e-eberle EOR-3DS Earth Fault and Short Circuit Indicator Installation Guide
- June 13, 2024
- e-eberle
Table of Contents
e-eberle EOR-3DS Earth Fault and Short Circuit Indicator
Product Information
This product is an Earth Fault and Short Circuit Indicator manufactured by A. Eberle GmbH & Co. KG. The model number of this indicator is EOR-3DS. For more detailed operating instructions, please visit the website www.a-eberle.de.
Contact Information:
- Telephone: +49 (0) 911 / 62 81 08 0
- Telefax: +49 (0) 911 / 62 81 08 99
- Email: info@a-eberle.de
- Website: www.a-eberle.de
Product Usage Instructions
Installation
- Follow the installation instructions provided by the manufacturer.
Operation / Display
- Always keep the operating instructions with the unit.
- Ensure that the device is never operated in a damaged or compromised condition.
- Only allow specialized personnel to operate the unit.
- Connect the device according to the manufacturer’s installation instructions.
- Do not operate the device beyond its stated ratings.
- Avoid installing or operating the device in environments where explosive gases, dust, or vapors may be present.
- Ensure that protective covers are always in place and functional.
- Observe the five safety regulations according to DIN VDE 0105.
- Clean the appliance only with commercially available detergents.
Please note that these installation instructions may not always contain the latest information. It is recommended to check the manufacturer’s website for the most up-to-date version of the instructions.
For any warranty claims, please contact A. Eberle GmbH & Co KG in Nuremberg or use the RMA formular on their website www.a-eberle.de. For disposal of old devices, refer to the information provided on the manufacturer’s homepage: https://www.a-eberle.de/ueber-uns/ruecknahme- recycling/.
General Information
General Information
This installati on manual contains all important information regarding
mounting and commissioning. Read this manual carefully and completely as it
contains important information about the product. Use this information and
obey the security details and warnings. Store this manual securely and make
sure that it is always available to the product operator.
The company A. Eberle GmbH & Co. KG does not accept any liability for damage
or losses of any kind arising from noncompliance with this information as well
as print-ing errors or changes in this manual. Furthermore, the company A.
Eberle GmbH & Co. KG will not accept any liability for loss or damage of any
kind resulting from faulty equipment or devices that have been modified by the
user.
Changes
Please notice that these installation instructions may not always contain the
latest information concerning the device. If, for example, the firmware
version has changed, then the present description may be incorrect in some
points.
In this case please contact us or use the current version of this document and
any additional documents concerning this device on our website
(www.a-eberle.de).
Copyright 2023 A. Eberle GmbH & Co. KG
Changes reserved.
Disposal
Directive 2012/19/EU, better known as the WEEE2 directive, deals with the
return and recycling of electronic waste and electrical equipment in order to
recover valuable raw materials. This concerns all
Eberle products marked with the symbol of a waste garbage can shown.
Our WEEE registration number is: DE 37396879
For old devices please also note the information on our homepage:
https://www.a-eberle.de/ueber-uns/ruecknahme-recycling/
Warranty
We guarantee that every product of A. Eberle GmbH & Co. KG is free of material
and manufacturing defects under normal use. The detailed conditions for the
warranty can be found in our general terms and conditions of business under:
https://www.a-eberle.de/agbs/
To claim warranty, please contact A. Eberle GmbH & Co KG in Nuremberg or use
the RMA formular on our homepage under
www.a-eberle.de.
Safety details
Safety instructions
IT IS IMPORTANT TO OBEY THESE INSTRUCTIONS IN ORDER TO ENSURE THE SAFETY OF
INDIVIDUALS. THESE INSTRUCTIONS ARE TO BE STORED SECURELY!
These installation instructions do not contain every safety detail necessary for op-erating the device. Special operating conditions may require additional measures. These installation instructions contain references that have to be obeyed for your personal safety and to prevent property damage.
Structure of warnings
Warnings are structured as follows:
SIGNAL WORD
Nature and source of the danger. Consequences of non-compliance.
- Measures to avoid the danger.
Types of warnings
Warnings are distinguished by the type of danger they are warning against:
DANGER!
Warns of imminent danger that can result in death or serious injuries if not
avoided.
WARNING!
Warns of a potentially dangerous situation that can result in death or serious
injuries when not avoided.
CAUTION!
Warns of a potentially dangerous situation that can result in fairly serious
or minor injuries when not avoided.
NOTICE!
