THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE LMD602, LMD602T, LMD604, and LMD604T SERIES INDUCTIVE LOOP MONITOR.
REVISION: MARCH 2012
pn 888-060X-001
THE LMD602 AND LMD604 SERIES IS DESIGNED AND MANUFACTURED IN THE USA BY EBERLE
DESIGN INC.
PHOENIX, ARIZONA
EDI IS CERTIFIED TO ISO 9001:2008 QUALITY SYSTEMS STANDARDS.
INFORMATION CONTAINED HEREIN IS PROPRIETARY TECHNICAL INFORMATION OF EBERLE
DESIGN INC. PUBLICATION, REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED
EXCEPT UNDER TERMS AGREED UPON IN WRITING.
DEFLECTOMETER IS A TRADEMARK OF EBERLE DESIGN
U.S. PATENT NO. 7,855,893
© COPYRIGHT 2012 EDI
Section 1: GENERAL
1.1 DESCRIPTION
The LMD602 two channel and LMD604 four channel Nema TS-1 rack mounted inductive Loop Monitor with DEFLECTOMETER® Series is built on the international card format with double-sided 44 pin edge connectors for connection of power, loop inputs and call outputs. The units meet or exceed all requirements for detectors as defined in Nema Standard TS1-1989 (R2005). Each channel has individual controls for setting up sensitivity, operational mode and frequency on the front panel. Two high intensity front panel LEDs indicate vehicle detection, timing operation and fault monitoring status for each channel. Call outputs are available in either relay or optically-isolated solid-state transistor form.
1.2 OVERVIEW
A dynamic Overview of the LMD operation which includes an LMD Simulator is available on the EDI Web Site; www.EDItraffic.com.
1.3 DEFLECTOMETER® FEATURE
The LMD Series Loop Monitor introduces a concept to the inductive loop detector field that revolutionizes the process of installing and programming a loop detector. The new user interface of the LMD Series provides the feedback necessary to the signal technician to quickly and accurately program the parameters of the detector exactly to the loop plus lead in system characteristics.
Why guess when you can know!
The DEFLECTOMETER display shows the relative strength of the call while a
vehicle is in the detection zone. This provides feedback that the unit is
optimally tuned to detect vehicles of all sizes.
Setting the sensitivity level of the detector can be easily done in one step
with a “typical” vehicle parked in the detection zone. The DEFLECTOMETER
display updates dynamically as the sensitivity level is changed. See section
2.1.1.
The simple push-button interface is intuitive and eliminates many of the
reliability problems found with tiny DIP switches of conventional detectors.
Operational mode, Frequency, and Sensitivity are all programmed and
displayed using the push-button interface. Settings are stored in non-volatile
memory.
Loop diagnostic capabilities incorporated within the LMD Series Loop Monitor enable the detection of short or open circuit loops and sudden changes of inductance exceeding 25 percent of the nominal inductance. Each type of fault is signified by the fault indicator emitting a different flash sequence. This information can greatly assist the user in the diagnosis of loop related problems.
The unit will detect inductance changes as small as 0.010% ∆L/L. Each channel is sequentially energized and sampled so as to negate the possibility of crosstalk between loops connected to different channels of the same detector.
Eberle Design Deflectometer
Section 2: Installation and Adjustments
2.1 SET THE SENSITIVITY LEVEL
The DEFLECTOMETER (front panel 7-segment LED display) aids in setting the detector to the most optimum sensitivity level to ensure the detection of all vehicles, including motorcycles and high bed vehicles.
While the LMD Series unit is in the Call state (DEFLECTOMETER = 1-9), the
DEFLECTOMETER displays the Call Strength (1 – 9). The Call Strength will
increase or decrease one step as the Sensitivity Level is increased or
decreased one step.
The Call Strength value will depend on the size and type of vehicle in the
detection zone as well as the Sensitivity Level setting of the channel. The
optimum value for a mid-sized vehicle is 5.
The procedure in section 2.1.1 provides a quick and simple way to program
the Sensitivity Level to the optimum setting to ensure all classes of vehicles
are reliably detected with one simple step.
The resulting Sensitivity Level can be then be displayed using the procedure
in section 2.1.2. While the LMD Series is in the No-Call state (DEFLECTOMETER
= 0), the DEFLECTOMETER will display the Sensitivity Level (1 – 9) when either
SENS button is pressed once.
