Important Safety Instructions

This manual contains important instructions to follow during installation and maintenance of the Photovoltaic Grid-connected Inverter(Microinverter).To reduce the risk of electrical shock and ensure the safe installation and operation of the Microinverter the following symbols appear throughout this document to indicate dangerous conditions and important safety instructions. Specifications subject to change without notice – please ensure you are using the latest manual found at the manufacturer website.

WARNING : This indicates a situation where failure to follow instructions may cause a serious hardware failure or personnel danger if not applied appropriately. Use extreme caution when performing this task.
NOTE : This indicates information that is important for optimized Microinverter operation. Follow these instructions strictly.

CAUTION : IMPORTANT TO READ CAREFULLY AND KEEP FOR EVENTUAL REQUESTS.

Safety Instructions

  • DO NOT disconnect the PV module from the Microinverter without disconnecting the AC power.
  • Only qualified professionals should install and/or replace the Microinverters.
  • Perform all electrical installations in accordance with local electrical codes.
  • Before installing or using the Microinverter, please read all instructions and cautionary markings in the technical documents and on the Microinverter system and the solar-array.
  • Be aware that the body of the Microinverter is the heat sink and can reach a temperature of 80℃. To reduce risk of burns,do not touch the body of the Microinverter.
  • When the Microinverter is working properly, please maintain a distance of at least 20cm from it.
  • DO NOT attempt to repair the Microinverter. If it fails, contact technical support to obtain an RMA number and start the replacement process. Damaging or opening the Microinverter will void the warranty.
  • Caution! The external protective earthing conductor is connected to the inverter protective earthing terminal through AC connector.
  • When connecting, connect the AC connector first to ensure the inverter earthing then do the DC connections.
  • When disconnecting, disconnect the AC by opening the branch circuit breaker first but maintain the protective earthing conductor in the branch circuit breaker connect to the inverter ,then disconnect the DC inputs.
  • In any circumstance, do not connect DC input when AC connector is unplugged.
  • Please install isolation switching devices on the AC side of the inverter.

Radio Interference Statement

The equipment could radiate radio frequency energy and this might cause harmful interference to radio communications if not following the instructions when installing and using the equipment. But there is no guarantee that interference will not occur in a particular installation. If this equipment causes harmful interference to radio or television reception,the following measures might resolve the issues:

  • A) Relocate the receiving antenna and keep it well away from the equipment.
  • B) Consult the dealer or an experienced radio / TV technical for help. Changes or modifications not expressly approved by the party responsible for compliance may void the user’s authority to operate the equipment.
  • WiFi information
  • Frequency range:2.412-2.472GHz
  • WiFi maximum transmitting power:16dBm ± 2dBm
  • Antenna: External Antenna
  • Antenna Gain:3.00dBi

Microinverter System Introduction
The Microinverter is used in utility-interactive grid-tied applications, comprised of two key elements:

  • Microinverter
  • Router
    This series Microinverter has built-in WIFI module so it can communicate with router directly.

30 / 35 / 40 / 45 / 50 G4

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
1

Inverter Model| SUN-M30G4
-EU-Q0| SUN-M35G4
-EU-Q0| SUN-M40G4
-EU-Q0| SUN-M45G4
-EU-Q0| SUN-M50G4
-EU-Q0
---|---|---|---|---|---
PV Input Voltage| 42.5V (20V-60V)
PV Array MPPT Voltage Range| 25V-55V
No. of MPP Trackers| 1
No. of Strings per MPP Tracker| 1

NOTE : If the wireless signal in the area where the Microinverter is installed is weak, it is necessary to add a wifi signal booster at a suitable place between the router and the Microinverter.

This integrated system improves safety; maximizes solar energy harvest; increases system reliability, and simplifies solar system design, installation, maintenance, and management.

Microinverter Maximize PV Energy Production
Each PV module has individual Maximum Peak Power Tracking (MPPT) controls, which ensures that the maximum power is exported to the utility grid regardless of the performance of the other PV modules in the array. When PV modules in the array are affected by shade, dust, orientation,or any situation in which one module underperforms compared with the other units, the Microinverter ensures top performance from the array by maximizing the performance of each module within the array.

More Reliable than Centralized or String Inverters
The distributed Microinverter system ensures that no single point of system failure exists across the PV system.Microinverters are designed to operate at full power at ambient outdoor temperatures of up to 113℉ (45℃). The inverter housing is designed for outdoor installation and complies with the IP67 environmental enclosure rating.