Warns of a potentially dangerous situation that if not avoided could result in
material or environmental damage.
Tips on the appropriate device use and recommendations
Intended use
The Earth Fault and Short Circuit Indicator EOR-3DS is intended for fixed
installation and the continual measurement, monitoring and evaluation of
voltages and currents.
The EOR-3DS is exclusively intended for use in electrical power engineering
facilities and installations, where professionals carry out the necessary
work. Professionals are defined as people who are familiar with the
installation, assembly, commissioning and operation of such products. They
have qualifications that meet the requirements of their activities.
The earth fault and short circuit indicator EOR-3DS complies with the laws,
rules and standards applicable at the time of delivery, in particular with
relevant safety and health requirements.
In order to maintain this condition and ensure safe operation, the operator
must follow all the instructions and warnings in the user manual and the
technical data must be observed.
A. Eberle GmbH & Co. KG accepts no liability for damage resulting from
unauthorized or improper modification or use of the product. Improper
modifications of the product without consultation with A. Eberle GmbH & Co. KG
can lead to personal injury, property damage and malfunctions.
The EOR-3DS is suitable for the following sites of installation and may only
be operated in these locations:
- Switch panel mounting
- DIN rail mounting
Other applicable documents
For safe and correct use of the facility also notice the additional documents,
e. g. the complete operating instructions and included documents as well as
effective standards and laws.
Target group
The installation manual is intended for skilled technicians and trained and
certified operators. The contents of this installation manual must be
accessible to people tasked with the installation and operation of the system.
To avoid personal or prop-erty damage the operating personnel must be an
electrically trained person with the following knowledge.
- Knowledge of national accident prevention guidelines
- Knowledge of standards in safety engineering
- Knowledge of installation, commissioning and operation
Cleaning instructions
Use a soft, slightly damp, lint-free cloth. Make sure no liquid gets in the
housing. Do not use window cleaners, sprays, dissolvent, cleaners that contain
alcohol, am-monia solutions or abrasive cleaning agents.
Only use water for cleaning.
Meaning of the symbols in use
- CAUTION – DANGER! Read the operating instructions and security details
- Functional ground of the measuring device
- Service adapter connection
- TCP-IP interface
- The CE label guarantees the adherence of europeans directives and the regulations concerning the EMV.
- The UKCA label guarantees the adherence of respective regulations in the United Kingdom.
- The CMIM label guarantees the adherence of safety standards for electronic products in Morocco.
- DC Voltage
- WEEE2 label, see chapter 1.3
Commissioning
EOR-3DS short description
The EOR-3DS combines earth fault and short circuit location in a compact
device. The advantages of various locating methods can be used and
prioritized. The device has been developed for locating on one feeder. Through
a multitude of SCADA protocols, SPS functionality, the use of monostable
relays and IT-security features the EOR-3DS is especially designed for the use
in intelligent secondary substations.
Scope of delivery
The EOR-3DS’s scope of delivery includes a display unit for indication and
localization of short circuits and earth faults. Depending on the order
characteristics ‚C‘ and ‚U‘ the device is delivered with different measurement
cards and / or additional current and voltage adapters. In addition, depending
on the order characteristic ‚U‘, the device has a RJ45 port.
- EOR-3DS possibly including C21/C25 and / or U10 Adapter
- Installation instructions
- Additionally ordered adapter cables and service adapters
- Additionally ordered case adapters for DIN rail mounting
Mounting
The EOR-3DS is designed for mounting in a compact switch gear. It is mounted
in a control panel cut out or with an additional available housing adapter on
a DIN rail.
The cut out needs the following dimensions: 92+0,8 x 45+0,6 mm.
The EOR-3DS has metal brackets on the top and bottom, as well as plastic
brackets on the side. When correctly mounted these brackets lock in place in
the cutout. The plastic brackets have to be removed to dismount the device.
To mount the DIN rail adapter the four screws on the back of the EOR-3DS have to be removed. Afterwards the rail adapter can be mounted using the provided, longer screws. There are two additional provided braces that can be used to sup-port the device additionally.
Connect the braces to the outside of the adapter. Put the slot nut into the
slot. Afterwards the screw can be mounted and the device can be aligned
horizontally.
Attach the optional C21 and C25 current adapters onto the device. The optional
U10 voltage adapter is designed for DIN rail mounting.
NOTICE! Property damage by failure to comply to the mounting instructions
The device can be damaged by disregarding the mounting instructions or through
incorrect mounting!
