range(V)| 200V-700V
Rated DC input voltage(V)| 500V
MPPT Full Power Voltage Range(V)| 290V-700V| 330V-700V| 360V-700V
Max.DC Input Current(A)| 40A+40A+40A+40A+40A+40A+40A+40A
Max. Short Circuit Current (A)| 60A+60A+60A+60A+60A+60A+60A+60A
Number of MPPT/Strings per MPPT| 8/4+4+4+4+4+4+4+4
MAX inverter backfeed current (A)| 0
Output Side
Rated Output Power(kW)| 60kW| 70kW| 75kW
Max.Active Power(kW)| 60kW| 70kW| 75kW
Rated AC Grid Voltage(V)| 3L/N/PE 127V/220V,133V/230V
AC Grid Voltage Range(V)| 0.85Un-1.1Un (this may vary with grid standards)
Rated Grid Frequency(Hz)| 50/60 (Optional)
Operating Phase| Three phase
Rated AC Grid Output Current(A)| 157.5/150.4A| 183.8/175.5A| 196.9/188.0A
x.AC Output Current(A)| 157.5/150.4A| 183.8/175.5A| 196.9/188.0A
Maximum output fault
Mcuarxriemntu(ma.co.uAtp, puet aokve) rcurrent| 300.6A| 350.9A| 375.9A
OpruottpeucttiPoonw(ae.rcF. aAc,ptoerak)| 334.1A| 389.8A| 417.6A
Grid Current THD| 0.8 leading to 0.8 lagging
DC Injection Current| <3% <0.5%
Grid Frequency Range| 45-55 or 55-65 (Optional)
Efficiency
Max.Efficiency| 98.7%
Euro Efficiency| 98.3%
MPPT Efficiency| >99%
General Data
Cabinet Size(WHD) [mm]| 1006W×516H×325.5D (Excluding connectors and
brackets)
Weight(kg)| 103kg
Topology| Transformerless
Internal consumption| <1W (Night)
Operating temperature| -25 to +60℃,>45℃ derating
Ingress protection| IP65
Noise Emission(Typical)| ≤55dB
Cooling Concept| Smart cooling
Permissible Altitude (m)| 4000m
Warranty [year]| Standard 5 years, extended warranty
Grid Connection Standard| NBR 16149, NBR 16150, EN 50549, RD 140
Safety EMC / Standard| IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
General Data
Display| LCD 240 x 160
Interface| RS485/RS232/Wifi/LAN
Protective Class| Class I
Over Voltage Category| III (AC), II (DC)
Inverter Topology| Non-is olated
Pollution degree| PD2(Inside), PD3(Outside)
EU Declaration of Conformity
within the scope of the EU directives ****
- Electromagnetic compatibility 2014/30/EU (EMC)
- Low Voltage Directive 2014/35/EU (LVD)
- Restriction of the use of certain hazardous substances 2011/65/EU(RoHS)
NINGBO DEYE INVERTER TECHNOLOGY CO.,LTD. confirms herewith that the products
described in this document are in compliance with the fundamental requirements
and other relevant provisions of the above mentioned directives. The entire EU
Declaration of Conformity and certificate can be found at
https://www.deyeinverter.com/download/#string-inverter.
231018001
www.deyeinverter.com
EU Declaration of Conformity
Product: Grid-connected PV Inverter
Models: SUN-120K-G01P3-EU-AM8-HV:SUN-125K-G01P3-EU-AM8-HV;SUN-130K-G01P3-EU-
AM8-HV:
SUN-135K-G01P3-EU-AM8-HV;SUN-136K-G01P3-EU-AM8-HV;
SUN-120K-G01P3-EU-AM8;SUN-125K-G01P3-EU-AM8;SUN-130K-G01P3-EU-AM8;
SUN-135K-G01P3-EU-AM8;SUN-136K-G01P3-EU-AM8;SUN -60K-G01P3-EU-AM8-LV;
SUN- 70K-G01P3-EU-AM8-LV;SUN-75K-G01P3-EU-AM8-LV;
Name and address of the manufacturer: Ningbo Deye Inverter Technology Co.,
Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China
This declaration of conformity is issued under the sole responsibility of the
manufacturer. Also this product is under manufacturer’s warranty.
This declaration of conformity is not valid any longer: if the product is
modified, supplemented or changed in any other way, as well as in case the
product is used or installed improperly.
The object of the declaration described above is in conformity with the
relevant Union harmonization legislation:
The Low Voltage Directive (LVD) 2014/35/EU;the Electromagnetic Compatibility
(EMC) Directive 2014/30/EU:the restriction of the use of certain hazardous
substances (ROHS) Directive 2011/65/EU.
References to the relevant harmonized standards used or references to the
other technical specifications in relation to which conformity is declared:
LVD:|
---|---
EN 62109-1:2010| •
EN 62109-2:2011| •
EMC:|
EN IEC 61000-6-1:2019| •
EN IEC 61000-6-2:2019| •
EN IEC 61000-6-3:2021| •
EN IEC 61000-6-4:2019| •
EN IEC 61000-3-2:2019+A1:2021| •
EN 61000-3-3:2013/A2:2021/AC:2022-01| •
EN IEC 61000-3-11:2019| •
EN 61000-3-12:2011| •
EN 55011:2016/A2:2021| •
Nom et Titre / Name and Title:
Au nom de / On behalf of:
Date / Date (yyyy-mm-dd):
A / Place :
EU DoC – v1
Bard Dai
Senior Standard and Certification Engineer
Ningbo Deye Inverter Technology Co., Ltd.
2023-10-18
Ningbo, China
Ningbo Deye Inverter Technology Co., Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China
NINGBO DEYE INVERTER TECHNOLOGY CO., LTD.
Add. : No.26 South YongJiang Road, Daqi, Beilun, NingBo, China.
Tel.: +86 (0) 574 8622 8957
Fax.: +86 (0) 574 8622 8852
E-mail.:service@deye.com.cn
Web.:www.deyeinverter.com
References
- マックスサーバ... CGI、PHP、ASP、フロントページ対応...安心と快適のウェブホスティング!
- Solar Grid-Tie Inverter Manufacturers, PV On-Grid Inverter | Deye
- home.solarmanpv.com
- pro.solarmanpv.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>