Elimko KY-94-1123-1 E-94 Series Universal Advanced Controller User Guide

June 15, 2024
Elimko

Elimko KY-94-1123-1 E-94 Series Universal Advanced Controller

Elimko-KY-94-1123-1-E-94 Series-Universal-Advanced-Controller-fig-
\(11\)

Product Information

Specifications

  • Model: E-94 Series
  • Dimensions: 1/8 DIN (96×48 mm IEC/TR 60668)
  • Control Forms: On/Off, PID, and other control forms
  • Display Range: -1999 to 9999
  • Inputs: T/C, R/T, mV, mA
  • Outputs: Relay (RL1, RL2, RL3, RL4) or SSR (SSR1, SSR2)
  • Analog Output: mA or 0-10 V DC

Product Usage Instructions

Installation

  • The E-94 controller is designed for panel mounting and should be used in an industrial environment.
  • Before installing and operating the controller, please read the user manual thoroughly.
  • The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
  • Keep the unit away from flammable gases that could cause an explosion.

Cleaning

  • Do not use alcohol or other solvents to clean the controller.
  • Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.

Safety Precautions

  • The E-94 controller is not intended for use in medical applications.

FAQ

  • Q: What are the dimensions of the E-94 Series controller?
    The dimensions of the E-94 Series controller are 1/8 DIN (96×48 mm IEC/TR 60668).

  • Q: What types of inputs are supported by the E-94 Series controller?
    The E-94 Series controller supports T/C, R/T, mV, and mA inputs.

  • Q: Can the E-94 Series controller be used in medical applications?
    No, the E-94 Series controller is not intended for use in medical applications.

DESCRIPTION

E-94 Series general-purpose process controllers are industrial devices in 1/8 DIN (96×48 mm IEC/TR 60668) dimensions designed by using new generation microcontrollers with on/off, PID and other control forms. Inputs and outputs can be easily programmed by the user.
In E-94 Series controllers, set value and measured value can be displayed from -1999 to 9999 on two 4-digit displays and general purpose inputs (T/C, R/T, mV, mA) can be programmed

DIMENSIONS and PANEL CUT-OUT

Elimko-KY-94-1123-1-E-94 Series-Universal-
Advanced-Controller-fig- \(2\)

CONNECTION DIAGRAM

Elimko-KY-94-1123-1-E-94 Series-Universal-Advanced-
Controller-fig- \(3\)

  • 1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2).
  • Controllers with RS-485 do not have a Valve Feedback input.
  • Analog output (AO1) can be selected as either mA or 0-10 V DC.

Elimko-KY-94-1123-1-E-94 Series-Universal-Advanced-Controller-fig-
\(4\)

WARNINGS

E-94 controller is designed for panel mounting and should be used in an industrial environment.

  • The package of E-94 controller contains; Controller, 2 pieces of mounting clamps, User manual, and Guarantee certificate.
  • After opening the package, please check the contents of the above list. If the delivered product is the wrong type, any item is missing or there are visible defects, contact the vendor from which you purchased the product.
  • Before installing and operating the controller, please read the user manual thoroughly.
  • The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
  • Keep the unit away from flammable gases, that could cause an explosion.
  • Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
  • It is not used in medical applications.

EU DIRECTIVE COMPLIANCE

  • Low Voltage Directive
  • EN 61010-1
  • EMC Directive
  • EN 61326-1

TSE-ISO-EN 9000
Quality Management System Certificate

TYPE CODING

E-94 Series Universal Advanced ControllerElimko-KY-94-1123-1-E-94 Series-
Universal-Advanced-Controller-fig- \(5\)

When E-94 Series devices are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.
Controllers with RS-485 do not have a Valve Feedback input.

TECHNICAL SPECIFICATIONS

Parameter Description
Control Type On/Off, PID, Heat/Cool, Floating and Feedback Control of

Valves
Operating Voltage| 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC
Relays / SSR| 4 x SPST – NO 250 V AC 5 A relays or 24 V DC 25 mA (SSR) drives
Dimensions (mm)| 96 (Lenght) x 48 (Height) x 100 (Width)
Panel Cut-Out (mm)| 92 (Lenght) X 45 (Height)
Analog Output| 0..20 / 4..20 mA or 0..10 V DC optional
Analog Input| Universal (Note 1), 1 x External set point (mA)
Communication (RS- 485)| Available (Note 2)
Digital Input| None
Valve Feedback| Available (Note 2)
Transmitter Supply| Available
Weight| 220 g
Power Consumption| Max. 7 W (10 VA)
Operating Temperature| – 10 °C … 55 °C
Storage Temperature| – 25 °C … 65 °C
Memory| Max. 100.000 write
Protection Class| IP-65 Front Panel, IP-20 Rear Case

