Deye SUN-8K-G03-LV Grid Connected PV Inverter User Manual
- June 15, 2024
- Deye
Table of Contents
- SUN-8K-G03-LV Grid Connected PV Inverter
- Introduction
- Safety warnings and instructions
- Operation Interface
- Product installation
- Electrical Connection
- Startup and Shutdown
- Zero-export function via energy meter
- General Operation
- Repair and Maintenance
- Error information and processing
- Specification
- EU Declaration of Conformity
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Grid-connected PV Inverter
SUN-8K-G03-LV
User Manual
SUN-8K-G03-LV Grid Connected PV Inverter
About This Manual
The manual mainly describes the product information, guidelines for
installation, operation and maintenance. The manual cannot include complete
information about the photovoltaic (PV) system.
How to Use This Manual
Read the manual and other related documents before performing any operation on
the inverter.
Documents must be stored carefully and be available at all times. Contents may
be periodically updated or revised due to product development. The information
in this manual is subject to change without notice.The latest manual can be
acquired via service@deye.com.cn
Photovoltaic Grid-connected System
Introduction
1.1 Appearance Introduction
On-grid Inverter can convert solar panel DC power into AC power which can
directly input to the grid. Its appearance is shown below.These models contain
SUN-8K-G03-LV.
The following is collectively referred to as “inverter”.
1.2 Parts list
Please check the following table, to see whether all the parts are included in
the package:
1.3 Product handling requirements
One people stand on both sides of the machine, holding two handles to lift the
machine.
Safety warnings and instructions
Improper use may result in potential electric shock hazards or burns. This manual contains important instructions that should be followed during installation and maintenance. Please read these instructions carefully before use and keep them for future reference.
2.1 Safety signs
Safety symbols used in this manual, which highlight potential safety risks and
important safety information, are listed as follows:
Warning:
Warning symbol indicates important safety instructions, which if not correctly
followed, could result in serious injury or death.
Shock Hazard:
Caution, risk of electric shock symbol indicates important safety
instructions, which if not correctly followed, could result in electric shock.
Safety Hint:
Note symbol indicates important safety instructions, which if not correctly
followed, could result in some damage or the destruction of the inverter.
High Temperature Hazard:
Caution, hot surface symbol indicates safety instructions, which if not
correctly followed, could result in burns.
2.2 Safety instructions
Warning:
Electrical installation of the inverter must conform to the safety operation
rules of the country or local area.
Warning:
Inverter adopts non-isolated topology structure, hence must insure DC input
and AC output are electrical isolated before operating the inverter.
Shock Hazard:
Prohibit disassembling inverter case, there existing shock hazard, which may
cause serious injury or death, please ask qualified person to repair.
Shock Hazard:
When PV module is exposed to sunlight, the output will generate DC voltage.
Prohibit touching to avoid shock hazard.
Shock Hazard:
While disconnect the input and output of the inverter for maintenance, please
waits for at least 5 mins until the inverter discharge the remnant
electricity.
High Temperature Hazard:
Local temperature of inverter may exceed 80℃ while under operating.
Please do not touch the inverter case.
2.3 Notes for using
The single phase string power inverter is designed and tested under related
safety regulations. It can ensure the personal safety of the user. But as a
electric device, it may cause shock or injury by incorrect operation. Please
operate the unit under below requirements:
-
Inverter should be installed and maintained by qualified person under local standard regulations.
-
Must disconnect the AC side first, then disconnect DC side while doing installation and maintenance, after that, please wait at least 5 mins to avoid getting shocked.
-
Local temperature of the inverter may exceed 80 ℃ while under operating.Do not touch to avoid getting injured.
-
All electrical installation must be in accord with local electrical standards, and after obtaining the permission of the local power supply department, the professionals can connect the inverter to the grid.
-
Please take appropriate anti-static measure.
-
Please install where children can not touch.
-
The steps to start the inverter:1) switch on the AC side circuit breaker, 2) Switch on the DC side circuit breaker of the PV panel. 3) Turn on the DC switch of the inverter.
