Elimko E-220 Series Universal Advanced Digital Controller
Product Information
The E-220 is a digital device manufactured by Elimko. It is compliant with EU Directives such as the Low Voltage Directive EN 61010-1 and Electromagnetic Compatibility EN 61326. The device has a KY-220-0723-0 model number and is part of the Elimko 220 series. It has a digital display and various LED indicators for status and alarms.
The device operates on an operating voltage of 7W (10 VA) and has a front panel protection class of IP 66 (NEMA 4X) and a back panel protection class of IP 20. It has an accuracy class for measurement and control, and uses a 16-bit analog-digital converter and 16-bit digital-analog converter. The control type can be set to ON/OFF or PID.
The E-220 supports various input types, including temperature sensors (e.g. TYPE-B, TYPE-E, TYPE-J, TYPE-K, TYPE-L, TYPE-N, TYPE-R, TYPE-S, TYPE-T, TYPE-U, PT-100) and linear inputs (e.g. current 0-20 mA, current 4-20 mA, voltage 0-50 mV, voltage 0-1 V, voltage 0.2-1 V).
The device has specific dimensions of 96 mm x 96 mm x 10 mm and weighs 430 g. It can be panel-mounted using appropriate fuses or switches in the supply line and power outputs. The power supply cables must meet the requirements of IEC 60245 or IEC 60227 standards.
Product Usage Instructions
Device Energization and Start Page
- Connect the device to a power source using appropriate fuses or switches.
- Press the power button to turn on the device.
- The start page will be displayed on the digital display.
Title Area
The title area on the front panel displays the device name (E-220) and
other relevant information.
LED Indicators and Meanings
The device has LED indicators that provide information about different
statuses and alarms. Refer to the user manual for detailed explanations of
each LED indicator.
Operator Pages
The device has multiple operator pages that allow you to access different functionalities and settings. These include:
- ANALOG Operator Page
- DIGITAL Operator Page
- ALARM SET Operator Page
- STATUS Operator Page
Refer to the user manual for instructions on navigating and using these operator pages.
Settings
The device has various settings that can be adjusted according to your requirements. These include setting parameters, input settings, output settings, alarm settings, tune settings, device settings, profile settings, and steps settings. Refer to the user manual for detailed instructions on accessing and configuring these settings.
Modbus Registers
The device supports Modbus communication and has specific Modbus registers for profile programs and profile steps. These registers can be used for advanced programming and control purposes. Refer to the user manual for more information on Modbus registers and their usage.
Please refer to the user manual for additional information and detailed instructions on using the E-220 device.
E-220
Elimko
User Manual
KY-220-0723-0
Elimko
220
999.9 999.9
DIGITAL
LOGIN
PV
°C
33.0 RL1 RL2
SET
°C RL3
35.0 RL4
-199.9 -199.9
OUT
%
23.5 MNL
SET
Elimko
E-220
Compliance with EU Directives
Low Voltage Directive EN 61010-1
Electromagnetic Compatibility EN 61326
K – Q TSE-ISO-EN
9000
KY-220-0723-0
TS EN ISO 9001 Quality Management System Certificate
E-220
1. DEFINITION
CONTENTS
2. TECHNICAL SPECIFICATIONS
2.1. Input Types
2.2. Type Coding
2.3. Dimensions
2.4. Panel Mounting
2.5. Connection Diagrams
2.6. Front Panel
3. USAGE
3.1. Device Energization and Start Page
3.2. Title Area
3.3. LED Indicators and Meanings
3.4. Operator Pages