Simple to Install
You can install individual PV modules in any combination of Module quantity, orientation, different type and power rate. The Ground wire (PE) of the AC cable is connected to the chassis inside of the Microinverter, potentially eliminating the installation of grounding wire (check local regulation). Data collection adopts internal wifi, wireless router is needed near the Microinverter. When complete the installation of the Microinverter, configure wireless router with internal wifi (refer to the wifi user manual). The data will be uploaded automatically. Users can monitor and manage the Microinverter through corresponding website or APP.

Microinverter Introduction
The Microinverters connect with the single-phase grid, and can also use multiple Microinverters in the form of single-phase grid to achieve three- phase grid. For more information, please see the Technical Data page (P16-P19) of this manual.

Microinverter System Installation
A PV system using Microinverters is simple to install. Each Microinverter easily mounts on the PV racking, directly beneath the PV module(s). Low voltage DC wires connect from the PV module directly to the Microinverter, eliminating the risk of high DC voltage. Installation MUST comply with local regulations and technical rules.

  • WARNING : Perform all electrical installations in accordance with local electrical codes.
  • WARNING : Be aware that only qualified professionals should install and/or replace Microinverters.
  • WARNING : Before installing or using an Microinverter,please read all instructions and warnings in the technical documents and on the Microinverter system itself as well as on the PV array.
  • WARNING : Be aware that installation of this equipment includes the risk of electric shock.
  • NOTE : Strongly recommend to install Surge protection Devices in the dedicated meter box.
  • NOTE : The product is suitable for residential, commercial and light industrial environments, not for industrial environments.

Required Parts and Tools from you
In addition to your PV array and its associated hardware, you will need the following items:

  • An or several AC connection junction boxes
  • Mounting hardware suitable for module racking
  • Sockets and wrenches for mounting hardware
  • Continuous grounding conductor and grounding washers
  • A Phillips screwdriver
  • A torque wrench

Parts list
Please check the following table, to see whether all the parts are included in the package:

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
2

Choose either Bus AC connector or Extension cable with European standard plug, can’t use them in the same project.

Installation Procedures

Step 1 – Install the AC branch circuit junction box

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
3

  • a. Install an appropriate junction box at a suitable location on the PV racking system (typically at the end of a branch of modules).
  • b. Connect the open wire end of the AC cable into the junction box using an appropriate gland or strain relief fitting.
  • c. Connect the AC branch circuit junction box to the point of utility Grid Interconnection (Usually it is inside a distribution box).

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
4

WARNING : Wiring colour code can be different according local regulation,check all the wires of the installation before connecting to the AC cable to be sure they match. Wrong cabling can damage irreparably the Microinverters,such an issue is not covered by the warranty.

Step 2 – Attach the Microinverters to the racking or the PV module frame

  • a. Mark the location of the Microinverters on the rack, with respect to the PV module and junction box or any other obstructions.
  • b. Mount one Microinverter at each of these locations using hardware recommended by your module racking vendor.

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
5

The AC wire on the Microinverter is a TC-ER wire with a wire cross-section area of 1mm²(18AWG).

WARNING : Prior to installing any of the Microinverters, verify that the utility voltage at the point of common connection matches the voltage rating on Microinverter label.
WARNING : Do not place the inverters (including DC and AC connectors) where exposed to the sun, rain or snow, even gap between modules.Allow a minimum of 3/4 (1.5cm.) between the roof and the bottom of the Microinverter to allow proper air flow.

Step 3 – Connect the Microinverters in parallel

  • a. Check the Microinverter technical data page ? for the maximum allowable number of Microinverters on each AC branch circuit.
  • b. As to parallel connection, please refer to page (P??-P??), use the T-connector, AC extension cable, Bus AC connector(If only one branch, just use the Extension cable with European standard plug) to connect the Microinverter in each branch.

Model| Wire Size| 2

Cable(mm)

| Torque value(max)| Max cable length
---|---|---|---|---
SUN-M30G4-EU-Q0| 12AWG| 2.5| 1.0Nm|

Outside cable (L+N+PE)20m

SUN-M35G4-EU-Q0| 12AWG| 2.5| 1.0Nm
SUN-M40G4-EU-Q0| 12AWG| 2.5| 1.0Nm
SUN-M45G4-EU-Q0| 12AWG| 2.5| 1.0Nm
SUN-M50G4-EU-Q0| 12AWG| 2.5| 1.0Nm

WARNING : DO NOT exceed maximum number of Microinverters in an AC branch circuit, as displayed on the page 6 of this manual.