Ground connection
The device contains a functional ground that is also used as a reference
potential for voltage measurement with order characteristic C31/U31.
The functional ground is labeled on the measurement device.
Connect the ground cable with the connector on the EOR-3DS. Use a PE flat
connector (6.3 mm). Notice the additional instructions in chapter 5.23.
DANGER! Risk of death through electric shock!
The incorrect connection of this measuring device can lead to death, serious
injuries or risk of fire.
- The functional ground must always be connected to the PE potential
- Under no conditions the functional ground can carry dangerous voltage
Supply voltage
The connection of EOR-3DS power supply is identical for all devices as there
is only one power supply version (feature H23) available. The EOR-3DS has a
wide range power supply that can be used in the range between DC 20…148 V. The
power supply is protected against polarity reversal, i. e. a connection with
reverse polarity on terminals X2-1 and X2-3 in the range of the permitted
operating volt-age does not damage the device. The terminal X2 is located on
the back of the device in the upper right corner, as shown in the following
image. A detailed connection description (e. g. wire cross section) can be
found in chapter 5.23.
DANGER!
Risk of death through electric shock!
Serious injuries or death can occur by:
- Touching blank or not insulated live wires
- Touching hazardous connectors on the device
- Assemble / disassemble Ethe device only in voltage free state
- Make sure all wires are connected and strain-relieved.
- The cable requirements of all connector blocks have to be met.
After connection and switch on of the supply voltage the power LED will show a green light and the device will start. As soon as the device is operable, the status LED will light up green. The LED layout can be found in chapter 4.1. The terminal assignment can be found in chapter 5.23.
NOTICE!
Property damage due to disregarding the terminal assignment or improper
voltages!
By disregarding the terminal assignment or exceeding the permitted voltage
range the device can be damaged or destroyed. Make sure to follow these
instructions bevor connecting the device to the supply voltage:
- Voltage and frequencies have to correspond to the identification plate! Obey limits according to the technical specifications in chapter 5.
- Do not take the supply voltage from the voltage transducer.
Variants in connecting the measurement inputs
NOTICE! Personal or property damage due to disregarding the safety
instructions
Please read this manual carefully before connecting the terminals and obey the
given safety instructions.
The EOR-3DS can be connected to low power sensors and classic (inductive)
trans-ducers. The suitable analog input is selected during order process
(order characteristics ‘C’ and ‘U’). For technical data of the different
analog inputs please refer to the latest EOR-3DS data sheet or chapter 5.
The EOR-3DS has a maximum of four voltage inputs and four current inputs.
Hereby three phase voltages and three phase currents as well as the zero
sequence voltage (Uen) and the zero sequence current (3I0) can be measured.
The following chapter explains the connection of the measuring transformer and
low power sensors depending on the chosen features.
Notice the technical specifications when connecting the different ‚C‘ and ‚U‘
features (chapter 5).
Connecting low power sensors LR/LRM systems
DANGER! Risk of death through electric shock Attention dangerous contact
voltage!
- Ensure that the PE connector (ground) on the EOR-3DS is connected.
- Check for zero potential before executing this task!
- Make sure all wires are connected and strain-relieved.
- The cable requirements of all connector blocks have to be met. (see chapter 5.23)
U05 connection for capacitive LR and LRM systems (incl. adapter cable)
With the EOR-3DS it is possible to measure voltage parallel to a capacitive
voltage detecting system.
Principle schematic of connecting the EOR-3DS to a capacitive transducer
Terminal assignment for U05 characteristic
U06/U07 connection for low power voltage sensors (burden 200 kΩ or 2 MΩ)
Terminal assignment for characteristics U06/U07
Normally Uen is not measured using low power sensors. This means the parameter ‘calculate Uen‘ must be activated in the EOR-3DS.
C10 connection for low power current sensors
The EOR-3DS offers the possibility to connect low power current sensors
from multiple manufacturers.
Terminal assignment for characteristic C10
C29/U29 connection for ABB low power sensors
The EOR-3DS offers the possibility to connect ABB low power current and
voltage sensors via RJ45. This way a combined sensor or separate sensors for
current and voltage with y-adapter can be connected.
NOTICE! Property damage due to disregarding the mounting instructions!
The RJ45 connector cables must be preformed and strain-relieved in order to
connect them mechanically tension free to the device. Otherwise, there is a
risk of damaging the RJ45 ports on the EOR-3DS.