3.4.1. ANALOG Operator Page
3.4.2. DIGITAL Operator Page
3.4.3. ALARM SET Operator Page
3.4.4. STATUS Operator Page
3.5. SETTINGS
3.5.1. Setting Parameters
3.5.2. INPUT Page
3.5.3. OUTPUT Page
3.5.4. SET Page
3.5.5. ALARM Page
3.5.6. TUNE Page
3.5.7. DEVICE Page
3.5.8. PROFILE Page
3.5.9. STEPS Page
4. MODBUS REGISTERS
4.1. Profile Programs Modbus Registers
4.2. Profile Steps Modbus Registers
1
Elimko
2 3 4 5 6 7 8 10 11 11 11 13 14 16 18 22 23 24 26 29 34 49 51 54 56 58 59 60
65 66
Elimko
1. DEFINITION
2
E-220
E-220
2. TECHNICAL SPECIFICATIONS
Elimko
Input Types
Control Output
Alarm Outputs Display Type
Accuracy Class
Thermocouple : (±%0.5’i or ±1 oC read value) max. ±1 digit Pt-100 : (±%0.5’i or ±1 oC read value) max. ±1 digit Voltage/Current : ±%0.5 FS max. ±1 digit
Analog-Digital Converter Digital-Analog Converter Control Type
16 bit 16 bit ON/OFF, PID
Operating Voltage
Power Consumption Protection Class Operation Temperature Storage Temperature
7W (10 VA)
Front Panel : IP 66 (NEMA 4X) Back Panel : IP 20 -10 oC, +55 oC (+14 oF, +131
oF) (Without Condensation and Icing)
-25 oC, +65 oC (-13 oF, +149 oF) (Without Condensation and Icing)
Mechanical Life of Relays
Electrical Life of Relays
Weight
430 g
3
Elimko
2.1. Input Types
TEMPERATURE SENSORS
E-220
TYPE-B TYPE-E TYPE-J TYPE-K TYPE-L TYPE-N TYPE-R TYPE-S TYPE-T TYPE-U PT-100
Standard
IEC584-1 IEC584-1 IEC584-1 IEC584-1 DIN43710 IEC584-1 IEC584-1 IEC584-1
IEC584-1 DIN43710 IEC751
(oC)
60 , 1820 -200 , 840 -200 , -200 , 1360 -200 , 900 -200 , 1300
-40 , 1760 -40 , 1760 -200 , 400 -200 , 600 -200 , 840
(oF)
140 , 3308 -328 , 1544 -328 , 1562 -328 , 2480 -328 , 1652
-328 , 2372 104 , 3200 104 , 3200 -328 , 752
-328 , -328 , 1544
LINEAR INPUTS
Type
Current 0-20 mA
Current 4-20 mA
Voltage 0-50 mV
Voltage
0-1 V
Voltage 0.2-1 V
Measurement Range 0-20 mA DC 4-20 mA DC 0-50 mV DC 0-1 V DC 0.2-1 V DC
4
E-220
2.2. Type Coding
W
Elimko
X
Y
Z 5
Elimko
2.3. Dimensions
96 mm
Elimko
220
999.9 999.9
DIGITAL
LOGIN
PV
°C
33.0 RL1 RL2
SET
°C RL3
35.0 RL4
-199.9 -199.9
OUT
%
23.5 MNL
SET
10 mm
96 mm
E-220
91 mm
100 mm
91 mm
91 mm
6
E-220
2.4. Panel Mounting
Elimko
Appropriate fuses or switches must be used in the supply line and power outputs of the devices.
Power supply cables must meet the requirements of IEC 60245 or IEC 60227 standards.
-0.0 92 x 92 mm
+0.5
35 mm min.
10 mm min.
Panel Cut – Out
Open the slot on the panel as shown in the figure above. Place the device in
the slot from the front of the panel. Place the clamps by fitting the clamp
tabs into their slots on
the device. Tighten the screws until the clamps are secured to the panel
surface.
7
Elimko
E-220
2.5. Connection Diagram
Optional features are marked on the connection diagram. Connections must comply with optional features.
Optional features are marked in the connection diagram. Connections must comply with optional specifications.
AO 1
AO 2
SSR1
RL1
01
21
31
11
Digital Inputs
02
22
32
03
+ 23 COM 33
SSR2
RL2
04
24
DI1 34
05
25
DI2 35
12
13
14
External Set
AIN2
0-20 mA
15
4-20 mA
RL3
06
26
DI3 36
16
AIN1
RL4 RS-485 GND TRX+ TRX
07
27
37
17
08
28
38
09
29
39
10
30
20-60VAC; 50-60 Hz / 20-85VDC
18 TC mV mA
19 SM Pot
20
85-265VAC; 50-60 Hz / 85-375VDC
Analog Input 1
Analog Input 2
13
13
14
14
15
15
16
16
17
17
18
18
0-20 mA / 4-20 mA Rezistans Termometre
2 Telli Transmitter
13
13
14
14
15
15
16
16
17
17
18
18
13
13
14
14
15
15
16
16
17 V
17
18
18
8
E-220
Elimko
Do not touch the terminals 01-10 while the device is energized as dangerous
voltage levels are present.
