Elimko KY-94-1123-1 E-94 Series Universal Advanced Controller User Guide
- June 15, 2024
- Elimko
Table of Contents
- Elimko KY-94-1123-1 E-94 Series Universal Advanced Controller
- Product Information
- Product Usage Instructions
- DESCRIPTION
- DIMENSIONS and PANEL CUT-OUT
- CONNECTION DIAGRAM
- TYPE CODING
- TECHNICAL SPECIFICATIONS
- PARAMETER TABLE
- ACCESSING PARAMETERS
- APPLICATION EXAMPLES
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Elimko KY-94-1123-1 E-94 Series Universal Advanced Controller
Product Information
Specifications
- Model: E-94 Series
- Dimensions: 1/8 DIN (96×48 mm IEC/TR 60668)
- Control Forms: On/Off, PID, and other control forms
- Display Range: -1999 to 9999
- Inputs: T/C, R/T, mV, mA
- Outputs: Relay (RL1, RL2, RL3, RL4) or SSR (SSR1, SSR2)
- Analog Output: mA or 0-10 V DC
Product Usage Instructions
Installation
- The E-94 controller is designed for panel mounting and should be used in an industrial environment.
- Before installing and operating the controller, please read the user manual thoroughly.
- The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
- Keep the unit away from flammable gases that could cause an explosion.
Cleaning
- Do not use alcohol or other solvents to clean the controller.
- Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
Safety Precautions
- The E-94 controller is not intended for use in medical applications.
FAQ
-
Q: What are the dimensions of the E-94 Series controller?
The dimensions of the E-94 Series controller are 1/8 DIN (96×48 mm IEC/TR 60668). -
Q: What types of inputs are supported by the E-94 Series controller?
The E-94 Series controller supports T/C, R/T, mV, and mA inputs. -
Q: Can the E-94 Series controller be used in medical applications?
No, the E-94 Series controller is not intended for use in medical applications.
DESCRIPTION
E-94 Series general-purpose process controllers are industrial devices in 1/8
DIN (96×48 mm IEC/TR 60668) dimensions designed by using new generation
microcontrollers with on/off, PID and other control forms. Inputs and outputs
can be easily programmed by the user.
In E-94 Series controllers, set value and measured value can be displayed from
-1999 to 9999 on two 4-digit displays and general purpose inputs (T/C, R/T,
mV, mA) can be programmed
DIMENSIONS and PANEL CUT-OUT
CONNECTION DIAGRAM
- 1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2).
- Controllers with RS-485 do not have a Valve Feedback input.
- Analog output (AO1) can be selected as either mA or 0-10 V DC.
WARNINGS
E-94 controller is designed for panel mounting and should be used in an industrial environment.
- The package of E-94 controller contains; Controller, 2 pieces of mounting clamps, User manual, and Guarantee certificate.
- After opening the package, please check the contents of the above list. If the delivered product is the wrong type, any item is missing or there are visible defects, contact the vendor from which you purchased the product.
- Before installing and operating the controller, please read the user manual thoroughly.
- The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
- Keep the unit away from flammable gases, that could cause an explosion.
- Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
- It is not used in medical applications.
EU DIRECTIVE COMPLIANCE
- Low Voltage Directive
- EN 61010-1
- EMC Directive
- EN 61326-1
TSE-ISO-EN 9000
Quality Management System Certificate
TYPE CODING
E-94 Series Universal Advanced Controller
When E-94 Series devices are ordered with communication, the E-IB-11 USB-RS485
converter can be used for PC connection. There are various control and
monitoring software provided by Elimko.
Controllers with RS-485 do not have a Valve Feedback input.
TECHNICAL SPECIFICATIONS
Parameter | Description |
---|---|
Control Type | On/Off, PID, Heat/Cool, Floating and Feedback Control of |
Valves
Operating Voltage| 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V
DC
Relays / SSR| 4 x SPST – NO 250 V AC 5 A relays or 24 V DC 25 mA (SSR)
drives
Dimensions (mm)| 96 (Lenght) x 48 (Height) x 100 (Width)
Panel Cut-Out (mm)| 92 (Lenght) X 45 (Height)
Analog Output| 0..20 / 4..20 mA or 0..10 V DC optional
Analog Input| Universal (Note 1), 1 x External set point (mA)
Communication (RS- 485)| Available (Note 2)
Digital Input| None
Valve Feedback| Available (Note 2)
Transmitter Supply| Available
Weight| 220 g
Power Consumption| Max. 7 W (10 VA)
Operating Temperature| – 10 °C … 55 °C
Storage Temperature| – 25 °C … 65 °C
Memory| Max. 100.000 write
Protection Class| IP-65 Front Panel, IP-20 Rear Case
Universal Input
- Thermocouple: B, E, J, K, L, N, R, S, T, U
- Resistance Thermometer: Pt-100
- Current : 0-20 mA, 4-20 mA (Linear)
- Voltage : 0-50 mV, 0-1 V, 0.2- 1 V (Linear), 0-10 V DC, must be specified in the order.
