Elimko E-48P Series Universal Advanced Digital Controllers User Guide
- June 15, 2024
- Elimko
Table of Contents
- Elimko E-48P Series Universal Advanced Digital Controllers
- Product Information
- Product Usage Instructions
- DESCRIPTION
- DIMENSIONS and PANEL CUT-OUT
- CONNECTION DIAGRAM
- PRECAUTIONS
- TYPE CODING
- TECHNICAL SPECIFICATIONS
- PARAMETER TABLE
- ACCESSING PARAMETERS
- APPLICATION EXAMPLES
- Contact
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Elimko E-48P Series Universal Advanced Digital Controllers
Product Information
Specifications
- Model: KY-48P-1123-1
- Input Types: Thermocouple / miliVolt 0-20 mA / 4-20 mA, Resistance Thermometer 2-Wire Transmitter Volt
- Dimensions: 48×48 mm
- Display Range: -1999 to 9999
- Analog Output: mA or 0-10 V DC
- Operating Voltage: 85-265 V AC / 85-375 V DC
- Compliance: Low Voltage Directive EN 61010-1, EMC Directive EN 61326-1
FAQ
- Q: What are the dimensions of the E-48P controller?
- A: The dimensions of the E-48P controller are 48×48 mm.
- Q: What is the operating voltage range for the E-48P controller?
- A: The operating voltage range for the E-48P controller is 85-265 V AC / 85-375 V DC.
- Q: Can I clean the controller with alcohol or solvents?
- A: No, do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
Product Usage Instructions
Installation
- The E-48P controller is designed for panel mounting and should be used in an industrial environment. Before installing and operating the controller, please read the user manual thoroughly.
- The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
- Keep the unit away from flammable gases that could cause an explosion.
Cleaning
- Do not use alcohol or other solvents to clean the controller.
- Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
Limitations
- The E-48P controller is not to be used in medical applications.
EU Directive Compliance
The E-48P controller complies with the following EU directives:
- Low Voltage Directive EN 61010-1
- EMC Directive EN 61326-1
DESCRIPTION
- E-48P Series universal process controllers are industrial devices at 48×48 mm IEC/TR 60668 dimensions designed using new generation microcontrollers with on/off, PID and other control forms, where inputs and outputs can be easily programmed by0 the user.
- In E-48P Series controllers, the set value and measured value can be displayed from -1999 to 9999 on two 4-digit displays; general purpose inputs (T/C, R/T, mV, mA) can be programmed.
DIMENSIONS and PANEL CUT-OUT
CONNECTION DIAGRAM
Warning: Operating voltage suitable for the device type shall be applied.
- 1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2).
- Only one of analog output (AO1) and RS-485 can be selected.
- Analog output (AO1) mA or 0-10 V DC can be selected.
Analog Input
PRECAUTIONS
WARNINGS
E-48P controller is designed for panel mounting and should be used in an industrial environment.
- The package of E-48P controller contains; Controller, 2 pieces of mounting clamps, User manual and Guarantee certificate.
- After opening the package, please check the contents with the above list. If the delivered product is wrong type, any item is missing or there are visible defects, contact the vendor from which you purchased the product.
- Before installing and operating the controller, please read the user manual thoroughly.
- The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
- Keep the unit away from flamable gases, that could cause explosion.
- Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
- It is not used in medical applications.
EU DIRECTIVE COMPLIANCE
- Low Voltage Directive EN 61010-1
- EMC Directive EN 61326-1
TYPE CODING
- Only one of the analog output and RS-485 options can be coded. For example, only one of the options (X) and (Y) can be coded as 1.
- When E-48P Series controllers are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.
TECHNICAL SPECIFICATIONS
Parameter | Description |
---|---|
Control Type | On/Off, PID, Heat/Cool, Floating and Feedback Control of |
Valves
Operating Voltage| 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V
DC
Relays / SSR| 2 pieces SPST – NO 250 V AC 5A relays or 24 V DC 25 mA
(SSR) drives
Dimensions (mm)| 48 (Lenght) x 48 (Height) x 100 (Width)
Panel Cut-Out (mm)| 45 (Lenght) x 45 (Height)
Analog Output| 1 x 0..20 / 4..20 mA or 0..10 V DC optional
Analog Input| Universal (Note 1),
Communication (RS-485)| Available (RS-485)
Digital Input| None
Valve Feedback| None
Transmitter Supply| Available
Weight| 115 g
Power Consumption| Max. 7 W (10 VA)
Operating Temperature| – 10 °C … 55 °C
Storage Temperature| – 25 °C … 65 °C
Memory| Maks. 100.000 write
Protection Class| IP-65 Front Panel, IP-20 Rear Case
Notes
- (1) Universal Input:
- Thermocouple: B, E, J, K, L, N, R, S, T, U
- Resistance Thermometer: Pt-100
- Current: 0-20 mA, 4-20 mA (Linear)
- Voltage: 0-50 mV, 0-1 V, 0.2- 1 V (Linear),
- 0-10 V DC, must be specified in the order.
- Resolution: 16 bit
- Accuracy: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)
- Resistance Thermometer, Max. ±0.5 °C
- (Conversion and wire resistance compensation)
- Linear Input, Max. % 0.1
PARAMETER TABLE
ACCESSING PARAMETERS
APPLICATION EXAMPLES
- Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High AO1: 4-20 mA PID Control Output
- Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High
- Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)
Table 1. Input Type Options
- (*) Custom specified volt input
Table 2. Control Set Options
Table 3. Alarm Options
Table 4. Control Type Options
Table 5. Relay Output Options
Table 6. Analog Output Options
Table 7.1. Analog Output Range
Table 7.2. Analog Output Range
Scan
For detailed information, you can access the comprehensive user manual of the
device under the heading “User Manuals” at
www.elimko.com.tr.
You can also use the QR Code on the front for this.
Contact
Elimko Elektronik İmalat ve Kontrol Ticaret Ltd. Şti.
- Ankara Sanayi Odası 2. Organize Sanayi Bölgesi Alcı OSB Mahallesi 2001. Cad. No:14 Temelli 06909 Ankara / TURKİYE
- Tel: +90 312 212 64 50 (Pbx)
- Fax: +90 312 212 41 43
- E-mail: elimko@elimko.com.tr
- www.elimko.com.tr
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>