Make sure that the parameters were set for the intended use before
commissioning the device. Incorrect configuration may cause damage.
(*) Digital Input Connection
DI1
Auto/Manual mode selection.
DI2 ve DI3
DI2 DI3 0 / 1 = ON / OFF 00 01 10 11
*AO1, AO2 Analog Outputs, Pulse Output ve Digital Inputs are not isolated from each others.
9
Elimko
2.6. E-220 Front Panel
E-220
Elimko
220
999.9 999.9
DIGITAL
LOGIN
PV
°C
33.0 RL1 RL2
SET
°C RL3
35.0 RL4
-199.9 -199.9
OUT
%
23.5 MNL
SET
Up/Down Buttons
Set Button TFT Display
10
Back Button
E-220
3. USAGE
Elimko
ELIMKO E-220 PID CONTROLLER
Version 01.00
Figure 3.1
Page Name
TITLE AREA
Operator Name
DIGITAL
LOGIN
32.3 PV
°C RL1
RL2
Figure 3.2
11
999.9 999.9
Elimko
E-220
Page Name
PV
SV
OUT
ALARM SET
32.3 20.0 23.5
A1SP °C A2SP
20.0 RL1 RL2
30.0 Figure 3.3
If a valid password is not entered, Operator Name field appears as LOGIN. If a
valid operator password is entered, name of the operator that logged in
appears.
For E-220 devices, switching between operator pages is done with Button.
In the event of an alarm, alarm message flashes on the TITLE AREA. The
predefined alarm messages are listed below.
1 – SENSOR OPEN 2 – SENSOR UFL 3 – SENSOR OFL
12
E-220
Elimko
3.3. LED Indicators and Meaning
On the right-hand side of the operator pages, LED indicators are continuously
displayed. Please see below for the indicator
explantions.
ADMIN
RL1 RL1 is energized.
RL2 RL2 is energized.
RL3 RL3 is energized.
RL4 RL4 is energized.
MNL MANUEL mod is active.
AT
13
Elimko
3.4. Operator Pages
E-220
ANALOG
DIGITAL ALARM SET STATUS
999.9 999.9
DIGITAL
LOGIN
PV
°C
33.0 RL1 RL2
SET
°C RL3
35.0 RL4
OUT
%
23.5 MNL
ALARM SET A1SP °C A2SP °C A3SP °C A4SP °C
32.3 20.0 23.5
20.0 RL1 RL2
30.0 RL3 40.0 RL4
MNL
50.0 AT
-199.9 -199.9
ANALOG
37.5
ADMIN
62.5 RL1
25.0
RL2 Set 75.0
25.0 °C
12.5
RL3 87.5 RL4
°C 75.0
MNL
0.0 % 30.0
100.0
AT
STATUS AOUT1 mA AOUT2 mA POS. % OUT %
32.3 20.0 23.5
20.0 RL1 RL2
12.0 RL3 75.0 RL4
MNL
50.0 AT
14
E-220
Elimko
Press and buttons together to access MENU screen. Press to exit this screen.
SET
MENU
32.3 20.0 23.5
SETTINGS
RL1
RL2
LOGIN
RL3
CLEAR ALARMS
RL4
MNL
AT
15
Elimko
3.4.1. ANALOG Operator Page
E-220
ANALOG
37.5
ADMIN
62.5
RL1
25.0
RL2
Set 75.0
25.0 °C
12.5
RL3 RL4
87.5
°C 75.0
MNL
0.0 % 30.0
100.0
AT
SET POINT LOW
OUT SV PV SET POINT HIGH
16
E-220
Elimko
17
Elimko
E-220
E-220
Elimko
SPAN
999.9 999.9
ALARM 1 MAGENTA
ALARM 2 BLUE
ALARM 3 CYAN
ALARM 4 YELLOW
DIGITAL
LOGIN
PV
°C
30.7 RL1 RL2
SET
°C RL3
40.0 RL4
OUT
%
72.9 MNL
Alarm Set Indicators SV Bar Graph PV Bar Graph
18
ZERO
-199.9 -199.9
SPAN
999.9 999.9
DIGITAL
LOGIN
PV
°C
30.7 RL1 RL2
SET
°C RL3
40.0 RL4
OPEN
CLOSE
Alarm Set Indicators SV Bar Graph PV Bar Graph
19
MNL
ZERO
-199.9 -199.9
Elimko
E-220
E-220
Elimko
999.9 999.9
DIGITAL
PV
SET OUT PRFL
LOGIN
30.7 °C
RL1
°C
40.0 RL2
20.0 RL3
1
Repeat 10 RL4
-199.9 -199.9
RUN HOLD
MNL
1.S 1.0 min. Repeat:10
Step No
Remaining Repetitions
Note: Monitored when the profile is active.