- Resolution : 16 bit
- Accuracy: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)
- Resistance Thermometer, Max. ±0.5 °C (Conversion and wire resistance compensation)
- Linear Input, Max. % 0.1
Valve Feedback are supplied as potentiometer input in standard controllers. If the feedback type is requested as mA, it must be specified in the order. Controllers with RS-485 do not have a Valve Feedback input
PARAMETER TABLE
Description | Min | Maks | Unit | |
---|---|---|---|---|
INPUT SETTINGS | gcnf | INP1 | Analog Input 1 Type | Table 1 |
DP | Decimal Point | 0 | 3 | |
SCLO | Analog Input 1 Linear Scale Lower Value | -199.9 | 999.9 | EU |
SCHI | Analog Input 1 Linear Scale Upper Value | -199.9 | 999.9 | EU |
UNIT | Temperature Unit | *C | *F | |
OFST | Analog Input 1 Offset Value | -100.0 | 100.0 | EU |
FLTR | Analog Input 1 Filter | 1 | 15 | s |
SNBR | Analog Input 1 Sensor Broken Behaviour | LO | HI | |
INP2 | Analog Input 2 Type | 0-20 | 4-20 | |
S2LO | Analog Input 2 Linear Scale Lower Value | -199.9 | 999.9 | EU |
S2HI | Analog Input 2 Linear Scale Upper Value | -199.9 | 999.9 | EU |
S2BR | Analog Input 2 Sensor Broken Behaviour | LO | HI | |
ADRS | Modbus Adress | 1 | 127 | |
BAUD | Modbus Baud Rate [4.8, 9.6, 19.2, 38.4 kbaud] | 4.8 | 38.4 | |
PRTY | Modbus Parity [None, ODD, Even] | |||
CONTROL SET SETTINGS | SETP | SPSR | Control Set Point Source | Table 2 |
--- | --- | --- | --- | --- |
SPLL | Control Set Point Lower Limit | -199.9 | SPHL | EU |
SPHL | Control Set Point Upper Limit | SPLL | 999.9 | EU |
SPRR | Control Set Point Ramping Rate | OFF | 60.0 | EU/min |
S-1 | 1. Step Set Value | SPLL | SPHL | EU |
T-1 | 1. Step Time | OFF | 999.9 | min |
S-2 | 2. Step Set Value | SPLL | SPHL | EU |
T-2 | 2. Step Time | OFF | 999.9 | min |
S-3 | 3. Step Set Value | SPLL | SPHL | EU |
T-3 | 3. Step Time | OFF | 999.9 | min |
ALARM SETTINGS | ACNF | A1TP | Alarm 1 Type | Table 3 |
--- | --- | --- | --- | --- |
A1SP | Alarm 1 Set Point | -199.9 | 999.9 | EU |
A1HY | Alarm 1 Hysteresis | 0.0 | 999.9 | EU |
A1LT | Alarm 1 Lock | DSB | ENB | |
A2TP | Alarm 2 Type | Table 3 | ||
A2SP | Alarm 2 Set Point | -199.9 | 999.9 | EU |
A2HY | Alarm 2 Hysteresis | 0.0 | 999.9 | EU |
A2LT | Alarm 2 Lock | DSB | ENB | |
A3TP | Alarm 3 Type | Table 3 | ||
A3SP | Alarm 3 Set Point | -199.9 | 999.9 | EU |
A3HY | Alarm 3 Hysteresis | 0.0 | 999.9 | EU |
A3LT | Alarm 3 Lock | DSB | ENB | |
A4TP | Alarm 4 Type | Table 3 | ||
A4SP | Alarm 4 Set Point | -199.9 | 999.9 | EU |
A4HY | Alarm 4 Hysteresis | 0.0 | 999.9 | EU |
A4LT | Alarm 4 Lock | DSB | ENB | |
OUTPUT SETTINGS | OCNF | CTYP | Control Type | Table 4 |
--- | --- | --- | --- | --- |
CFRM | Control Form [DIR, REV] | DIR | REV | |
CPRD | Control Period | 1 | 250 | s |
MNPR | Manual Mode Selection | DSB | ENB | |
TRTM | Floating Control Valve Travel Time | 10 | 2500 | s |
DBND | Dead Band | 0.1 | 25.0 | % |
OLL | Control Output Lower Limit | 0.0 | OHL | % |
OHL | Control Output Upper Limit | OLL | 100.0 | % |
OMR | Control Output Manual Reset | OLL | OHL | % |
PONC | PID Power On Behaviour | 0 | 4 | |
TRLL | Retransmission Scale Lower Value | -199.9 | TRHL | EU |
TRHL | Retransmission Scale Upper Value | TRLL | 999.9 | EU |