Terminal assignment for characteristic C29/U29
U31/C31 connection for Siemens low power sensors
The EOR-3DS offers the possibility to connect Siemens low-power combi sensors
(SIBushing) to measure voltage and current via RJ45.
NOTICE! Property damage due to disregarding the mounting instructions!
The RJ45 connector cables must be pre formed and strain relieved in order to
connect them mechanically tension free to the device. Otherwise, there is a
risk of damaging the RJ45 ports on the EOR-3DS.
Definition P1/P2 on measuring card C31/U31 (Siemens SIBushing): In the Siemens SIBushing P1 is in feeder direction and P2 in busbar di-rection. The EOR-3DS considers this fact automatically with measurement card C31/U31. An inversion of the current direction by adjusting the respective parameters is not necessary.
Connecting of transducers
DANGER! Risk of death through electric shock!
Attention dangerous contact voltage!
Voltage spark over and high short circuit currents in CAT II and CAT III
possible!
- Ensure that the PE connector (ground) on the EOR-3DS is connected.
- Check for zero potential before executing this taks!
- Short circuit the current transducer before executing this task.
- Make sure all wires are connected and strain relieved.
- The cable requirements of all connector blocks have to be met. (see chapter 5.23)
Adapter modules C21, C25 (only 3Io measurement) and U10
Connection zero sequence voltage Uen and zero sequence current 3Io
The connection of zero sequence voltage (referred as Uen or Uo) takes place
via the so-called open delta winding. A core-balanced current transformer is
used to measure 3I0.
Connection of phase to earth voltages UL1, UL2, UL3 and phase currents IL1,
IL2, IL3
In the following example, only the phase voltages and the phase currents are
con-nected to the EOR-3DS. Uen and 3I0 are not used.
Connection to the busbar side neutral point of the current transducer
The voltage measurement is identical to chapter 3.6.2.3. However, the current
measurement is wired in a way that a connection from one transducer is
combined with the other two current transducers. The sum of the three phase
currents (i. e. 3I0) can consequently be measured at this ‘node’.
Separate connection of phase voltages and currents, zero sequence voltage
and sum current
Beside the measurements for phase voltages and phase currents, measurements
also exist for the zero sequence voltage (Uen) and zero sequence current
(3I0).
Operation / Display
EOR – 3DS housing
- Power LED
- OLED colour display
- Status LED
- Operating keys
- Signaling LEDs
- RESET key
- Service port
USB or ethernet adapters are available for the service port. More information is included in the EOR-3DS data sheet.
Menu navigation with the operating keys on the device
Key | Description | Function |
---|---|---|
**** | Up / Higher |
- Move up in the menu
- Increase parameter value
****| Down / Lower|
- Move down in the menu
- Decrease parameter value
****| Left|
- Switch to previous / higher level in the menu: ‘Back’
- For parameters with more than one number, move to the left (cursor)
- 20 keystrokes in start screen
option for factory reset
****| Right|
- Change to the next / lower level in the menu: ‘Forward’
- For parameters with more than one number, move to the right (cursor)
****| Return / Enter|
- Jump to the menu from the start screen
- Selection of a particular menu item
- Confirmation of a changed parameter
****| RESET|
- Quick press è Resetting of the signals
- Long press (> 4 seconds) è restart
Technical specifications
Regulations and standards
IEC 60255-1:2022
DIN EN 61010-1:2020
DIN EN 61010-2-030:2022
DIN EN 61000-6-5:2016
DIN EN 55032:2016 (CISPR 32:2015)
AC voltage input U05
Capacitive voltage tap-off on LR/LRM systems
Measuring voltage | 0 … 42 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | 110 pF |
Accuracy | ± 1,0 % |
AC voltage input U06
Low power sensors with 200 k rated burden and Un = 3,25 V / √? e.g. sensors
from Zelikso, Green-wood Power, etc.
Measuring voltage | 0 … 4 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | 220 kW |
Accuracy | ± 0,5 % |
AC voltage input U07
Low power sensors with 2 M rated burden and Un = 3,25 V / √?, e.g. sensors
from ABB, Zelisko, Greenwood Power, etc.