NOTE : Port marked with two-way arrow on T-type plug can only connect with extended cable and Port marked with one-way arrow on T-type plug can only connect with the Microinverter.

Step 4 – Connect the wire open of branch end to the junction box.

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
8

Step 5 – Connect Microinverters to the PV Modules

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
9

General Guidelines:

  • a. PV modules should be connected to DC input ports of a Microinverter.
  • b. In order to meet the relevant regulatory requirements, the cable length must be <3M. Please consult the local power operator to make sure that the DC cable complies with local regulations.

NOTE :When plugging in the DC cables, if AC already available, the Microinverter should immediately blink red light and will start work within the setting time (default 60 seconds). If AC is not available, the red light will blink 3 times quickly and repeat after one second until AC is connected.

Microinverter System Operating Instructions

To operate the Microinverter PV system:

  1. Turn ON the AC circuit breaker on each Microinverter AC branch circuit.
  2. Turn ON the main utility-grid AC circuit breaker. Your system will start producing power after a one-minute waiting time.
  3. The units should start blinking red one minutes after turning on the AC circuit breaker. Then blue led blinking. This means they are producing power normally, the faster blinking of the blue led means more power generated.
  4. Configure the internal wifi module according to its user manual.
  5. The Microinverters will start to send performance data over wifi module to the network every 5 minutes.It enables customers to monitor performance data of each Microinverter through website and APP.

When AC power is applied but the Microinverter not started up, about 0.1A current and 25VA power for each Microinverter may be measured by a power meter. This power is reactive power, not consume from utility grid.

Troubleshooting

Qualified personnel can use the following troubleshooting steps if the PV system does not operate correctly:

Status Indications and Error Reporting

  • Start up LED : One minute after DC power is first applied to the Microinverter,one short red blinks indicate a successful Microinverter startup sequence, be equal or greater than two short red blinks after DC power is first applied to the Microinverter indicate a failure during Microinverter setup.
  • Operation LED:
    • Flashing Slow Blue – Producing small power
    • Flashing Fast Blue – Producing big power
    • Flashing Red – Not producing power
    • Red blinking two times – AC low-voltage or high-voltage
    • Red blinking three times – Grid failure
  • GFDI Error: A four time red LED indicates the Microinverter has detected a Ground Fault Detector Interrupter (GFDI) error in the PV system. Unless the GFDI error has been cleared, the LED will remain four times blinking.
  • Other Faults: All other faults can be reported to the website and APP.
  • WARNING : Never disconnect the DC wire connectors under load. Ensure that no current is flowing in the DC wires prior to disconnecting. An opaque covering may be used to cover the module prior to disconnecting the module.

Troubleshooting a non-operating Microinverter

There are two possible overall areas of trouble:

  • A. The Microinverter itself may be having problems.
  • B. The Microinverter itself is working fine but the communication between Microinverter and network has problem. The items below refer to Microinverter issues, not communication issues:

One quick way to tell whether the issue is the Microinverter or the communication problem:

Diagnosing from the network:

  • a. No-Data-Display: The website and APP don’t display any data.Check the network configuration.
  • b. Only display the Microinverter is online but no data.This maybe because server is updating.

To troubleshoot a non-operating Microinverter, Follow the steps below in order:

  1. Verify the utility voltage and frequency are within ranges shown in the Technical Data section of this manual.
  2. Check the connection to the utility grid. Disconnect AC firstly,then disconnect DC and make sure the utility grid voltage can be measured at AC connector. Never disconnect the DC wires while the Microinverter is producing power. Re-connect the DC module connectors and watch for three short LED flashes.
  3. Check the AC branch circuit interconnection between all the Microinverters. Verify each inverter is energized by the utility grid as described in the previous step.
  4. Make sure that any AC breaker are functioning properly and are closed.
  5. Check the DC connections between the Microinverter and the PV module.
  6. Verify the PV module DC voltage is within the allowable range shown in the Technical Data of this manual.
  7. If the problem still persists, please contact technical support.

WARNING : Do not attempt to repair the Microinverter.If troubleshooting methods fail, please call for Technical Support.