RL1D | Relay 1 Function | Table 5 | ||
RL2D | Relay 2 Function | Table 5 | ||
RL3D | Relay 3 Function | Table 5 | ||
RL4D | Relay 4 Function | Table 5 | ||
AO1D | Analog Output 1 Function | Table 6 | ||
AO1R | Analog Output 1 Type | Table 7.1 ve Table 7.2 | ||
SRVL | Feedback Valve Fully-Closed Position | |||
SRVH | Feedback Valve Fully-Open Position | |||
PID SETTINGS | tUNE | AT | PID Auto Tune | OFF |
--- | --- | --- | --- | --- |
PID | PID Parameter Type | STD | ADV | |
PB-1 | Proportional Band + | 0.1 | 999.9 | EU |
PB-2 | Proportional Band – | 0.1 | 999.9 | EU |
ITH | Integral Time + | OFF | 9999 | s |
ITC | Integral Time – | OFF | 9999 | s |
DTH | Derivative Time + | OFF | 2500 | s |
DTC | Derivative Time – | OFF | 2500 | s |
HYS | Hysteresis | 0.0 | 999.9 | EU |
SECURITY | PRTC | SCOD | Security Code | 0 |
--- | --- | --- | --- | --- |
DPRL | Parameter Access Level | 0 | 9 | |
APRL | Parameter Setting Level | 0 | 9 | |
FCST | Factory Settings [OFF, LOAD, SAVE, DFLT] |
ACCESSING PARAMETERS
APPLICATION EXAMPLES
- Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High AO1: 4-20 mA PID Control Output
- Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High
- Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)
- Input: 4-20 mA, Scale: 0-600, External Set Point: 4-20 mA, Scale: 0-600, Floating Valve Control (Travel Time 30 s), Relay1: Valve Open, Relay2: Valve Close
Table 1. Input Type Options
b| Type B Thermocouple
e| Type E Thermocouple
j| Type J Thermocouple
k| Type K Thermocouple
l| Type L Thermocouple
n| Type N Thermocouple
r| Type R Thermocouple
s| Type S Thermocouple
t| Type T Thermocouple
u| Type U Thermocouple
pt| Pt-100
0-20| 0-20 mA
4-20| 4-20 mA
0-50| 0-50 mV
0.0-1| 0-1 V
0.2-1| 0.2-1 V
0-10| 0-10 V ()
2-10| 2-10 V ()
Table 2. Control Set Options
int| Internal adjustment with
keys
prfl| With Profile Control
e/t| External adjustment with AIN2 external input
Table 3. Alarm Options
off| Off
lo| Low Alarm
hi| High Alarm
loD| Low Deviation
hiD| High Deviation
lob| Band Alarm (In)
hib| Band Alarm (Out)
Table 4. Control Type Options
off| No Control
sco| Single (Heat)
Dco| Double (Heat/Cool)
bnD| Floating Control of Valve
pfb| Feedback Control of Valve
Tablo 5. Relay Output Options
co-1| PID + (Heating)
co-2| PID – (Cooling)
Do-1| On-Off + (Heating)
Do-2| On-Off – (Cooling)
al-1| Alarm 1
al-2| Alarm 2
al-3| Alarm 3
al-4| Alarm 4
Table 6. Analog Output Options
co-1| PID + (Heating)
co-2| PID – (Cooling)
pvtr| Process Value
sptr| Control Set Value
Table 7.1. Analog Output Range
0-20| 0-20 mA
20-0| 20-0 mA
4-20| 4-20 mA
20-4| 20-4 mA
Table 7.2. Analog Output Range
0-10| 0-10 V
10-0| 10-0 V
2-10| 2-10 V
10-2| 10-2 V
For detailed information, you can access the comprehensive user manual of the
device under the heading “User Manuals” at
www.elimko.com.tr. You can also use the QR Code on
the front for this
Elimko Elektronik İmalat ve Kontrol Ticaret Ltd. Şti.
Ankara Sanayi Odası 2. Organize Sanayi Bölgesi Alcı OSB Mahallesi 2001. Cad.
No:14 Temelli 06909 Ankara / TURKİYE
Tel : +90 312 212 64 50 (Pbx)
Fax: +90 312 212 41 43
E-mail: elimko@elimko.com.tr
www.elimko.com.tr
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>