Universal Input

  • Thermocouple: B, E, J, K, L, N, R, S, T, U
  • Resistance Thermometer: Pt-100
  • Current  : 0-20 mA, 4-20 mA (Linear)
  • Voltage : 0-50 mV, 0-1 V, 0.2- 1 V (Linear), 0-10 V DC, must be specified in the order.
  • Resolution : 16 bit
  • Accuracy: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)
  • Resistance Thermometer, Max. ±0.5 °C (Conversion and wire resistance compensation)
  • Linear Input, Max. % 0.1

Valve Feedback are supplied as potentiometer input in standard controllers. If the feedback type is requested as mA, it must be specified in the order. Controllers with RS-485 do not have a Valve Feedback input

PARAMETER TABLE

  Description Min Maks Unit
INPUT SETTINGS gcnf INP1 Analog Input 1 Type Table 1
DP Decimal Point 0 3
SCLO Analog Input 1 Linear Scale Lower Value -199.9 999.9 EU
SCHI Analog Input 1 Linear Scale Upper Value -199.9 999.9 EU
UNIT Temperature Unit *C *F
OFST Analog Input 1 Offset Value -100.0 100.0 EU
FLTR Analog Input 1 Filter 1 15 s
SNBR Analog Input 1 Sensor Broken Behaviour LO HI
INP2 Analog Input 2 Type 0-20 4-20
S2LO Analog Input 2 Linear Scale Lower Value -199.9 999.9 EU
S2HI Analog Input 2 Linear Scale Upper Value -199.9 999.9 EU
S2BR Analog Input 2 Sensor Broken Behaviour LO HI
ADRS Modbus Adress 1 127
BAUD Modbus Baud Rate [4.8, 9.6, 19.2, 38.4 kbaud] 4.8 38.4
PRTY Modbus Parity [None, ODD, Even]    
CONTROL SET SETTINGS SETP SPSR Control Set Point Source Table 2
--- --- --- --- ---
SPLL Control Set Point Lower Limit -199.9 SPHL EU
SPHL Control Set Point Upper Limit SPLL 999.9 EU
SPRR Control Set Point Ramping Rate OFF 60.0 EU/min
S-1 1. Step Set Value SPLL SPHL EU
T-1 1. Step Time OFF 999.9 min
S-2 2. Step Set Value SPLL SPHL EU
T-2 2. Step Time OFF 999.9 min
S-3 3. Step Set Value SPLL SPHL EU
T-3 3. Step Time OFF 999.9 min
ALARM SETTINGS ACNF A1TP Alarm 1 Type Table 3
--- --- --- --- ---
A1SP Alarm 1 Set Point -199.9 999.9 EU
A1HY Alarm 1 Hysteresis 0.0 999.9 EU
A1LT Alarm 1 Lock DSB ENB
A2TP Alarm 2 Type Table 3
A2SP Alarm 2 Set Point -199.9 999.9 EU
A2HY Alarm 2 Hysteresis 0.0 999.9 EU
A2LT Alarm 2 Lock DSB ENB
A3TP Alarm 3 Type Table 3
A3SP Alarm 3 Set Point -199.9 999.9 EU
A3HY Alarm 3 Hysteresis 0.0 999.9 EU
A3LT Alarm 3 Lock DSB ENB
A4TP Alarm 4 Type Table 3
A4SP Alarm 4 Set Point -199.9 999.9 EU
A4HY Alarm 4 Hysteresis 0.0 999.9 EU
A4LT Alarm 4 Lock DSB ENB
OUTPUT SETTINGS OCNF CTYP Control Type Table 4
--- --- --- --- ---
CFRM Control Form [DIR, REV] DIR REV
CPRD Control Period 1 250 s
MNPR Manual Mode Selection DSB ENB
TRTM Floating Control Valve Travel Time 10 2500 s
DBND Dead Band 0.1 25.0 %
OLL Control Output Lower Limit 0.0 OHL %
OHL Control Output Upper Limit OLL 100.0 %
OMR Control Output Manual Reset OLL OHL %
PONC PID Power On Behaviour 0 4
TRLL Retransmission Scale Lower Value -199.9 TRHL EU
TRHL Retransmission Scale Upper Value TRLL 999.9 EU
RL1D Relay 1 Function Table 5
RL2D Relay 2 Function Table 5
RL3D Relay 3 Function Table 5
RL4D Relay 4 Function Table 5
AO1D Analog Output 1 Function Table 6
AO1R Analog Output 1 Type Table 7.1 ve Table 7.2
SRVL Feedback Valve Fully-Closed Position    
SRVH Feedback Valve Fully-Open Position    
PID SETTINGS tUNE AT PID Auto Tune OFF
--- --- --- --- ---
PID PID Parameter Type STD ADV
PB-1 Proportional Band + 0.1 999.9 EU
PB-2 Proportional Band – 0.1 999.9 EU
ITH Integral Time + OFF 9999 s
ITC Integral Time – OFF 9999 s
DTH Derivative Time + OFF 2500 s
DTC Derivative Time – OFF 2500 s
HYS Hysteresis 0.0 999.9 EU
SECURITY PRTC SCOD Security Code 0
--- --- --- --- ---
DPRL Parameter Access Level 0 9
APRL Parameter Setting Level 0 9
FCST Factory Settings [OFF, LOAD, SAVE, DFLT]    