Replacement

Follow the procedure to replace a failed Microinverter

  • A. Disconnect the Microinverter from the PV Module, in the order shown below:
    • Disconnect the AC by turning off the branch circuit breaker.
    • Disconnect the AC connector of the Microinverter.
    • Cover the module with an opaque cover.
    • Disconnect the PV module DC wire connectors from the Microinverter.
    • Remove the Microinverter from the PV array racking.
  • B. Install a replaced Microinverter to the bracket then remove the opaque cover. Remember to observe the flashing LED light as soon as the new Microinverter is plugged into the DC cables.
  • C. Connect the AC cable of the replacement Microinverter.

Technical Data

  • WARNING : Be sure to verify the voltage and current specifications of your PV module match with those of the Microinverter. Please refer to the datasheet or user manual.
  • WARNING : You must match the DC operating voltage range of the PV module with the allowable input voltage range of the Microinverter.
  • WARNING : The maximum open circuit voltage of the PV module must not exceed the specified maximum input voltage of the inverter.

M30G4/35G4/40G4 Microinverter Datasheet

Model SUN-M30G4-EU-Q0 SUN-M35G4-EU-Q0 SUN-M40G4-EU-Q0

PV String Input Data
Max. PV Input Power(W)| 210-420(1 Piece)| 210-490(1 Piece)| 210-560(1 Piece)
Max. PV Input Voltage(V)| 60
Start-up Voltage(V)| 20
MPPT voltage range(V)| 25-55
Full Load MPPT Voltage Range(V)| 30-55| 33-55| 33-55
Rated PV input voltage(V)| 42.5
Max. Input Short-Circuit Current (A)| 19.5
Max. Operating PV Input Current(A)| 13
NStori.nogfsMpPerPMTrPaPckTerrasc/kNeor. of| 1/1
AC Output Side
Rated AC Output Active Power(W)| 300| 350| 400
Max.AC Output Apparent Power(VA)| 300| 350| 400
Rated AC output current (A)| 1.4/1.4| 1.6/1.6| 1.9/1.8
Max.AC Output Current(A)| 1.4/1.4| 1.6/1.6| 1.9/1.8
Max. Output Fault Current(A)| 4
Max. Output Overcurrent Protection (A)| 21
Rated output voltage/range (V)| 220V/230V 0.85Un-1.1Un
Grid Connection Form| L+N+PE
Rated Output Grid Frequency/range(Hz)| 50Hz/45Hz-55Hz 60Hz/55Hz-65Hz
Max. unit per branch| 17| 14| 13
Power Factor Adjustment Range| 0.9leading-0.9lagging/0.95leading-0.95lagging(VDE4105)
Total Current Harmonic Distortion THDi| <3%
DC Injection Current| <0.5%In
Efficiency
Max. Efficiency| 96.5%
Euro Efficiency| 96.0%
MPPT Efficiency| >99%
Equipment Protection
DC Polarity Reverse Connection Protection| yes
AC Output Overcurrent Protection| yes
AC Output Overvoltage Protection| yes
AC Output Short Circuit Protection| yes
Thermal Protection| yes
DC Terminal Insulation Impedance Monitoring| yes
Power Network Monitoring| yes
Island protection monitoring| yes
Earth Fault Detection| yes
Overvoltage Load Drop Protection| yes
Surge Protection Level| TYPE II(AC)

M30G4/35G4/40G4 Microinverter Datasheet

|
---|---
Interface
Communication Interface| WiFi
General Data
Operating Temperature Range (°C)| -40℃to +65℃, >45℃ derating
Permissible Ambient Humidity| 0-100%
Permissible Altitude (m)| 2000m
Noise (dB)| ≤ 25 dB
Ingress Protection(IP) Rating| IP 67
Inverter Topology| Isolated
Over Voltage Category| OVC II(DC),OVC III(AC)
Cabinet Size(WHD)[mm]| 173×158.5×31.5(Excluding connectors and brackets)
Weight [kg]| 1.85
Warranty [year]| Standard 15 years, extended warranty
Type Of Cooling| Natural cooling
Grid Regulation| IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G98, VDE-AR-N 4105
Safety EMC/Standard| IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2