Measuring voltage | 0 … 4 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | 2 MW |
Accuracy | ± 0,5 % |
AC voltage input U10
Classical voltage transducers with 100 V or 110 V; all values refer to the
connection at the U10 adapter; AC voltage input at indicator itself like U06
feature
Measuring voltage | 0 … 150 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | 10 MW |
Accuracy | ± 1,0 % |
AC voltage input U29
Low power sensors with 2 M rated burden, e.g. ABB sensors acc. to IEC 60044 or
61869 with RJ45 plug
Measuring voltage | 0 … 8 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | 2 MW |
Accuracy | ± 0,5 % |
AC voltage input U31
Low power sensors from Siemens (SIBushing) acc. to IEC 61869 with RJ45 plug
(with sensor configuration file)
Measuring voltage | 0 … 8 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | 2 MW |
Accuracy | ± 0,5 % |
AC current input C10
Inductive low power sensors with Ur = 255mV, e.g. sensors from ABB, Zelisko,
Greenwood Power, etc.
Measuring voltage | 0 … 500 mVAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | ≥ 60 kW |
Accuracy | ± 0,5 % |
AC current input C21/C25
Classical current transducers 1A / 5A secondary
Measuring voltage | 0 … 500 mVAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | ≥ 60 kW |
Accuracy | ± 0,5 % |
AC current input C29
Low power sensors ABB acc. to IEC 60044 or 61869 with RJ45 plug
Measuring voltage | 0 … 4,69 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | £ 0,1 VA |
Accuracy | ± 0,5 % |
AC current input C31
Low power sensors from Siemens (SIBushing) acc. to IEC 61869 with RJ45 plug
(with sensor configuration file)
Measuring voltage | 0 … 1,125 VAC |
---|---|
Shape of the curve | Sine |
Frequency range of fundamental wave | 48 .. 52 Hz |
Burden | £ 0,1 VA |
Accuracy | ± 0,5 % |
Binary inputs
Inputs BI1 + BI2
Input voltage
(valid for order codes C29/U29 and C31/U31)
| DC 0 … 60 V
---|---
Input voltage
(valid for order codes except C29/U29 and C31/U31)
| DC 0 … 110 … 132 V
Curve shape, permissible| Rectangular
H – Level| DC 20 V
L – Level| DC 15 V
Input resistance| > 16 kW
Potential isolation| Impedance isolation
Input voltage| DC 0 …60 V
---|---
Curve shape, permissible| Rectangular
H – Level| DC 20 V
---|---
L – Level| DC 15 V
Input resistance| > 16 kW
Potential isolation| Impedance isolation
Binary outputs
max. switching fre- quency | £ 1 Hz |
---|---|
Potential isolation | Isolated from all device- internal potentials |
Contact load (maximum values with ohmic load) | AC 60 V / 1.0 A |
DC 30 V / 2.0 A
DC 60 V / 0.5 A
Type of use| In secondary circuit, galvanic separated from line voltage
max. isolation volt- age| DC 1500 V
min. switching load| 100 mW
Switch. operations| > 106 electrical
BO 1| monostable relay with change over contacts
BO 2..4| monostable relays (normal open contacts)
Serial RS485 interface
Type | 2-wire RS485 interface |
---|---|
Potential isolation | galvanic separated |
Connection | shielded cable |
120 Ω
termination
| via DIP switch on backside
Supply voltage
Character- istic | Voltage range | Power consumption |
---|---|---|
H23: | DC: 20 .. 148 V |
protect. against polarity reversal
| < 4 W (boot)
< 3 W (operation)
< 6 W (operation + service adapter)
Rated conductor cross section
Rated conductor length | 10 mm |
---|
Terminal X1
(digital outputs)
| 0,5 – 1,5 mm²
Terminal X2
(power supply)
| 0,5 – 1,5 mm²
Terminal X4
(RS485)
| 0,5 – 1,5 mm²
Terminal X5 (measurement inputs &
binary inputs 3..6)
| 0,5 – 1,5 mm²
Terminal X6
(binary inputs 1&2)
| 0,5 – 2,5 mm²
Terminal X6
(binary inputs 1..6 – only with features C29/U29 or C31/U31)