The steps to stop the inverter:1) switch off the AC side circuit breaker, 2) switch off the DC side circuit breaker of the PV panel. 3) Turn off the DC switch of the inverter. -
Don’t insert or remove AC and DC terminals when the inverter is in normal operation.
-
The DC input voltage of the inverter must not exceed the maximum value of the model.
Operation Interface
3.1 Interface View
3.2 Status Indicator
There are four LED status indicator lights in the front panel of the inverter.
Please see table 3.1 for details.
Indicator | status | Explanation |
---|---|---|
DC | on | Inverter detects DC input |
off | Low DC input voltage | |
AC | on | Grid Connected |
off | Grid Unavailable | |
NORMAL | on | Under normal operating |
off | Stop operating | |
ALARM | on | Detected faults or report faults |
off | Under normal operating |
Table 3.1 Status indicator lights
3.3 Buttons
There are four keys in the front panel of the Inverter(from left to right):
Esc, Up, Down and Enter keys. The keypad is used for:
- Scrolling through the displayed options (the Up and Down keys);
- Access to modify the adjustable settings (the Esc and Enter keys).
3.4 LCD Display
The two-line Liquid Crystal Display (LCD) is located on the front panel of the
Inverter, which shows the following information:
- Inverter operation status and data;
- Service messages for operator;
- Alarm messages and fault indications.
Product installation
4.1 Select installation location
To select a location for the inverter, the following criteria should be
considered:
WARNING: Risk of fire
- Do not install the inverter in areas containing highly flammable materials or gases.
- Do not install the inverter in potentially explosive atmospheres.
- Do not install in small closed spaces where air can not circulate freely. To avoid overheating, always make sure the flow of air around the inverter is not blocked.
- Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting. It is recommended that inverter installed to avoid direct sunlight or raining.
- To avoid overheating ambient air temperature must be considered when choosing the inverter installation location. It is recommended that using a sun shade minimizing direct sunlight when the ambient air temperature around the unit exceeds 104°F/40℃.
- Install on a wall or strong structure capable of bearing the weight.
- Install vertically with a maximum incline of +/-15°. If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
- If install more than one inverter, must leave at least 500mm gap between each inverter. And two adjacent inverters are also separated by at least 5000 mm. And must install the inverter at the place where children cannot touch. Please see picture 4.3.
- Consider whether the installation environment is helpful to see the inverter LCD display and indicator status clearly.
- Must offer a ventilate environment if inverter installed in the airtight house.
Safety Hint:
Do not place or store any items next to the inverter.
4.2 Inverter Installation
The inverter is designed according to the wall mounted type installation,
please use the wall mounted (the brick wall of the expansion bolt) when
installing.
Procedure shows below:
- Locate on the appropriate wall according to the bolt position on the mounting bracket, then mark the hole.On the brick wall, the installation must be suitable for the expansion bolt installation.
- Ensure that the position of the installation holes on the wall is in accordance with the mounting plate, and the mounting rack is vertically placed.
- Hang the inverter to the top of the mounting rack and then use the M4 screw in the accessory to lock inverter heat sink to the hanging plate, to ensure that the inverter will not move.
Electrical Connection
4.1 DC input terminal connection
- Switch the Grid Supply Main Switch(AC)OFF.
- Switch the DC lsolator OFF.
- Assemble PV input connector to the inverter.
Warning:
When using PV modules, please ensure the PV+ & PV- of solar panel is not
connected to the system ground bar.
Safety Hint:
Before connection, please make sure the polarity of the output voltage of PV
array matches the “DC+” and “DC-” symbols.
Warning:
Before connecting inverter, please make sure the PV array open circuit voltage
is within the 800V of the inverter.
Safety Hint:
Please use approved DC cable for PV system.