For typical vehicles (mid-size vehicle / small pick up) utilizing properly installed roadway loops, when the Call Strength value 4, 5, or 6 (5 being optimum) is displayed on the DEFLECTOMETER during the DETECT output period then the sensitivity level is set correctly. For high profile vehicles (commercial trucks, 4×4’s, etc…), a DEFLECTOMETER Call Strength value of 4 will be best. For low profile vehicles (sports cars, etc…), a DEFLECTOMETER Call Strength value of 6 will be best.
2.1.1 ADJUSTING SENSITIVITY USING THE DEFLECTOMETER (RECOMMENDED)
The DEFLECTOMETER should read zero (0) with no vehicle over the roadway loop.
With a typical mid-sized vehicle in the detection zone (DET indicator On), the
DEFLECTOMETER will display the Call Strength value (1 – 9). If a mid-size
vehicle, located over the roadway loop causes the Call Strength value “7” to
be displayed on the DEFLECTOMETER, the sensitivity should be lowered two
levels (7 – 2 = DEFLECTOMETER reading “5”). This is done by pressing the front
panel SENS (down) button twice.
If a mid-size vehicle, located over the roadway loop causes the value “2” to
be displayed on the DEFLECTOMETER, the sensitivity should be increased three
levels (2 + 3 = DEFLECTOMETER reading “5”. This is done by pressing the front
panel SENS (up) button three times.
NOTE : The DEFLECTOMETER dynamically updates after each Sensitivity Level
change, allowing changes to the Sensitivity setting while a vehicle remains in
the loop detection zone. Note that the Call Strength value may be different
than
the actual Sensitivity Level setting.
2.1.2 ADJUSTING SENSITIVITY DIRECTLY
The LMD Series offers nine levels of sensitivity (1 to 9). The Sensitivity Level can be manually set to any desired level by pressing the SENS or SENS front panel buttons when a vehicle is NOT over the roadway loop. The Sensitivity Level will be now displayed on the DEFLECTOMETER. Pressing the SENS or SENS button once will display the Sensitivity Level without changing the setting. After pressing the SENS or SENS buttons to display the Sensitivity Level, the setting can then be modified by pressing the SENS or SENS buttons again. The display will automatically return to the normal display after three seconds. The factory default Sensitivity Level is 6.
Eberle Design Deflectometer Inductive Loop Monitor Sensitivity
Note that each change of the Sensitivity Level while in this “direct adjust” mode causes the LMD Series to retune.
2.1.3 DYNAMIC DEFLECTOMETER DISPLAY OPERATION
While the LMD Series is in the Call state (DEFLECTOMETER = 1-9), the DEFLECTOMETER displays the Call Strength (1 – 9). When the Call terminates (DET indicator Off) the Call Strength will be displayed for an additional three seconds. Pressing the SENS or SENS button during this interval will modify the Sensitivity Level as described in section 2.1.1, with the DEFLECTOMETER display remaining in the Call Strength mode.
Pressing the SENS or SENS button when the LMD Series is not in the Call state (DEFLECTOMETER = 0) will display and modify the Sensitivity Level directly as described in section 2.1.2. In this case the DEFLECTOMETER displays the actual Sensitivity Level.
2.2 SET THE OPERATIONAL MODE
Operational mode can be set to Short Presence, Long Presence, Pulse, Call or
Off mode. Pressing the MODE button once will display the Operational Mode
without changing the setting. After pressing the MODE button to display the
current Operational Mode, the setting can then be changed by pressing the MODE
button again. The display will automatically return to the normal display
after several seconds.
Changing the Operational Mode will cause the channel to retune.
2.2.1 OUTPUT CALL TEST
When the MODE button is pressed and held for one second, the unit will generate a pulsed (125 ms) Call state (true) output every 1500 ms. This operation can be used to quickly verify that a Call output is being received by the Controller Unit.
2.2.2 SHORT PRESENCE MODE (S)
The Short Presence mode will tune out a continuous Call after 30 minutes. Use Short Presence unless the detection zone is expected to be continuously occupied for periods of time in excess of 30 minutes.
2.2.3 LONG PRESENCE MODE (L)
The Long Presence mode will tune out a continuous Call after 120 minutes.
2.2.4 PULSE MODE (P)
The Pulse mode will provide a 125 ms ± 25ms width output pulse for each vehicle entering the loop.