20
21
Elimko
3.4.3. ALARM SET Operator Page
E-220
ALARM SET
A1SP °C A2SP °C A3SP °C A4SP °C
32.3 20.0 23.5
20.0 RL1 RL2
30.0 RL3 40.0 RL4
MNL
50.0 AT
22
E-220
3.4.4. STATUS Operator Page
Elimko
On this operator page AOUT1, AOUT2, Position and OUT values can be monitored.
AOUT1 : Analog Output 1 current value AOUT2 : Analog Ouput 2 current value
POS. : Feedback servo motor position
STATUS
32.3 20.0 23.5
AOUT1 mA AOUT2 mA
20.0 RL1 RL2
12.0 RL3
POS. % OUT %
75.0 RL4 MNL
50.0 AT
23
Elimko
3.5. SETTINGS
E-220
E-220
Elimko
SET
MENU
32.3 20.0 23.5
SET
SETTINGS
RL1
RL2
SET
LOGIN
RL3
SET
CLEAR ALARMS
RL4
MNL SET
AT
24
25
Elimko
3.5.1. Settings Parameters
E-220
SETTINGS page provides access to sub pages where all the device parameters are set. Device parameters are divided into 8 main groups. Depending on the privileges of the logged-in user, the ability to change parameters is limited.
Desired parameter group must be selected by using the and buttons first and after the selection, the selected group is accessed by pressing the button.
SET
SETTINGS
MENU
SETTINGS INPUT SET TUNE STEPS
32.3 20.0 23.5 OUTPUT ALARM PROFILE DEVICE
26
E-220
Elimko
CONTROL SET POINT PROPORTIONAL+ PROPORTIONAL INTEGRAL+ INTEGRAL DERIVATIVE+ DERIVATIVE HYSTERESIS SET POINT LOW SET POINT HIGH
SET POINT RAMP
ALARM SET POINT ALARM HYSTERESIS VALUE ZERO SPAN RETRANSMISSION LOW
RETRANSMISSION HIGH OFFSET PROFILE SET VALUES
27
Elimko
E-220
While on any configuration page, the parameter to be adjusted is selected by using the button. Selected parameter and changed with buttons. 7 parameters can be monitored on each page.
If the button is pressed after coming to the last parameter on the page, it will automatically move to the next page. Page number title displayed in the field. Press while in any parameter. If pressed long, the first parameter on the first page, if pressed short, a the next parameter is passed.
OUTPUT
SET
OUTPUT (1/3) 32.3 20.0 23.5
CONTROL TYPE
SINGLE
SET
CONTROL FORM
REVERSE
SET
PWM PERIOD
sec.
2
SET
MANUEL SWITCH
ON
SET
DEAD BAND
%
0.5
SET
SINGLE OUT LOW
%
0.0
SET
SINGLE OUT HIGH
%
100.0
SET
Figure 3.4 28
E-220
3.5.2. INPUT Page
Elimko
Temperature Sensors
Standard
0 TYPE-B 1 TYPE-E 2 TYPE-J 3 TYPE-K 4 TYPE-L 5 TYPE-N 6 TYPE-R 7 TYPE-S 8
TYPE-T 9 TYPE-U 10 PT-100
0-20 mA 12 4-20 mA 13 0-50 mV 14 0-1 V 15 0.2-1 V
IEC584-1 IEC584-1 IEC584-1 IEC584-1 DIN43710 IEC584-1 IEC584-1 IEC584-1
IEC584-1 DIN43710 IEC751
Current Current Voltage Voltage Voltage
Range
(oC)
(oF)
60 , 1820 140 , 3308 -200 , 840 -328 , 1544
-200 , -200 , 1360 -200 , 900
-328 , 1562 -328 , 2480 -328 , 1652
-200 , 1300 -40 , 1760
-40 , 1760 -200 , 400
-328 , 2372 104 , 3200 104 , 3200
-328 , 752
-200 , 600 -328 , -200 , 840 -328 , 1544
0-20 mA DC 4-20 mA DC 0-50 mV DC
0-1 V DC 0.2-1 V DC
29
Linear Inputs
Elimko
E-220
E-220
Elimko
0-mA, 1-A, 2-kA, 3-mV, 4-V, 5-kV, 6-bar,
7-mbar, 8-kpa, 9-Hz, 10-m3/h, 11-t/s, 12-%RH, 13-m,
14-cm, 15-mm, 16-MW, 17-Kw, 18-W, 19-mW, 20-kohm
30
31
Elimko
E-220
E-220
Elimko
32
33
Elimko
E-220
The following figure shows the feedback valve connection using RL1 and RL2.
