User and Installation guide
Temperature Controller
UTE 4100-R/-F/-Rw
UTE 4100 Temperature Controller
Functional principle
The UTE 4100 temperature controller makes it possible to switch easily between
comfort temperature = T+ and setback temperature = T-. In addition, the
temperature can be lowered automatically via an external timer.
After installation, the temperature is regulated to comfort temperature and
the current room temperature is displayed.
The temperature is controlled depending on the room temperature measured by
the internal or remote sensor. The heating is switched on when the temperature
drops below the set value.
Installation
Attention!
The device may only be opened by a qualified electrician and installed in
accordance with the circuit diagram in the housing cover or these
instructions. The existing safety regulations must be observed.
In order to achieve the requirements of protection class II, appropriate
installation measures must be taken.
This independently mountable electronic device is used to control the
temperature exclusively in dry and closed rooms, with usual environment. The
device complies with EN 60730, it operates according to the mode of action 1C.
Use
R-variant:
For controlling the room temperature in combination with:
- Actuators for floor and convector heating systems
- Oil or gas warm heating systems
- Circulation pumps
- Heat pumps
F-variant:
For control of floor temperature in combination with:
- Direct floor heating
- Floor temperature control system
Rw-variant:
For controlling the room temperature in combination with:
- Actuators for floor and convector heating systems
- Oil or gas hot water heating systems
- Heat pumps
- Underfloor heating with heating/cooling changeover
- Suitable for use with the terminal strip heating/cooling EV 230 H/C…
Features
- Single-line text display for simplified operation
- Backlighting
- Simple switching between 2 temperatures (e.g. comfort and setback temperature)
- Energy consumption display (heating on time * cost) for last 2 days, -week, -month, -year (Only for -R and -F variants).
- ECO input to activate a freely adjustable temperature, e.g. for night setback
- Time limit for manually selected temperature possible
- Adjustable when control panel is removed
- Short-time timer (party) for changing the temperature by the hour
- Temperature setting range can be limited
- Unauthorized person protection
- Operator languages adjustable
- Controller method PWM or 2-point (on/off)
- Minimum switch-on or switch-off time and hysteresis of the output adjustable, for on/off control
- Valve protection (R- and Rw-Variant only)
- Adaptation to valves normally closed/open (R- and Rw-Variant only)
- Measurement of room temperature via built-in or remote sensor
Mounting
The controller should be mounted in a location in the room that:
- is easily accessible for operation
- is free from curtains, cabinets, shelves, etc.
- allows free air circulation
- is free from direct sunlight
- is free from drafts (e.g. opening windows/doors)
- is not directly influenced by the heat source
- is not located on an outside wall
- is approx. 1.5 m above the floor
Fitting in a conduit box Ø 60 mm
- remove the display unit
- remove the frame
- Mount in following the reverse procedure
Caution!
Mounting in plastic wall boxes only
Technical Data
Order Type | UTE 4100-R | UTE 4100-F | UTE 4100-Rw |
---|---|---|---|
Supply voltage | 230 V 50 Hz (195 … 253 V) | 230 V 50 Hz (207 … 253 V) | 230 V 50 |
Hz (195…253 V)
Temperature setting range| 5 °C … 30 °C; in 0,5 °C steps| 10 °C … 40 °C; in
0,5 °C steps| 5 °C … 30 °C; in 0,5 °C steps
Temperature resolution| 0,1 °C steps
Output| Relay NO contact| Relais change over contact
Switching current| 10 mA … 10 (4) A, 230 V~| 10 mA … 16 (4) A*, 230 V~|
Heating: 10 mA … 5 (2) A, 230 V~
Cooling: 10 mA … 1 (1) A, 230 V~
Output signal| PWM (Pulse Width modulation) or ON/OFF
PWM cycle time| adjustable
Hysteresis| adjustable (ON/OFF only)
ECO-Input| e.g. for night set-back via external clock (230V Input), can be
extended up to 50 m| e.g. for night set-back via external clock (230V Input),
can be extended up to 10 m
Power consumption| ~ 1,2 W
Remote sensor| F 193 720, length 4 m,
F 190 021. Both can be extended up to 50 m (optional).| F 193 720, length 4 m.
Can be extended up to 50 m.| F 193 720, length 4 m, F 190 021.
Both can be extended up to 50 m (optional).
Ambient temperature| Operating 0 °C … 40 °C (without condensation)
Storage –20 °C … 70 °C (without condensation)
Rated impulse voltage| 4 kV
Ball pressure test temperature| 75 ± 2 °C
Voltage and Current for the purposes of interference mea- surements| 230 V,
0,1 A
Degree of protection| IP 30
Protection class of housing| II (see Caution)
Software class| A
Tightening Torque| 0,5 Nm
Pollution degree| 2
Weight| ~ 100 g| ~ 280 g (with remote sensor)| ~ 100 g
Energy class| IV = 2 %
814/2013)
(acc. EU 811/2013, 812/2013, 813/2013,
- For current > 14 A do not loop the N-wire through the controller, use a separate terminal.