M45G4/50G4 Microinverter Datasheet

| |
---|---|---
PV String Input Data
Max. PV Input Power(W)| 210-630(1 Piece)| 210-700(1 Piece)
Max. PV Input Voltage(V)| 60
Start-up Voltage(V)| 20
MPPT voltage range(V)| 25-55
Full Load MPPT Voltage Range(V)| 40-55
Rated PV input voltage(V)| 42.5
Max. Input Short-Circuit Current (A)| 19.5
Max. Operating PV Input Current(A)| 13
NStori.nogfsMpPerPMTrPaPckTerrasc/kNeor. of| 1/1
AC Output Side
Rated AC Output Active Power(W)| 450| 500
Max.AC Output Apparent Power(VA)| 450| 500
Rated AC output current (A)| 2.1/2.0| 2.3/2.2
Max.AC Output Current(A)| 2.1/2.0| 2.3/2.2
Max. Output Fault Current(A)| 4
Max. Output Overcurrent Protection (A)| 21
Rated output voltage/range (V)

Grid Connection Form

| 220V/230V 0.85Un-1.1Un
 | L+N+PE
Rated Output Grid Frequency/range(Hz)| 50Hz/45Hz-55Hz 60Hz/55Hz-65Hz
Max. unit per branch| 11| 10
Power Factor Adjustment Range| 0.9leading-0.9lagging/0.95leading-0.95lagging(VDE4105)
Total Current Harmonic Distortion THDi| <3%
DC Injection Current| <0.5%In
Efficiency
Max. Efficiency| 96.5%
Euro Efficiency| 96.0%
MPPT Efficiency| >99%
Equipment Protection
DC Polarity Reverse Connection Protection| yes
AC Output Overcurrent Protection| yes
AC Output Overvoltage Protection| yes
AC Output Short Circuit Protection| yes
Thermal Protection| yes
DC Terminal Insulation Impedance Monitoring| yes
Power Network Monitoring| yes
Island protection monitoring| yes
Earth Fault Detection| yes
Overvoltage Load Drop Protection| yes
Surge Protection Level| TYPE II(AC)

M45G4/50G4 Microinverter Datasheet


Interface
Communication Interface| WiFi
General Data
Operating Temperature Range (°C)| -40℃to +65℃, >45℃ derating
Permissible Ambient Humidity| 0-100%
Permissible Altitude (m)| 2000m
Noise (dB)| ≤ 25 dB
Ingress Protection(IP) Rating| IP 67
Inverter Topology| Isolated
Over Voltage Category| OVC II(DC),OVC III(AC)
Cabinet Size(WHD)[mm]| 173×158.5×31.5(Excluding connectors and brackets)
Weight [kg]| 1.85
Warranty [year]| Standard 15 years, extended warranty
Type Of Cooling| Natural cooling
Grid Regulation| IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G98, VDE-AR-N 4105
Safety EMC/Standard| IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2

Wiring Diagram

Sample Wiring Diagram Three PhaseDeye Inverter SUN-M30G4 Photovoltaic
Grid Connected Microinverter 10

Sample Wiring Diagram Single Phase

Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
11

Monitoring Platform

This series Microinverter has built-in WIFI modular which is able to connect router directly. For WIFI configuration, please check the manual of“ Built-in WIFI modular Microinverter WIFI configuration Manual”.

Web monitoring address : https://pro.solarmanpv.com ; (for Solarman distributor account)
https://home.solarmanpv.com (for Solarman end user account)

For mobile phone monitoring system, scan the QR code to download the APP. Also you can find it by searching“ solarman business” in App store or Google Play store, and this App is for distributor/installer. Find it by searching“ solarman smart” in App store or Google Play store and choose “ solarman smart”, this app is for plant owner.Deye Inverter SUN-M30G4 Photovoltaic
Grid Connected Microinverter 12

How to connect the Microinverter to the router via web

  1. Turn on the wireless network of your PC or smartphone.

  2. The default password of the AP network is 12345678 if there’s no nameplate that includes

    • PWD:XXXXXXXX on the inverter body. If there’s nameplate that includes
    • PWD:XXXXXXXX on the inverter body then the AP network password is the“ XXXXX
    • XXX”: for example, the default password of AP network is“ 5c4db4d8” of the inverter
    • SN: 2302202012.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter 13
    • Also, the default password can be changed. If forgetting the modified password, please contact [email protected] for help.
  3. Open a browser and enter . Both username and password are “admin”.
    (Recommended browser: IE 8+, Chrome 15+, Firefox 10+ ).Deye Inverter SUN-
M30G4 Photovoltaic Grid Connected Microinverter 14