2.2.5 CALL MODE (C)
The Call mode will set the channel output to the Call state (True). This mode can be used to provide a continuous Call state to the Controller Unit regardless of the state of the detection zone. Loop fault conditions are ignored in this mode.
2.2.6 OFF MODE (-)
The Off mode will set the channel output to the No Call state (False). This mode can be used if the channel is not used or not connected to a loop. Loop fault conditions are ignored in this mode.
2.3 SET THE FREQUENCY
Eberle Design Deflectometer Inductive Loop Monitor Frequency
Pressing the FREQ button once will display the Frequency Level (1 – 4) without
changing the setting. After pressing the FREQ button to display the current
Frequency Level, the setting can then be changed by pressing the FREQ button
again. The display will automatically return to the normal display after
several seconds.
The Frequency level needs to be changed only if interference occurs between
adjacent loops connected to different sensor units. Interference or crosstalk
may manifest itself as chattering of the call
output or a detect call occurring at the same time as an adjacent unit when
there is no vehicle present. If crosstalk is suspected, try to separate the
frequencies of the channels causing the problem. A minimum of 5 KHz separation
is recommended. Four frequency levels are available on each channel to assist
in alleviating interference affecting more than two units.
Changing the Frequency Level will cause the channel to retune.
2.3.1 DISPLAYING THE LOOP FREQUENCY
The current loop frequency is displayed by after pressing the FREQ button to display the current Frequency Level. The frequency is shown in KHz with a “-“ symbol displayed both before and after the numeric digits shown on the DEFLECTOMETER.
For example, after pressing the FREQ button once the display sequence might
show:
“3” “-“ “2” “7” “-“
This sequence would indicate Frequency Level “3” and a loop reference frequency of 27 KHz.
2.4 SET THE DELAY AND EXTEND TIMING (LMD602T AND LMD604T ONLY)
2.4.1 DELAY TIMING
For each channel, a delay time of 1 to 63 seconds can be set via the DELAY DIP switches. The numeric sum of the switches in the On position is equal to the Delay time. Call Delay time starts counting down when a vehicle enters the loop detection area. During the Delay time the DET indicator will flash two times per second and the DEFLECTOMETER will display the letter “d”. Delay time can be overridden by a True signal at the Timer Control input.
2.4.2 EXTEND TIMING
For each channel, an extend time of 0.25 to 15.75 seconds can be set via the EXTEND DIP switches. The numeric sum of the switches in the On position is equal to the Extend time.
2.4.2.1 EXTEND ALWAYS (DEFAULT)
Call Extend time starts counting down when the last vehicle clears the loop detection zone. During the Extend time the DET indicator will flash four times per second and the DEFLECTOMETER will display the letter “E”. Any vehicle entering the loop detection zone during the Extend time period causes the Extend timer to be reset and the output maintained. The Timer Control input has no effect on this mode.
2.4.2.2 EXTEND ON GREEN (EOG)
Call Extend time starts counting down when the last vehicle clears the loop
detection zone if the Timer Control input is True (low). During the Extend
time the DET indicator will flash four times per second and the DEFLECTOMETER
will display the letter “E”. Any vehicle entering the loop detection zone
during the Extend time period causes the Extend timer to be reset and the
output maintained.
The Extend on Green mode is enabled by a factory installed jumper located at
E6 on the pcb. Consult the factory for details.
2.4.3 TIMER CONTROL INPUTS
Timer Control inputs are provided for each channel to modify the operation of
the Delay and Extend Timing functions. The application of a True (low) state
voltage will inhibit the Delay timing function and/or enable the Extend timing
function as described in sections 2.4.1 and 2.4.2.2. When the Timer Control
Input is True (low) the decimal point of the
channel DEFLECTOMETER display will illuminate. Timer Control inputs are
primarily provided for downward compatibility.
2.5 MISCELLANEOUS
2.5.1 CHANNEL OFF
If a channel is not to be used, it may be switched off (disabled) by setting the Operational Mode to OFF. See section 2.2.6.
2.5.2 RETUNE OR RESET A CHANNEL
Press the MODE and FREQ buttons simultaneously to reset the channel. This will clear any previous loop fault indication and cause the channel to retune.