Feedback Valve OPEN
PID+ 01
1k-5k
CLOSE
02 PID- 03
04
Supply Voltage
O 19 C 20
E-220
Elimko
Floating Valve OPEN
CLOSE
PID+ 01 02
PID- 03 04
RL1:5A 250VAC 30VDC RL2:5A 250VAC 30VDC
38
39
Elimko
E-220
E-220
Elimko
40
41
Elimko
3.5.3. OUTPUT Page
E-220
E-220
Elimko
34
35
Elimko
E-220
E-220
Elimko
36
37
Elimko
E-220
E-220
Elimko
42
43
Elimko
E-220
E-220
Elimko
44
45
Elimko
E-220
E-220
3.5.5. ALARM Page
Elimko
: Continues without any change. : Profile is holded. : Continues from start of last running step. : Reverts to start of last running step and is holded. : Profile is stopped.
50
51
Elimko
ALARM TYPE
DESCRIPTION
ALARM SET > 0
ALARM SET < 0
Alarm Status 1
Alarm Status 1
E-220
LOW
0
0
ASP
Alarm Status 1
PV PV
0
ASP
0
Alarm Status 1
HIGH
0
0
ASP
Alarm Status 1
0
PV
ASP
0
Alarm Status 1
LOW (SV+ASP)
0
0
0
SV SV+ASP PV
0
SV-ASP SV
PV
Alarm Status 1
Alarm Status 1
HIGH (SV+ASP)
0
0
0
SV SP+ASP PV
0
SV-ASP SV
PV
Alarm Status 1
Alarm Status 1
HIGH BAND LOW BAND
0
0
0 SV-ASP SV SV+ASP PV
0
SV
PV
Alarm Status 1
Alarm Status 1
0
0
0 SV-ASP SV SV+ASP PV
0
SV
PV
OFF
When ALARM TYPE parameter is set to OFF, the alarm function is canceled.
Hysteresis
The hatched area in the graphs indicates the hysteresis.
Alarm Status 1
0 0
If the alarm status is “1”, the output (relay) PV is active.
Figure 3.5 52
E-220
Elimko
ALARM HYSTERESIS Determines the alarm hysteresis value. It can be set between
0 and 9999. This parameter is not monitored if ALARM TYPE is OFF. ALARM LATCH
If ALARM LATCH is set to ON, the alarm signal is not cleared even if the alarm
condition is released after the alarm has been detected. To clear the alarm
signal, press the button.
0-OFF 1-ON can be selected. This parameter is not monitored if ALARM TYPE is
OFF.
53
Elimko
E-220
AO1 SOURCE, AO2 SOURCE
Analog Output Function Selections
These are the parameters that determine which signals will be taken from 2
analog outputs in the device.
0-PID+ (PID control output in “+” direction) 1-PID- (PID control output in “-”
direction) 2-PV (Process value retransmission) 3-SET (Set point
retransmission) can be selected.
The output range of analog outputs is determined by parameters AO1 RANGE and
AO2 RANGE. The retransmission scale for PID+ selection is 0% and 100%. The
retransmission scale for PID- is 0% and -100%. The process value and setpoint
retransmission scale is determined by the RETRANSMISSION LOW and
RETRANSMISSION HIGH parameters.
46
E-220
Elimko
AO1 RANGE, AO2 RANGE
Analog Output Signal Range
0- 0-20 mA, 1- 20-0 mA, 2- 4-20 mA, 3- 20-4 mA,
4- 0-10 V, 5- 10-0 V, 6- 2-10 V, 7- 10-2 V
can be selected.