  4. Browser jumps to“ Status ” page, the basic information is listed there.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter 15

  5. Turn to “Wizard” page, click “Refresh” to search the wireless network. Select the target network and click “Next”.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter 16

  6. Enter the password and click Next.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter 17

  7. Users can select any options below to enhance the security and click Next.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter 18

  8. If the setup is successful, the following page will pop up and click OK to reboot the Microinverter.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter 19

  9. Connect to loggeer AP network again, then log in to 10.10.100.254 by Browser, and check the system info of “Status” page. After the network setting is done, the remote server A or B should be “connected”.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter 20

  10. When it shows “connected” which means this Microinverter has connected solarman platform successfully. Generally speaking, it will be online after ??-??min after configuration successfully at the first time.

How to connect in APP

  1. Registration
    Open the app of SOLARMAN Smart and register an account. Click “Register” and create your account here.Deye Inverter SUN-M30G4 Photovoltaic Grid Connected
Microinverter 21

  2. Create a Plant
    Click “Add Now” to create your plant.
    Please fill in plant basic info and other info here.Deye Inverter SUN-M30G4
Photovoltaic Grid Connected Microinverter 22

  3. Add a Logger
    Optional 1: Enter the logger SN manually.
    Optional 2: Click the icon in the right and scan the QR code to enter logger SN.
    You can find logger SN on the carton packaging or on the logger body.Deye
Inverter SUN-M30G4 Photovoltaic Grid Connected Microinverter
23

  4. Network Configuration
    After the logger is added, please configure the network to ensure normal operation. Go to “Plant Details”-“Device List”, find the target SN and click ” Device Networking”. If showing”online” which means the datalogger of the inverter connects the solarman platform successfully. Then you will be able to check the plant info on the platform.

Maintenance

Deye microinverters do not require any specific regular maintenance.

Troubleshooting
If you have any question you can’t handle during using Deye products,please contact with our after services by email: [email protected] , details can refer to products’ warranty.

EU Declaration of Conformity
within the scope of the EU directives

  • Radio Equipment Directive 2014/53/EU (RED)
  • Restriction of the use of certain hazardous substances 2011/65/EU)(RoHS) NINGBO DEYE INVERTER TECHNOLOGY CO., LTD. confirms herewith that the products described in this document are in compliance with the fundamental requirements and other relevant provisions of the above mentioned directives. The entire EU Declaration of Conformity and certificate can be found at https://www.deyeinverter.com/download/#microinverter.

EU Declaration of Conformity
Product : Utility-Interactive Inverter
Models : SUN-M30G4-EU-Q0; SUN-M35G4-EU-Q0; SUN-M40G4-EU-Q0;
SUN-M45G4-EU-Q0;SUN-M50G4-EU-Q0;
Name and address of the manufacturer: Ningbo Deye Inverter Technology Co., Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China

This declaration of conformity is issued under the sole responsibility of the manufacturer. Also this product is under manufacturer’s warranty. This declaration of conformity is not valid any longer: if the product is modified, supplemented or changed in any other way, as well as in case the product is used or installed improperly. The object of the declaration described above is in conformity with the relevant Union harmonization legislation: The restriction of the use of certain hazardous substances (RoHS) Directive 2011/65/EU and the Radio Equipment Directive (RED) 2014/53/EU. References to the relevant harmonized standards used or references to the other technical specifications in relation to which conformity is declared:

  • EN 62109-1:2010
  • EN 62109-2:2011
  • EN 300328 V 2.2.2:2019
  • EN 301489-1 V 2.2.3:2019
  • EN 301489-17 V 3.2.4:2020
  • EN 55011:2016+A1+A11+A2
  • EN 62920:2017+A11+A1
  • EN IEC 61000-6-1:2019
  • EN IEC 61000-6-2:2019
  • EN IEC 61000-6-3:2021
  • EN IEC 61000-6-4:2019
  • EN IEC 62311:2020
  • CISPR 11:2015+A1+A2

NINGBO DEYE INVERTER TECHNOLOGY CO., LTD.
Add.: No.26 South YongJiang Road, Daqi, Beilun, NingBo, China.
Tel.: +86 (0) 574 8622 8957
Fax.: +86 (0) 574 8622 8852
E-mail:[email protected]
Web.:www.deyeinverter.com