2.5.3 FACTORY DEFAULT SETTINGS
Press the Channel 1 MODE and FREQ buttons simultaneously while first applying power to the unit to reset all channels to the factory default settings.
Eberle Design Deflectometer Inductive Loop Monitor Factory Details
2.6 LOOP FAULT MONITORING
The LMD Series Loop Monitor continuously checks the integrity of the loop. The system is able to detect open circuit loops, shorted loops, or sudden changes in inductance exceeding 25% of the nominal inductance.
2.6.1 CURRENT FAULT
If a fault is detected, both the DET (Red) and FLT (Yellow) LEDs continuously emit a sequence of flashes and the DEFLECTOMETER will display the letter “F”. Each type of fault is identified by a different flash sequence followed by a one second pause:Eberle Design Deflectometer Inductive Loop Monitor Flash Sequence
2.6.2 PREVIOUS FAULT
If the fault condition is removed, the DET indicator and the channel output will return to normal operation. The FLT indicator will continue to flash indicating that a fault had previously occurred. This Previous Fault indication may be reset by momentarily pressing the MODE and FREQ buttons simultaneously. See section 2.5.2.
Section 3: Loop Installation
The typical sensing height is 2/3 of the shortest leg of a loop (in feet).
Therefore a 4’ x 8’ loop typically has a detection height of 2.6’.
The inductance of a conventional four-sided loop can be estimated using the
formula:
L = P x (T 2 + T) / 4
Where L = Loop Inductance in microHenries
P = Loop Perimeter in feet
T = Number of wires in saw slot
Therefore a 4’ x 8’ loop with 3 turns would be:
L = (4 + 8 + 4 + 8) x (3 2 + 3) / 4
L = 24 x (9 + 3) / 4
L = 24 x 12 / 4
L = 72 microHenries
Note : Loop feeder cable typically adds 0.22 microHenries of inductance
per foot of cable.
The following are suggested guidelines for loop installation:
To begin, make sure that the pavement surface in the area that loops are to be
installed is dry and free of debris. The outline of the loop(s) should be
marked on the pavement in such a way that the lines can be followed easily by
the saw operator and not be erased by the water feed from the saw itself.
All 90-degree corners should be chamfered so that the course of the loop wire
does not change direction sharply but rather at shallower angles of 45 degrees
or less. Core drilling of the corners achieves the same effect but can still
lead to failure due to sharp edges remaining in the corner area. When the
outline of the loop and lead-in has been marked, the pavement can be cut.
Diamond blade cutting saws are recommended. The saw cut should be
approximately 2.0 inches deep and 0.25 inches wide. The saw slot should then
be cleaned out and allowed to dry. Compressed air is useful both for ejecting
debris and speeding up the drying process. All debris in the vicinity of the
saw slot should also be removed so that it is not accidentally pushed back in.
As a general rule loops with circumference lengths less than 12 feet require 5
turns of wire, 12 to 60 feet require 3 to 4 turns of wire, loops with greater
circumference lengths should have 2 to 3 turns.
Recommended loop wire is typically 14, 16, 18, or 20 AWG with cross-linked
polyethylene insulation. Since moisture can cause significant changes in the
dielectric constant of the insulation, which results in excessive loop
(frequency) drift, choose insulation, which is most impervious to moisture.
PVC, TFFN, THHN, and THHN-THWN should be avoided since they tend to absorb
moisture and crack easily. XLPE (Cross Linked Polyethylene) is very resistant
to moisture absorption and provides good abrasion resistance.
If long lead-ins are required, it is suggested that the loop cable be spliced
onto shielded, pre-twisted, lead-in wire (IMSA specification 50-2 is
suggested) at a convenient pull box location close to the loop. The shield may
be connected to earth at the cabinet end but should then be insulated and
isolated from earth ground at the loop end. The inductance of the loop itself
should be at least 50% of the sum of loop inductance plus lead-in inductance.
Start laying the loop wire from the termination of the lead-in out towards the
loop, continue around the loop for the number of turns required and finally
return to the lead-in termination. Leave the lead-in wire out of the slot so
that it may be twisted together before being laid in the slot. Lead-ins should
be twisted with a minimum of 4 to 6 twists per foot to
prevent any separation of the lead-in wires.
Make sure that the loop wire is pushed fully to the bottom of the saw slot.
Small pieces of
foam rubber (backer rod) or similar material may be used at various points
around the circumference to prevent the loop wire from rising up while the
sealant is poured and curing.
