Elimko E-94 Series Universal Advanced Controller User Guide
- June 13, 2024
- Elimko
Table of Contents
E-94 Series
Universal Advanced
Controller
Quick Start Guide
E-94 Series Universal Advanced Controller
Manufacturer / Technical Support : Elimko Co. Ltd.
8. Cadde 21. Sokak No:16 06510 Emek / ANKARA – TURKEY
Phone:+ 90 312 212 64 50 Fax:+ 90 312 212 41 43
www.elimko.com.tr e-posta:
elimko@elimko.com.tr
DESCRIPTION
E-94 Series general purpose process controllers are industrial devices in 1/8
DIN (96×48 mm IEC/TR 60668) dimensions designed by using new generation
microcontrollers with on/off, PID and other control forms. Inputs and outputs
can be easily programmed by the user.
In E-94 Series controllers, set value and measured value can be displayed from
-1999 to 9999 on two 4-digit displays and general purpose inputs (T/C, R/T,
mV, mA) can be programmed.
DIMENSIONS and PANEL CUT-OUT
CONNECTION DIAGRAM
1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR
(SSR1, SSR2).
Controllers with RS-485 do not have a Valve Feedback input. Analog output
(A01) can be selected as either mA or 0-10 V DC.
WARNINGS
E-94 controller is designed for panel mounting and should be used in an industrial environment.
- The package of E-94 controller contains; Controller, 2 pieces of mounting clamps, User manual and Guarantee certificate
- After opening the package, please check the contents with the above list. If the delivered product is wrong type, any item is missing or there are visible defects, contact the vendor from which you purchased the product.
- Before installing and operating the controller, please read the user manual thoroughly.
- The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
- Keep the unit away from flamable gases, that could cause explosion.
- Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
- It is not used in medical applications.
EU DIRECTIVE COMPLIANCE
Low Voltage Directive: EN 61010-1
EMC Directive: EN 61326-1
TYPE CODING
E-94 Series Universal Advanced Controller
Relay Outputs| 2 relays (RL1, RL2)
3 relays (RL1, RL2, RL3)
4 relays (RL1, RL2, RL3, RL4)
1 SSR (SSR1) + 1 relay (RL2)
1 SSR (SSR1) + 2 relays (RL2, RL3)
1 SSR (SSR1) + 3 relays (RL2, RL3, RL4)
2 SSR (SSR1, SSR2) + 1 relays (RL3)
2 SSR (SSR1, SSR2) + 2 relays (RL3, RL4)|
---|---|---
Analog Outputs| None
0-20 / 4-20 mA (AO1)
0-10 V DC (AO1)
Communication| None
RS-485
Operating Voltage| 85-265 V AC / 85-375 V DC
20-60 V AC / 20-60 V DC
- When E-94 Series devices are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.
TECHNICAL SPECIFICATIONS
Parameter | Description |
---|---|
Control Type | On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves |
Operating Voltage | 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC |
Relays I SSR | 4 x SPST – NO 250 V AC 5 A relays or 24 V DC 25 mA (SSR) drives |
Dimensions (mm) | 96 (Lenght) x 48 (Height) x 100 (Width) |
Panel Cut-Out (mm) | 92 (Lenght) X 45 (Height) |
Analog Output | 0..20 / 4-20 mA or 0..10 V DC optional |
Analog Input | Universal (Note 1), 1 x External set point (mA) |
Communication (RS-485) | Available (Note 2) |
Digital Input | None |
Valve Feedback | Available (Note 2) |
Transmitter Supply | Available |
Weight | 220 g |
Power Consumption | Max. 7 W (10 VA) |
Operating Temperature | – 10 °C … 55 °C |
Storage Temperature | – 25 °C … 65 °C |
Memory | Max. 100.000 write |
Protection Class | IP-65 Front Panel, IP-20 Rear Case |
Notes:
-
Universal Input :
Thermocouple: B, E, J, K, L, N, R, S, T, U
Resistance Thermometer: Pt-100
Current: 0-20 mA, 4-20 mA (Linear) Voltage: 0-50 mV, 0-1 V, 0.2- 1 V (Linear), 0-10 V DC, must be specified in the order.
Resolution: 16 bit
Accuracy: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)
Resistance Thermometer, Max. ±0.5 °C (Conversion and wire resistance compensation) Linear Input, Max. % 0.1 -
Valve Feedback are supplied as potentiometer input in standard controllers. If the feedback type is requested as mA, it must be specified in the order. Controllers with RS-485 do not have a Valve Feedback input.