Cable type | Cross section (mm2) |
---|---|
Range | Recommended value |
Industry generic PV cable
(model: PV1-F)| 4.0-6.0
(12-10AWG)| 4.0(12AWG)
Table 5.1 DC Cable Specifications
The steps to assemble the DC connectors are listed as follows:
a) Strip off the DC wire about 7mm, disassemble the connector cap nut (see
picture 5.3). b) Crimping metal terminals
with crimping pliers as shown in picture 5.4.c) Insert the contact pin to the top part of the connector
and screw up the cap nut to the top part of the connector. (as shown in
picture 5.5).d) Finally insert the DC connector
into the positive and negative input of the inverter,shown as picture
5.6.
Warning:
Sunlight shines on the panel will generate voltage, high voltage in series may
cause danger to life. Therefore, before connecting the DC input line, the
solar panel needs to be blocked by the opaque material and the DC switch
should be ‘OFF’, otherwise, the high voltage of the inverter may lead to
lifethreatening conditions.
Warning:
Please use its own DC power connector from the inverter accessories. Do not
interconnect the connectors of different manufacturers. Max. DC input current
should be 20A. if exceeds, it may damage the inverter and it is not covered by
Deye warranty.
5.2 AC input terminal connection
Do not close the DC switch after the DC terminal is connected.Connect the AC
terminal to the AC side of the inverter, the AC side is equipped with Three
phase AC terminals that can be conveniently connected. Flexible cords are
recommended for easy installation. The are as shown in Table 5.2.
Warning:
Prohibit using a single circuit breaker for multiple inverters, prohibit
the connection of load between inverter circuit breakers.
Model| Cable CSA| Cable outer dia| AWG| Breaker|
Max cable length
---|---|---|---|---|---
SUN-8K-G03-LV| 6mm²| 20-25mm| 10| 30A/400V| Outside cable
(3L+N+PE)20m
Table 5.2 Cable information
The AC output connector is divided into three parts: matching socket, sleeve
and sealingsleeve, as shown in picture 5.7, the steps are as follows:
Step 1: Remove the cable sealing ring and sleeve in sequence from the AC
connector.
Step 2: Use strippers to strip the protective sheath and insulation layer of
the AC cable to the right length, as shown in Picture 5.8.Step 3: Insert the cable (L1, L2, L3, N, PE) into the sealing
sleeve.
Warning:
Be careful to distinguish the L1, L2,L3,N and PE of the AC cables.
Step 4: Use the hexagon screwdriver, loosen the bolts of the socket in turn,
and insert each cable core into the corresponding jack, and set each screw.
The connection hole of AC connection terminal labeling is shown in Picture
5.9.Step 5: Set the sleeve and sealing ring
in place.
Step 6: Connect the terminals to the inverter as shown in picture 5.10.
5.3 The connection of the ground line
Good grounding is good for resisting surge voltage shock and improving EMI
performance.There- fore, before connecting AC, DC and communication cables,
you need to ground the cable firstly. For a single system, just ground the PE
cable. For multiple machine systems, all PE cables of the inverter need to be
connected to the same grounding copper platoon to ensure the equipoten- tial
connection. The installation of the shell ground wire is shown as picture
5.11. The external protective earthing conductor is made of the same metal as
the phase conductor.
Model | Wire Size | Cable(mm²) | Torque value(max) |
---|---|---|---|
SUN-8K-G03-LV | 12AVVG | 3mm² | 8.5Nn |
Warning:
Inverter has built-in leakage current detection circuit, If an external
leakage current protection device is connected, its operating current must be
greater than 300 mA or higher, otherwise inverter may not work properly.
5.4 Max. over current protection device
In order to protect the inverter AC connection, it is recommended to install a
circuit breaker to prevent overcurrent. See table 5.3 below.
Inverter| Rated output voltage(V)| Rated output device(A)|
Current for protection
current(A)
---|---|---|---
SUN-8K-G03-LV| 127| 21A| 30
Table 5.3 Recommended current protector specifications
5.5 Inverter monitoring connection
Inverter has the function of wireless remote monitoring. The inverter with Wi-
Fi function is equipped with Wi-Fi Plug to connect the inverter and network.
Wi-Fi Plug’s operation, installation, Internet access, APP downloading and
other processes are detailed in the instructions.