ACCESSING PARAMETERS

Elimko-KY-94-1123-1-E-94 Series-Universal-Advanced-
Controller-fig- \(6\)

APPLICATION EXAMPLES

  1. Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High AO1: 4-20 mA PID Control OutputElimko-KY-94-1123-1-E-94 Series-Universal-Advanced-Controller-fig- \(7\)
  2. Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High
  3. Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)Elimko-KY-94-1123-1-E-94 Series-Universal-Advanced-Controller-fig- \(9\)
  4. Input: 4-20 mA, Scale: 0-600, External Set Point: 4-20 mA, Scale: 0-600, Floating Valve Control (Travel Time 30 s), Relay1: Valve Open, Relay2: Valve CloseElimko-KY-94-1123-1-E-94 Series-Universal-Advanced-Controller-fig- \(10\)

Table 1. Input Type Options

b| Type B Thermocouple
e| Type E Thermocouple
j| Type J Thermocouple
k| Type K Thermocouple
l| Type L Thermocouple
n| Type N Thermocouple
r| Type R Thermocouple
s| Type S Thermocouple
t| Type T Thermocouple
u| Type U Thermocouple
pt| Pt-100
0-20| 0-20 mA
4-20| 4-20 mA
0-50| 0-50 mV
0.0-1| 0-1 V
0.2-1| 0.2-1 V
0-10| 0-10 V ()
2-10| 2-10 V (
)
Table 2. Control Set Options

int| Internal adjustment with

keys

prfl| With Profile Control
e/t| External adjustment with AIN2 external input
Table 3. Alarm Options

off| Off
lo| Low Alarm
hi| High Alarm
loD| Low Deviation
hiD| High Deviation
lob| Band Alarm (In)
hib| Band Alarm (Out)
Table 4. Control Type Options

off| No Control
sco| Single (Heat)
Dco| Double (Heat/Cool)
bnD| Floating Control of Valve
pfb| Feedback Control of Valve
Tablo 5. Relay Output Options

co-1| PID + (Heating)
co-2| PID – (Cooling)
Do-1| On-Off + (Heating)
Do-2| On-Off – (Cooling)
al-1| Alarm 1
al-2| Alarm 2
al-3| Alarm 3
al-4| Alarm 4
Table 6. Analog Output Options

co-1| PID + (Heating)
co-2| PID – (Cooling)
pvtr| Process Value
sptr| Control Set Value
Table 7.1. Analog Output Range

0-20| 0-20 mA
20-0| 20-0 mA
4-20| 4-20 mA
20-4| 20-4 mA
Table 7.2. Analog Output Range

0-10| 0-10 V
10-0| 10-0 V
2-10| 2-10 V
10-2| 10-2 V

For detailed information, you can access the comprehensive user manual of the device under the heading “User Manuals” at www.elimko.com.tr. You can also use the QR Code on the front for this
Elimko Elektronik İmalat ve Kontrol Ticaret Ltd. Şti.
Ankara Sanayi Odası 2. Organize Sanayi Bölgesi Alcı OSB Mahallesi 2001. Cad. No:14 Temelli 06909 Ankara / TURKİYE
Tel : +90 312 212 64 50 (Pbx)
Fax: +90 312 212 41 43
E-mail: elimko@elimko.com.tr www.elimko.com.tr