Many different types of loop sealant are now available. Single part types are
the easiest to apply since no mixing is required, but they also tend to be
more expensive in terms of linear feet of saw slot filled. When applying the
sealant, make sure that it is able to sink to the bottom of the slot and
completely encase the loop wire. The wire should not be able to move when the
sealant has set. Ensure that there is enough sealant to completely fill the
slot; if possible the sealant should protrude slightly above the surface of
the pavement so that small rocks or other debris cannot collect in the slot.
The sealant manufacturer instructions concerning setting time should be noted
especially when determining the length of time to wait before allowing
vehicles to cross the loop area.
Consult the Eberle Design web site at www.EDItraffic.com for further
application
information regarding loop design.
Section 4: Specifications
4.1 MECHANICAL
Height …………………………………………………………………………… 4.50 inches
LMD602 (T) Width ………………………………………………………….. 1.14 inches
LMD604 (T) Width ………………………………………………………….. 2.34 inches
Depth (excluding handle) ………………………………………………….6.875 inches
4.2 ENVIRONMENTAL
Storage Temperature Range …………………………………………… -45 to +85 o C
Operating Temperature Range ………………………………………… -34 to +74 o C
Humidity Range (non-condensing) ……………………………… 0 to 95% Relative
4.3 ELECTRICAL
DC Supply Voltage Minimum…………………………………………………. 10.8 Vdc
DC Supply Voltage Maximum………………………………………………… 28.8 Vdc
DC Supply Current …………………………………………………. 100 mA Maximum
DC Inputs
True (low) ……………………………………………………………. less than 8 Vdc
False (high) …………………………………………………… greater than 16 Vdc
Optically Isolated Solid State Outputs
True (low, 50 mA) ………………………………………………. less than 1.5 Vdc
Maximum Leakage Current (DC Supply = 24Vdc) ……………………. 10 uA
Maximum Current (low) ……………………………………………………. 100 mA
Relay Outputs
AC Contact Rating …………………………………………………. 5A @ 120 Vac
DC Contact Rating …………………………………………………… 5A @ 30 Vdc
4.4 TUNING
4.4.1 LOOP INDUCTANCE (TUNING) RANGE
The detector will automatically tune to a loop and lead-in combination within the tuning range of 20 to 2500 microHenry with a Q factor greater than 5.
4.4.2 ENVIRONMENTAL TRACKING
The detector automatically and continuously compensates for component drift and environmental effects throughout the tuning range and across the entire temperature range.
4.4.3 GROUNDED LOOP OPERATION
Each detector channel will operate when connected to poor quality loops including those that have a short to ground at a single point.
4.4.4 LEAD-IN LENGTH
The unit will operate with lead-in (feeder) lengths up to 5,000 feet (1,524 m.) with appropriate loops and proper lead-in cable.
4.5 LOOP INPUT (LIGHTNING PROTECTION)
The loop input incorporates lightning and transient protection devices and the
loop oscillator circuitry is transformer-isolated for each channel. The
lightning protection will withstand the discharge of a 10uF capacitor charged
to 2,000V across the loop inputs or between a loop input and Earth Ground for
each channel. The transformer isolation allows
operation with a loop which is grounded at a single point.
4.6 RESPONSE TIMING
These tables assume that all channels are set to the same Sensitivity Level.
4.6.1 LMD602 SERIES RESPONSE TIMING
LMD602 SERIES RESPONSE TIMING Table
4.6.2 LMD604 SERIES RESPONSE TIMING
LMD604 SERIES RESPONSE TIMING Table
4.7 LMD602(T) CONNECTOR PIN ASSIGNMENTS
LMD602(T) CONNECTOR PIN ASSIGNMENTS Table
Pin 1 through 22 is on the top (component) side and pin A through Z is on the
bottom (solder) side. Polarization keys are located at three positions:
Between B/2 and C/3
Between M/11 and N/12
Between E/5 and F/6
4.8 LMD604(T) CONNECTOR PIN ASSIGNMENTS
LMD604(T) CONNECTOR PIN ASSIGNMENTS Table
Pin 1 through 22 is on the top (component) side and pin A through Z is on the
bottom (solder) side. Polarization keys are located at three positions:
Between B/2 and C/3
Between M/11 and N/12
Between E/5 and F/6