For a detailed description of this parameter, see the AO1 SOURCE, AO2 SOURCE parameters.
RETRANSMISSION LOW
Retransmission Low Limit.
It can be set between -1999 and RETRANSMISSION HIGH.
For a detailed description of this parameter, see the AO1 SOURCE, AO2 SOURCE parameters.
RETRANSMISSION HIGH
Retransmission High Limit.
It can be set between RETRANSMISSION LOW and 9999.
For adetailed description of this parameter, see the AO1 SOURCE, AO2 SOURCE parameters.
47
Elimko
E-220
E-220
3.5.4. SET Page
Elimko
DI2 DI3 0 / 1 = ON / OFF 0 0 DIGITAL SET1
0 1 DIGITAL SET2
1 0 DIGITAL SET3 1 1 DIGITAL SET4
48
49
Elimko
3.5.6. TUNE Page
E-220
E-220
Elimko
SV SV – HYSTERESIS
OUT
%100 %0
%100 %0
54
55
Elimko
E-220
E-220
Elimko
56
57
Elimko
3.5.8. PROFILE Page
3.5.9. STEPS Page
E-220
E-220
3.5.9. STEPS Page
SV (EU) Step N SET
Elimko
Step 2 SET
Step 1 SET PV
Step 1 Step 2 TIME TIME
Step N TIME
Time (min)
Profile Start
Control Outputs Active
Profile End
58
59
Elimko
E-220
4. MODBUS REGISTERS
Table 4.1 Address Description
0 Status Bits 1 (Table 4.3)
1 Status Bits 2 (Table 4.3)
Setting Permission Min.
OFF
0
OFF
0
Max. 0 0
2 PV (Process Value)
OFF
0
0
3 SV (Set Point)
OFF
0
0
4 Running Profile Number 5 Profile Remaining Repetition
OFF OFF
0
0
0
0
6 Running Step Number
OFF
0
0
7 Step End Remaining Time
OFF
0
0
8
OFF
0
0
9 SET POINT SOURCE
OFF
0
0
10
OFF
0
0
11 OUT (Output Value)
ON -1000 1000
12 SV (Set Point)
ON -1999 9999
13 AUTO TUNE
ON
0
1
14 Profile selection
ON
1
9
15 Profile repeat selection (0=Cont.) ON
1
9
16-35 see Section 4.1
36 PROPORTIONAL+
ON
1 9999
60
E-220
Address Description 37 PROPORTIONAL38 INTEGRAL+ 39 DERIVATIVE+ 40 HYSTERESIS
41 SET POINT SOURCE 42 SET POINT LOW 43 SET POINT HIGH 44 SET POINT RAMP 45 46
47 48 49 PROFILE POWERON 50
51 ALARM 1 HYSTERESIS 52 53 ALARM 1 SET 54 55 ALARM 2 HYSTERESIS 56
61
Elimko
Setting Permission Min.
Max.
ON
1 9999
ON
0 9999
ON
0 2500
ON
0 9999
ON
0
2
ON -1999 9999
ON -1999 9999
ON
0 600
ON -1999 9999
ON -1999 9999
ON -1999 9999
ON -1999 9999
ON
0
4
ON
0
6
ON
0 9999
ON
0
1
ON -1999 9999
ON
0
6
ON
0 9999
ON
0
1
Elimko
Address Description
57 ALARM 2 SET 58 ALARM 3 TYPE 59 ALARM 3 HYSTERESIS 60 ALARM 3 LATCH 61 ALARM
3 SET 62 ALARM 4 TYPE 63 ALARM 4 HYSTERESIS 64 ALARM 4 LATCH 65 ALARM 4 SET 66
CONTROL TYPE 67 CONTROL FORM 68 PWM PERIOD 69 MANUAL SWITCH 70 71 DEAD BAND 72
SINGLE OUT LOW 73 SINGLE OUT HIGH 74 SINGLE MNL. RESET
E-220
Setting Permission Min.