5.6 Installation of datalogger
When installing the WiFi stick, tear off the sealing strip on the inverter.
Insert the datalogger into the interface and fix it with a screw. The
configuration of the datalogger needs to be performed after various electrical
connections have been completed and the inverter DC power on. When the
inverter is on the DC power, it is determined whether the datalogger is
normally electrified (The LED light shines out of the shell).
5.7 Configuration of datalogger
For the configuration of datalogger, please refer to illustrations of the
datalogger.
Startup and Shutdown
Before starting the inverter, make sure that the inverter can meet the
following conditions, otherwise it may result in fire or damage to the
inverter. In this case, we do not undertake any responsibility. At the same
time, to optimize the system configuration, it is recommended that the two
inputs be connected to the same number of photovoltaic modules.
a). The maximum open circuit voltage of each set of photovoltaic modules shall
not exceed 800Vdc under any conditions.
b). Each input of the inverter better use the same type of photovoltaic module
in series.
c). Total output power of PV shall not exceed the maximum input power of
inverter, each photovoltaic modules shall not exceed the rated power of each
channel.
6.1 Start up the inverter
When starting up the three phase string inverter, should fellow steps below:
- Starting switch on the AC breaker.
- Turn on the DC switch of the photovoltaic module, and if the panel provides sufficient starting voltage and power, the inverter will start.
- The inverter will first check the internal parameters and the grid parameters, while the liquid crystal will show that the inverter is self-checking.
- If the parameter is within acceptable range, the inverter will generate energy.
NORMAL indicator light is on.
6.2 Inverter Shutdown
Must follow below steps while shutting down the inverter:
- Switch off the AC breaker.
- Wait for 30 seconds, turn off the DC switch (if any), or simply disconnect the DC input connector. The inverter will close the LCD and all LED within two minutes.
6.3 Anti-PID Function(option)
The Anti-PID module repairs the PID effect of the PV module at night.The PID
module always runs when connected to AC.
If maintenance is required and turn off the AC switch can disable the Anti-PID
function.
Warning:
The PID functionality is automatic.When the DC bus voltage is below 50VDC, the
PID module will create 450VDC between the PV and ground.No control and
equipment are required.
Warning:
If you need to maintain the inverter, Please turn off the AC switch first,then
turn off the DC switch, and wait 5 minutes before you do other operations.
Zero-export function via energy meter
There’re two kinds of energy meters for this series inverter. First type is
Eastron SDM630-Mod- bus V2 which is able to measure the Max. 100A current
directly. More details please refer to Pic 7.1&7.2. For the Eastron SDM630 MCT
40mA, it needs external CT to measure the current. The CT power range is from
5A-2000A. More details about the Eastron SDM630 MCT, please refer to Pic 7.3 &
7.4. Also, the CHNT meter DTSU666 is supported, it can measure the Max. 80A
current directly. More details about the DTSU666, please refer to Pic 7.1 &
7.16.
When you are reading this, we believe that you have completed the connection
according to the requirements of chapter 5, if you have been running your
inverter at this time, and you want to use the zero-export function, please
turn off AC and DC switch of the inverter, and wait for 5 minutes until the
inverter completely discharged.Please follow below Picture 7.1 to connect the
energy meter.
For system wiring diagram, the red line refers to L line (L1, L2, L3), the
black line refers to the neutral line (N). Connecting energy meter RS485 cable
to inverter’s RS485 port. It’s recommended to install an AC switch between the
inverter and the utility grid, the specs of the AC switch are determined by
the power of load.
If there is no integrated DC switch inside the inverter you purchased, we
commend you to connect the DC switch. The voltage and current of the switch
depend on the PV array you access.
Warning:
In final installation, breaker certified according to IEC 60947-1 and IEC
60947-2 shall be installed with the equipment.
7.1 Multiple strings and parallel connection meters
This application is that when the string inverters work in parallel, there is
only one power grid and one load, and only one meter can be connected to
prevent reverse current, so only this many-to-one anti-reverse current
connection can be connected.
Ifthere’ s several inverters in a plant, also it can use 1pcs meter to realize
zero export function.