Electrical connection
Caution: Disconnect electric circuit from supply
Connection according to Wiring Diagram
For flexible or solid wires 1 – 2,5 mm2
Connecting the remote sensor F 193 720 or F 190 021 (optional)
In order to measure the room temperature, instead of the internal sensor, an external one can be used.
Remote or internal sensor selection can be made via menu item H1.
Lay sensor inside a protective tube (simplifies replacement). The sensor lead can be extended up to 50 m by using a cable and connections suitable for 230 V. Avoid laying sensor cable alongside power cables, for example inside a conduit.
Caution! The Sensor is at mains voltage.
Circuit diagrams
UTE 4800-R UTE 4800-F UTE 4800-Rw
Dimensions
Remote sensor F 193 720 (as accessory) Remote sensor F 190 021 (as accessory)
ECO-Input
Via the ECO-Input the floor temperature can be controlled to an energy saving
temperature (e.g. via an external timer). The temperature can be adjusted by
using + – keys (display then T*). This mode will be indicated on the screen as
„ECO”.
Via key T+/T– a change over between the temperatures T+, T–, ECO will bei
possible.
If ECO input becomes inactive, T+ will be actived.
Note: TIMER will not be cancelled, ECO will be delayed accordingly.
Notes for adjustment
- Activated settings terminate automatically 3 min after the last key press, without saving. They return to the mode which was active before entering the settings, e.g. T+, T–, T*, ECO.
- Entering a Code: change value with + – key then press OK
- When going through User- or Installer settings the item num- ber used in the manual will be displayed, e.g. G1 for „T+ Setting” or H2 for „Control Mode”.
- There may be gaps in the sequence of menu numbers.
Troubleshooting
-
The controller does not accept any changes.
Is access protection switched on? See G6. -
The range of temperature setting is limited.
Are temperature limits set? See G7. -
Temperature display doesn’t change.
Is display of set-temperature activated? See G10.
Descriptions of Functions and Operation
Selecting language
Only for products where no language is pre-set, the user has to set up his
language by doing this:
This input is only requested at first start or Reset)
+ – to select language
2 x OK to accept -> T+ will be displayed (to change language again use menu
G14)
How the Temperature Controller can be used
T+| Control room to Comfort-Temperature, use key T + (Menu CONTROL)
Temperature can be pre-set via menu G1| Set temperature for a numer hours see
Menu, TIMER
---|---|---
T–| Control room to Set-Back-Temperature key T – (Menu CONTROL)
Temperature can bei pre-set via menu G2| Adjust the controller to personal
needs see Menu, USER-SETTINGS
T*| Control room to an other Temperature, use keys + – (Menu
CONTROL) (valid until T+, T-, ECO)| Adjust the controller to application needs
see Menu, INSTALLER-SETTINGS
ECO| Control room automatically to ECO-Temperature, via ECO-input (Menu
CONTROL9 Temperature can bei pre-set via menu H7|
| Keys| | to confirm*
---|---|---|---
| T+/T-| Change over between Comfort- (T+) and Set-Back (T-) Temperature, the
controlled temperature will be displayed for a short period time. Pre-set via
menu G1, G2.|
| + – while T+, T–, ECO| Choose a different temperature other than T+, T–,
ECO, displayed as T. A single press of + or – key will show the set
temperature, V to terminate.| OK
| + – in menu| Scroll through the menu.|
| OK| Accepts modification / selection.|
| Menu| Enter menus + – key to move.|
| V| Go one step back.|
| V for 10 sec (R- and F-Variant only)| Switch off connected load. Display
shows OFF. Detail is see G4.|
| Main Menu| | to confirm*
---|---|---|---
A| MENU| Use + – in order to navigate through the menu|
B| CONTROL| Temperature will bei controlled to:
T+ = Comfort-Temperatur
T– = Set-Back Temperature
ECO = via ECO-Input activated Temperature
T = with keys + – selected temperature|
D| TIMER| The temperature will be controlled temporarily according to the
hours and temperature set in this menu.
When terminating TIMER mode, the previously active mode will be re-activated.
To terminate timer manually select menu CONTROL.| OK
G| USER SETTINGS| Customise the controller according to personal
requirements.| OK
H| INSTALLER SETTINGS| Customise the controller according to application
requirements (from installer only).| OK
G| USER SETTINGS| Customise the controller according to personal
requirements| default settings ( ) = value range
---|---|---|---
1| Set T+| Pre-set Comfort Temperature.| 21 °C (5 … 30 °C)
2| Set T-| Pre-set Set-Back Temperature| 18 °C (5 … 30 °C)
4| Off-Heating permanent
(R- and F-Variant only)| Switch off the heater, the controller remains on
power. Display reading OFF. Frost protection may happen if selected. See H6.
Switching ON again by activating e. g. Mode/Menu CONTROL or by pressing key V
for 10 sec. When re-activating via key V or this menu, T+ will be activated.
