Elimko E-2000M Universal Advanced Controller User Guide
- June 13, 2024
- Elimko
Table of Contents
E-2000M Serisi
Universal Advanced
Controller
Quick Start Guide
E-2000M
DESCRIPTION
E-2000M Series general purpose process controllers are industrial devices in
1/4 DIN (96×96 mm IEC/TR 60668) dimensions designed by using new generation
microcontrollers with on/off, PID and other control forms. Inputs and outputs
can be easily programmed by the user.
In E-2000M Series controllers, set value and measured value can be displayed
from -1999 to 9999 on two 4-digit displays and general purpose inputs (T/C,
R/T, mV, mA) can be programmed.
DIMENSIONS and PANEL CUT-OUT
CONNECTION DIAGRAM
1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR
(SSR1, SSR2).
Analog output (AO1) can be selected as either mA or 0-10 V DC.
WARNING
E-2000M controller is designed for panel mounting and should be used in an industrial environment.
- The package of E-2000M controller contains; Controller,2 pieces of mounting clamps, User manual and Guarantee certificate
- After opening the package, please check the contents with the above list. If the delivered product is wrong type, any item is missing or there are visible defects, contact the vendor from which you purchased the product.
- Before installing and operating the controller, please read the user manual thoroughly.
- The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
- Keep the unit away from flamable gases, that could cause explosion.
- Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
- It is not used in medical applications.
EU DIRECTIVE COMPLIANCE
Low Voltage Directive: EN 61010-1
EMC Directive: EN 61326-1 TS EN ISO 9001
Quality Management System Certificate
TYPE CODING
E-2000M Series Universal Advanced Controller
Relay Outputs
None
1 relay (RL1)
2 relays (RL1, RL2)
1 SSR (SSR1)
1 SSR (SSR1) + 1 relay (RL2)
2 SSR (SSR1, SSR2)
Analog Outputs
None
0-20 / 4-20 mA (AO1)
0-10 V DC (AO1)
Communication
None
Operating Voltage
85-265 V AC / 85-375 V DC
20-60 V AC / 20-60 V DC
TECHNICALSPECIFICATION
Parameter | Description |
---|---|
Control Type | On/Off, PID, Heat/Cool, Floating Control of Valves |
Operating Voltage | 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC |
Relays / SSR | 2 x SPST – NO 250 V AC 5A or 24 V DC 25 mA (SSR) drives |
Dimensions (mm) | 96 (Lenght) x 96 (Height) x 50 (Width) |
Panel Cut-Out (mm) | 92 (Lenght) X 92 (Height) |
Analog Output | 1 x 0..20 / 4-20 mA or 0..10 V DC optional |
Analog Input | Universal (Note 1) |
Communication (RS-485) | None |
Digital Input | None |
Valve Feedback | None |
Transmitter Supply | None |
Weight | 230 g |
Power Consumption | Max. 7 W (10 VA) |
Operating Temperature | – 10 °C … 55 °C |
Storage Temperature | – 25 °C … 65 °C |
Memory | Maks. 100.000 write |
Protection Class | IP-65 Front Panel, IP-20 Rear Case |
Notes:
(1) Universal Input :
Thermocouple: B, E, J, K,L, N, R, S, T, U
Resistance Thermometer: Pt-100
Current: 0-20 mA, 4-20 mA (Linear)
Voltage: 0-50 mV, 0-1 V, 0.2- 1 V (Linear),
0-10 V DC, must be specified in the order.