PARAMETER TABLE
| Description| Min| Maks| Unit
---|---|---|---|---
INPUT SETTINGS| | | Analog Input 1 Type| Table 1
| Decimal Point| 0| 3|
| Analog Input 1 Linear Scale Lower Value| -199.9| 999.9| EU
| Analog Input 1 Linear Scale Upper Value| -199.9| 999.9| EU
| Temperature Unit| | |
| Analog Input 1 Offset Value| -100.0| 100.0| EU
| Analog Input 1 Filter| 1| 15| s
| Analog Input 1 Sensor Broken Behaviour| | |
| Analog Input 2 Type| | |
| Analog Input 2 Linear Scale Lower Value| -199.9| 999.9| EU
| Analog Input 2 Linear Scale Upper Value| -199.9| 999.9| EU
| Analog Input 2 Sensor Broken Behaviour| | |
| Modbus Adress| 1| 127|
| Modbus Baud Rate [ ]| | |
| Modbus Parity [ ]| | |
CONTROL SET SETTINGS| | | Control Set Point Source| Table 2
---|---|---|---|---
| Control Set Point Lower Limit| -199.9| | EU
| Control Set Point Upper Limit| | 999.9| EU
| Control Set Point Ramping Rate| | 60.0| EU/min
| 1. Step Set Value| SPLL| | EU
| 1. Step Time| | 999.9| min
| 2. Step Set Value| | | EU
| 2. Step Time| | 999.9| min
| 3. Step Set Value| | | EU
| 3. Step Time| | 999.9| min
ALARM SETTINGS| | | Alarm 1 Type| Table 3
---|---|---|---|---
| Alarm 1 Set Point| -200.| 1000.| EU
| Alarm 1 Hysteresis| 0.0| 1000.| EU
| Alarm 1 Lock| | |
| Alarm 2 Type| Table 3
| Alarm 2 Set Point| -200.| 1000.| EU
| Alarm 2 Hysteresis| 0.0| 1000.| EU
| Alarm 2 Lock| | |
| Alarm 3 Type| Table 3
| Alarm 3 Set Point| -200.| 1000.| EU
| Alarm 3 Hysteresis| 0.0| 1000.| EU
| Alarm 3 Lock| | |
| Alarm 4 Type| Table 3
| Alarm 4 Set Point| -200.| 1000.| EU
| Alarm 4 Hysteresis| 0.0| 1000.| EU
| Alarm 4 Lock| | |
OUTPUT SETTINGS| | | Control Type| Table 4
---|---|---|---|---
| Control Form VI 1/-, rEu]| | |
| Control Period| 1| 250| s
| Manual Mode Selection| | |
| Floating Control Valve Travel Time| 10| 2500| s
| Dead Band| 0.1| 25.0|
| Control Output Lower Limit| 0.0| |
| Control Output Upper Limit| | 100.0|
| Control Output Manual Reset| | 01-11|
| PID Power On Behaviour| 0| 4|
| Retransmission Scale Lower Value| -999..9| | EU
| Retransmission Scale Upper Value| | 999..9| EU
| Relay 1 Function| Table 5
| Relay 2 Function| Table 5
| Relay 3 Function| Table 5
| Relay 4 Function| Table 5
| Analog Output 1 Function| Table 6
| Analog Output 1 Type| Table 7.1 ve Table 7.2
| Feedback Valve Fully-Closed Position| | |
| Feedback Valve Fully-Open Position| | |
PID SETTINGS
| | | PID Auto Tune| | |
---|---|---|---|---|---|---
| PID Parameter Type| | |
| Proportional Band +| 0.1| 999.9| EU
| Proportional Band| 0.1| 999.9| EU
| Integral Time +| | 9999| S
| Integral Time| | 9999| S
| Derivative Time +| | 2500| S
| Derivative Time| | 2500| S
| Hysteresis| | 999.9| EU
SECURITY
|
| | Security Code| 0| 9999|
---|---|---|---|---|---|---
| Parameter Access Level| 0| 9|
| Parameter Setting Level| 0| 9|
| Factory Settings | | |
ACCESSING PARAMETERS
APPLICATION EXAMPLES
-
Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High A01: 4-20 mA PID Control Output
-
Input: TC Type J, Relayl: On-Off Control Output, Relay2 / Alarm2: 350 °C High
-
Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relayl: PID Control Output, A01: Retransmission Output (4-20 mA, 0-1200 °C)
-
Input: 4-20 mA, Scale: 0-600, External Set Point: 4-20 mA, Scale: 0-600, Floating Valve Control (Travel Time 30 s), Relayl: Valve Open, Relay2: Valve Close
Table 1. Input Type Options
| Type B Thermocouple
| Type E Thermocouple
| Type J Thermocouple
| Type K Thermocouple
| Type L Thermocouple
| Type N Thermocouple
| Type R Thermocouple
| Type S Thermocouple
| Type T Thermocouple
| Type U Thermocouple
| pt-100
| 0-20 mA
| 4-20 mA
| 0-50 mV
| 0-1V
| 0.2-1 V
| 0-10 V ()
| 2-10 V ()
(*) Custom specified volt input
Table 2. Control Set Options
| Internal adjustment with keys
| With Profile Control
| External adjustment with
AIN2 external input
Table 3. Alarm Options
| Off
| Low Alarm
| Low Deviation
| High nigh Deviation
| Band Alarm (In)
| Band Alarm (Out)
Table 4. Control Type Options
| No Control
| Single (Heat)
| Double (Heat/Cool)
| Floating Control of Valve
| Feedback Control of Valve
Tablo 5. Relay Output Options
| PID + (Heating)
| PID – (Cooling)
| On-Off + (Heating)
| On-Off – (Cooling)
| Alarm 1
| Alarm 2
| Alarm 3
| Alarm 4
Table 6. Analog Output Options
| PID + (Heating)
| PID – (Cooling)
| Process Value
| Control Set Value
Table 7.1. Analog Output Range
| 0-20 mA
| 20-0 mA
| 4-20 mA
| 20-4 mA
Table 7.2. Analog Output Range
| 0-10 V
| 10-0 V
| 2-10 V
| 10-2 V
For detailed information, you can access the comprehensive user manual of the
device under the heading “User Manuals” at
www.elimko.com.tr.
You can also use the QR Code on the front for this.