| 0,5 – 1,5 mm²
PE flat connector (6.3 mm)| 2,5 mm²
Measurement value recording
Non-volatile | ≤ 32 GB |
---|
Environment parameters
Reference temp. | 23°C ± 1 K |
---|---|
Operation | -20 °C…+50 °C |
Transport and stor- age | -25 °C…+65 °C |
Relative humidity | 5 %..95 % |
non-condensing
Altitude| Up to 2000 meters
**Limit-value monitoring**
Limit values | programmable |
---|---|
Response times | programmable |
Alarm indicators | programmable LED; Display |
Weight
EOR-3DS B04 | 0.29 kg |
---|---|
EOR-3DS B04 with C21 adapter | 0.41 kg |
EOR-3DS B04 with U10 adapter | 0.46 kg |
EOR-3DS B04 with C21 & U10 adapter | 0.58 kg |
Electrical safety
DIN EN 61010-1:2020
DIN EN 61010-2-030:2022
Degree of protection:
Device front with attached service interface coverage
Device back
| IP50 IP20
Protection class| I
Degree of pollution| 2
Measurement category (only U10-adapter)| III/150 V
Measurement category (only U10-adapter)| II/300 V
Overvoltage category| II
DC 50 V| RS485, Ethernet
---|---
DC 60 V| Binary inputs 1..6, measurement inputs
DC 132 V| Binary inputs 1+2
(except C29/U29 or C31/U31)
DC148 V| Power supply
AC 60 V| Binary outputs
AC 150 V| U10 voltage adapter
Electromagnetic compatibility
Immunity | DIN EN 61000-6-5:2016 |
---|---|
Emissions | DIN EN 55032:2016 |
(CISPR 32:2015)
Anschluss / Klemmen
Please notice the security instructions and information given in the
previous chapters regarding the connection of the device according to the
characteristics ‘C’ and ‘U’ and according to the respective connection to low
power sensors and transducers
Connector block nr. | Name | Function | Connector nr. | Cross sec- tion [mm²] |
---|---|---|---|---|
X1 | relay | R1/R2 | Pole R1/R2 | 11 |
R1 | NC | 9 | ||
NO | 7 | |||
R2 | NO | 6 | ||
R3 | NO | 4 | ||
R4 | NO | 3 | ||
R3/R4 | Pole R3/R4 | 1 | ||
PE | PE flat con- nector (6,3 mm) | GND | PE | PE |
X2 | Supply voltage | L(+) | 3 | 0,5 – 1,5 |
— | 2 | |||
L(-) | 1 | |||
X4 | RS485 | RS485_A | 1 | 0,5 – 1,5 |
RS485_B | 2 | |||
RS485_GND | 3 | |||
X6 | Binary input 1 | BI1 | BI1 | 1 |
GND | 2 | |||
Binary input 2 | BI2 | BI2 | 3 | |
GND | 4 | |||
X5 | Binary input 3 | BI3 | BI3 | 1o |
GND | 1u | |||
Binary input 4 | BI4 | BI4 | 2o | |
GND | 2u | |||
Binary input 5 | BI5 | BI5 | 3o | |
GND | 3u | |||
Connector block nr. | Name | Function | Connector nr. | Cross sec- tion [mm²] |
--- | --- | --- | --- | --- |
Binary input 6 | BE6 | BI6 | 4o | |
GND | 4u | |||
X5 | Phase voltage L1 | U1 | 6o | 0,5 – 1,5 |
GND | 6u | |||
Phase voltage L2 | U2 | 7o | ||
GND | 7u | |||
Phase voltage L3 | U2 | 8o | ||
GND | 8u |
Zero sequence voltage U0
(depending on feature U)
| U0| 9o
GND| 9u
X5| Phase current L1| I1| 10o| 0,5 – 1,5
GND| 10u
Phase current L2| I2| 11o
GND| 11u
Phase current L3| I3| 12o
GND| 12u
Zero sequence current 3I0 (depending on feature C)| 3I0| 13o
GND| 13u
Assignment of connector block X6 for devices with order characteristics C29/U29 & C31/U31. In this case the connector block X5 is replaced by three RJ45 ports L1, L2, L3.
Connector block nr. | Name | Function | Connector nr. | Cross sec- tion [mm²] |
---|---|---|---|---|
X6 | Binary input 1&2 | GND 1/2 | 1o | 0,5 – 1,5 |
BI1 | 2o | |||
BI2 | 3o | |||
Binary input 3-6 | GND 3-6 | 1u | ||
BI3 | 4o | |||
BI4 | 2u | |||
BI5 | 3u | |||
BI6 | 4u |
For each connector block the length of the wire end ferrule or stripped wire must be 10mm.
A. Eberle GmbH & Co KG
Frankenstraße 160
D-90461 Nuremberg
Tel.: +49 (0) 911 / 62 81 08-0
Fax: +49 (0) 911 / 62 81 08 99
E-Mail: info@a-eberle.de
http://www.a-eberle.de
Art.-Nr. 584.0891.01
Version: 20.09.2023 10:44