Resolution: 16 bit
Accuracy: Thermocouple, Max. +1.0 °C (Conversion and CJC error)
Resistance Thermometer, Max. 0.5 °C (Conversion and wire resistance
compensation)
Linear Input, Max. % 0.1
PARAMETER TABLE
| Description| Min| Maks| Unit
---|---|---|---|---
INPUT SETTINGS| | | Analog Input 1 Type|
Table 1
| Decimal Point| 0| 3|
| Analog Input 1 Linear Scale Lower Value| -199.9| 999.9| EU
| Analog Input 1 Linear Scale Upper Value| -199.9| 999.9| EU
| Temperature Unit| | |
| Analog Input 1 Offset Value| -100.0| 100.0| EU
| Analog Input 1 Filter| 1| 15| s
| Analog Input 1 Sensor Broken Behaviour| | |
CONTROL SET SETTINGS| | | Control Set Point Source|
Table 2
---|---|---|---|---
| Control Set Point Lower Limit| -199.9| | EU
| Control Set Point Upper Limit| | 999.9| EU
| Control Set Point Ramping Rate| | 60.0| EU/min
| 1. Step Set Value| | | EU
| 1. Step Time| | 999.9| min
| 2. Step Set Value| | | EU
| 2. Step Time| | 999.9| min
| 3. Step Set Value| | | EU
| 3. Step Time| | 999.9| min
ALARM SETTINGS| | | Alarm 1 Type| Table 3
---|---|---|---|---
| Alarm 1 Set Point| -199.9| 999.9| EU
| Alarm 1 Hysteresis| 0.0| 999.9| EU
| Alarm 1 Lock| | |
| Alarm 2 Type| Table 3
| Alarm 2 Set Point| -199.9| 999.9| EU
| Alarm 2 Hysteresis| 0.0| 999.9| EU
| Alarm 2 Lock| | |
OUTPUT SETTINGS| | | Control Type| Table 4
---|---|---|---|---
| Control Form [ ]| | |
| Control Period| 1| 250| s
| Manual Mode Selection| | |
| Floating Control Valve Travel Time| 10| 2500| s
| Dead Band| 0.1| 25.0| %
| Control Output Lower Limit| 0.0| | %
| Control Output Upper Limit| | 100.0| %
| Control Output Manual Reset| | | (Y0
| PID Power On Behaviour| 0| 4|
| Retransmission Scale Lower Value| -200.| | EU
| Retransmission Scale Upper Value| | 1000.| EU
| Relay 1 Function| Table 5
| Relay 2 Function| Table 5
| Analog Output 1 Function| Table 6
| Analog Output 1 Type| Table 7.1 ve Table 7.2
PID SETTINGS| | | PID Auto Tune| | |
---|---|---|---|---|---|---
| PID Parameter Type| | |
| Proportional Band +| 0.1| 999.9| EU
| Proportional Band –| 0.1| 999.9| EU
| Integral Time +| | 9999| s
| Integral Time –| | 9999| s
| Derivative Time +| | 2500| s
| Derivative Time –| | 2500| s
| Hysteresis| 0.0| 999.9| EU
SECURITY| | | Security Code| 0| 9999
---|---|---|---|---|---
| Parameter Access Level| 0| 9
| Parameter Setting Level| 0| 9
| Factory Settings [ ]| |
ACCESSING PARAMETERS
APPLICATION EXAMPLES
- Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High
AO1: 4-20 mA PID Control Output![Elimko E 2000M Universal Advanced Controller
-
Symbols 85](https://manuals.plus/wp-content/uploads/2023/10/Elimko-E-2000M- Universal-Advanced-Controller-Symbols-85.png)
- Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High
- Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes),
Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)
Table 1. Input Type Options
| Type B Thermocouple
| Type E Thermocouple
| Type J Thermocouple
| Type K Thermocouple
| Type L Thermocouple
| Type N Thermocouple
| Type R Thermocouple
| Type S Thermocouple
| Type T Thermocouple
| Type U Thermocouple
| Pt-100
| 0-20 mA
| 4-20 mA
| 0-50 mV
| 0-1 V
| 0.2-1 V
| 0-10 V ()
| 2-10 V ()
(*) Custom specified volt input
Table 2. Control Set Options
| Internal adjustment with keys
| With Profile Control
Table 3. Alarm Options
| Off
| Low Alarm
| High Alarm
| Low Deviation
| High Deviation
| Band Alarm (In)
| Band Alarm (Out)
Table 4. Control Type Options
| No Control
| Single (Heat)
| Double (Heat/Cool)
| Floating Control of Valve
Tablo 5. Relay Output Options
| PID + (Heating)
| PID – (Cooling)
| On-Off + (Heating)
| On-Off – (Cooling)
| Alarm 1
| Alarm 2
| Alarm 3
| Alarm 4
Table 6. Analog Output Options
| PID + (Heating)
| PID – (Cooling)
| Process Value
| Control Set Value
Table 7.1. Analog Output Range
| 0-20 mA
| 20-0 mA
| 4-20 mA
| 20-4 mA
Table 7.2. Analog Output Range
| 0-10 V
| 10-0 V
| 2-10 V
| 10-2 V
For detailed information, you can access the comprehensive user manual of the
device under the heading “User Manuals” at
www.elimko.com.tr.
You can also use the QR Code on the front for this.
****Manufacturer / Technical Support : Elimko Co. Ltd.
8. Cadde 21. Sokak No:16 06510 Emek / ANKARA – TURKEY
Phone:+ 90 312 212 64 50 Fax:+ 90 312 212 41 43
www.elimko.com.tr e-posta:
elimko@elimko.com.trhttps://elimko.com.tr/en
/technical-support/user-manuels
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>