Pressing OK will show details for frost protection.| NO
5| T Max Duration| Sets the max. duration for T. E.g. settings to 3 h: after
3 h the previous used temperature T+, T–, ECO will be used.| OFF (OFF, 1 …
23h)
6| Key Lock| Protect controller against unauthorised use. Re-activate via code
= 93.| NO
7| Temperature limits min/max| Limits the temperature which can bei set by the
user, if both values are the same, no adjustement is possible. This affects
Mode/Menu CONTROL. T+, T–, ECO will not be affected automatically.| 5; 30 °C
8| Cost/Hr for Energy
(R- and F-Variant only)| The assumed energy cost per hour (in cent/h) can bei
set. To use this feature as hour counter set the cost to 100 cent/h.| 100 (1 …
999)
9| Energy consumption to date
(R- and F-Variant only)| Show the approximate energy cost of the controlled
area. For the last: 2 days, week (7 days), month (30 days), year (365 days).
On the actual day, calculation is up to current time. In case of overflow 9999
will be displayed. This feature mainly can bei used for electric heating.
Calculation: On-Time of heater x cost per hour see above. Reset see H9.|
10| Set temperature to read| Show set temperature instead of room
temperature.| NO
11| Adjust temperature
(R- and Rw-Variant only)| Adjust temperature to personal needs.| 0.0 (-5,0 …
+5,0)
12| Number for floor temperature
(F-Variant only)| Read the floor temperature as number.
Instead of a temerature in °C a number will be displayed e.g. instead of
285°C, 285 an be read| NO
13| Backlight| Continuously OFF or temporarily illuminates after key press. In
case of using a remote sensor, the backlight can be sat to continuous on.|
SHORT (SHORT, OFF)
14| Language| Select preferred operating language.|
15| Info| Displays Controller-type and -version.|
16| Reset user settings only| Only USER SETTINGS will be set to factory
settings.
R- and F-Variant only: The energy counter will not be reset; to do this see
H9.| NO
Change INSTALLER SETTINGS
CAUTION! These settings should only be set-up by a qualified person. They
can influence safety and the proper functioning of the system.
H| INSTALLER SETTINGS| Customise the controller according application needs
(by installer only)| default settings ( ) = value range
---|---|---|---
0| Code| Enter Code (= 7) in order to access the menus. It is valid for 1
hour.|
1| Application| This controller is suitable for the heating system mentioned
on right column| ROOM / FLOOR / NO see 1
2| Control Mode| PWM or ON/OFF can be selected. In case of PWM, the cycle time
can be set (in Minutes). Min ON/OFF time = 10% of cycle time. Use short time
for fast and longer time for slow reacting heating systems. PWM ist not
possible with COOLING (H4).
For ON/OFF you can select:
• Hysteresis (OFF = no temperature hysteresis, even at very low changes of
temp. the relay will switch over according to the Min On/Off Time setting.)
• Min On/Off Time (the minimum duration for the relay to be On or Off)| PWM/10
(/10 … 30)
OFF (OFF, 0,1… 5.0)
10 min (1.. 30)
4| Heating or Cooling
(R-Variant only)| Heating: Controller works in Heating mode.
Cooling: Controller works in cooling mode. Conditions:
• Cooling is only possible if application (H1) = ROOM
• Frost protection (H6) = NO (can not be activated)
• In case of error = no cooling
• Only for control mode ON/OFF (H2).|
5| Valve protection
(R- and Rw-Variant only)| The output will be activated for the specified time.
This will be repeated every 24 hours, calculated from the last power on or
Reset (H11).| 3 min (OFF, 1 … 10)
6| Frost protection
(R- and F-Variant only)| Set frost protection temperature. Only if controller
is switched OFF, the temperature will be controlled to the value.| 5° (OFF, 5
… 30)
7| ECO Temp. Setting| Setting Pre-set ECO temperature see 8. (Will be used if
ECO-input becomes active.)| 18 °C (5 … 30 °C)
8| Valves NO
(R- and Rw-Variant only)| NO if valves normally open have to be used.| NO
9| Energy Counter Reset
(R- and F-Variant only)| The energy counter will be set to 0.| NO
11| Reset all| All INSTALLER and USER settings will be set to its factory
setting.| NO
12| EN 50559 interrupt
(F-Variant only)| Interrupts heating after continous heating of 1 hr for this
adjusted time| 5 Min (0…20 Min)
Error Indication
In case of errors, «Err» is blinking. The following errors can be displayed:
CONFIGURATION| Display- and powermodule do not fit
→ use only suitable parts
→ switch off and on power supply
---|---
COMMUNICATION| Communication between display- and power unit fails
→ unplug and re-plug display unit
→ switch off and on power supply
EXT SENSOR| 1. Error of remote sensor
→ replace sensor
2. Over- or under run of valid display range
R- und F-Variant only:
If H4 = Heating: On all these errors, heating will be activated with 30 % of
time
If H4 = cooling: On all these errors = no cooling
Resistance values for remote sensor
Temperature | Resistance | Temperature | Resistance |
---|---|---|---|
10 °C | 66,8 kΩ | 30 °C | 26,3 kΩ |
20 °C | 41,3 kΩ | 40 °C | 17,0 kΩ |
25 °C | 33 kΩ | 50 °C | 11,3 kΩ |
Recycling
This product should not be disposed of with household waste.
Please recycle the products where facilities for electronic waste exist. Check
with your local authorities for recycling advice.