ON -1999
ON
0
ON
0
ON
0
ON -1999
ON
0
ON
0
ON
0
ON -1999
ON
0
ON
0
ON
1
ON
0
ON
10
ON
1
ON
0
ON
0
ON
0
Max. 9999
6 9999
1 9999
6 9999
1 9999
4 1 250 1 2500 250 1000 1000 1000
E-220
Address Description
75 DOUBLE OUT LOW 76 DOUBLE OUT HIGH 77 DOUBLE MNL. RESET 78 POWER ON ACTION
79 RL1 SOURCE 80 RL2 SOURCE 81 RL3 SOURCE 82 RL4 SOURCE 83 AO1 SOURCE 84 AO2
SOURCE 85 AO1 RANGE 86 AO2 RANGE 87 ANALOG INPUT 1 88 ANALOG INPUT 2 89
DECIMAL POINT 90 ZERO 91 92 RETRANSMISSION LOW
Elimko
Setting Permission Min.
ON -1000
ON -1000
ON -1000
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
0
ON
1
ON -1999
ON -1999
ON -1999
Max. 1000 1000 1000
4 14 14 14 14
3 3 3 3 15 1 3 9999 9999 9999
Elimko
Address Description
93 RETRANSMISSION HIGH 94 95 OFFSET 96 FILTER 97 SENSOR BREAK 98 LANGUAGE 99
BRIGHTNESS 100 LINEAR UNIT 101 MODBUS ADDRESS 102 BAUD RATE 103 PARITY 104
INTEGRAL105 DERIVATIVE106 RESERVED 107 RESERVED 108 RESERVED 109 RESERVED 110
RESERVED
E-220
Setting Permission Min.
ON -1999
Max. 9999
ON
0
1
ON -1000 1000
ON
1 100
ON
0
1
ON
0
1
ON
0 100
ON
0 100
ON
1
32
ON
0
3
ON
0
2
ON
0 2500
ON OFF
0 2500
0
0
OFF
0
0
OFF
0
0
OFF
0
0
OFF
0
0
64
E-220
4.1. Profile Programs Modbus Registers
Setting
Address Description
Permission
16 Reserve
ON
17 Reserve
ON
18 PROFILE1 START STEP
ON
19 PROFILE1 END STEP
ON
20 PROFILE2 START STEP
ON
21 PROFILE2 END STEP
ON
22 PROFILE3 START STEP
ON
23 PROFILE3 END STEP
ON
24 PROFILE4 START STEP
ON
25 PROFILE4 END STEP
ON
26 PROFILE5 START STEP
ON
27 PROFILE5 END STEP
ON
28 PROFILE6 START STEP
ON
29 PROFILE6 END STEP
ON
30 PROFILE7 START STEP
ON
31 PROFILE7 END STEP
ON
32 PROFILE8 START STEP
ON
33 PROFILE8 END STEP
ON
34 PROFILE9 START STEP
ON
35 PROFILE9 END STEP
ON
65
Elimko
Min. 1
Max. 99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
1
99
Elimko
E-220
4.2. Profile Steps Modbus Registers
Address Description
Setting Permission Min.
Max.
200+4n
ON
0 9999
201+4n 202+4n 203+4n
ON -1999 9999
ON
0
63
ON
0 9999
Table 4.2
Bit 0:OFF 1: ON
0 ALARM A
1 ALARM B
2 ALARM C 3 ALARM D
4
ALARM O
If the deviation during the step is more than the step hysteresis, holds and gives ALARM O.
5 ALARM H Holds at the beginning of the step and gives ALARM H.
66
E-220
Elimko
Table 4.3 Status Bits 1 Bit Description (for 1 ) 0 1.Relay (RL1) Energized 1
2.Relay ( RL2 ) Energized 2 3.Relay ( RL3 ) Energized 3 4.Relay ( RL4 )
Energized 4 Sensor Break 5 Sensor OFL 6 Sensor UFL 7 Manual 8 9 10 Reserved 11
Reserved
12 Reserved 13 Reserved 14 Reserved 15 Reserved
Status Bits 2 Bit Description (for 1 ) 0 Digital Input 1 1 Digital Input 2 2
Digital Input 3 3 Reserved 4 Alarm 1 5 Alarm 2 6 Alarm 3 7 Alarm 4 8 Reserved
9 Reserved 10 Reserved 11 Reserved
12 Reserved 13 Reserved 14 Reserved 15 Reserved
Address Permission
0
ON
1
ON
2
ON
3
ON
4
ON
Table 4.4 Description Manual/Auto
0 (Reset) 1 (Set) Auto Manual Open Close Stop Start
Continue Hold
67