For example,if there’ s 3pcs inverter in the system with 1pcs meter.We need to
setup lpcs inverter as the master and others setup as slaves. And, all of them
need to connect to the meter via RS485. Below is the system diagram and
configuration of the system.
Name | Description | Range |
---|---|---|
Exp_Mode | AVG: Average power of three phase is zero exported. MIN: Phase with |
minimum load power is zero exported, while the other two phase may be
in purchase mode.| AVG/MIN
CT_Ratio| CT ratio of power grid side meter when extern CT is applied.| 1-1000
MFR| Manufacturer of the grid side meter. Modbus Address of it should be set
as 01.| AUTO/CHNT/ EASTRON
Feedin| Percentage of the Feed in power exported to the grid .| 0-110%
Shunt| Parallel mode. Set one inverter as Master, others are Slave. ONLY need
to set the master, Slave will follow the settings in the master.| OFF/Master/
Slave
ShuntQTY| Number of inverters in parallel| 1-16
Generator| DG side meter function Enable/Disable| ON/OFF
G.CT| CT ratio of power DG side meter when extern CT is applied.| 1-1000
G.MFR| Manufacturer of the DG side meter. Modbus Address of it should be set
as 02.| AUTO/CHNT/ EASTRON
G.Cap| Capacity of the DG.| 1-999kW
Note: Select Meter option in Run Param and long press ENTER button to enter this Meter Setting page.
7.2 Use of zero-export function
When the connection is completed, the following steps should be refered to
use this function:
- Turn on the AC switch.
- Turn on the DC switch, waiting for the inverter’s LCD is turned on.
- Press Enter button on the LCD panel in the main interface into the menu options, select [parameter setting] to enter setup submenu, and then select [running parameters] as shown in picture 7.34, at this time please input the default password 1234 hrough pressing the button [up down, enter], enter the operation parameter setting interface, shown as picture 7.35.
- Operate the button [up down], move setting cursor to energy meter and press the button [enter]. At this time you can turn on or turn off the energy meter by choosing [up down] button, please press [enter] button to confirm when setting done.
- Move the cursor to [OK], press [enter] to save the settings and exit the running parameters page, otherwise the settings are invalid.
- If set up successfully, you can return to the menu interface, and display the LCD to [home page] by press the [up down] button. If it displays [meter power XXW], the zero-export function setting is completed. Shown as picture 7.36.
- Meter power XXW shows positive means grid is supplying the load, and no power fed into grid. if meter power shows negative, it means PV energy is being sold to grid or energy meter wiring conncetion has problem.
- After properly connection is done, wait for inverter starting. If the power of the PV array meets the current power consumption, the inverter will keep a certain output to counteract the power of the grid without backflow .
7.3 Notes while using zero export function
For your safety and the operation of limiter function of the inverter, we put
forward the follow- ing suggestions and precautions:
Safety Hint:
Under zero export mode we strongly recommend that the two PV arrays are
formed by the same number of PV panels of the same size, which will make the
inverter more responsive to limit the power.
Safety Hint:
While the utility power is negative and inverter has no output power, that
means the orientation of the current sensor is wrong, please turn off the
inverter and change orientation of the current sensor.
7.4 How to browse the load power of your PV grid-tie plant on monitoring
platform?
If you want to browse load power of the system and how much energy (KWH) does
it export to grid(inverter output power is used to power the load firstly and
then the surplus energy will feed into grid). You also need to connect the
meter according to above diagram. After the connection completed successfully,
the inverter will show the load power on the LCD. But please don’ t setup
“Meter ON” . Also, you will be able to browse the load power on the monitoring
platform.
The plant setting method as below description.
Firstly, go to the solarman platform(https://pro.solarmanpv.com, this link
is for solarman distributor account; or https://home.solarmanpv.com, this
link is for solarman end user account;) plant home page and click “edit”
.And then choose your system type as
“Self-consumption”Secondly, go to plant page, if it shows
the PV power, load power and grid power, which means the configuration is
correct.
General Operation
During normal operation, the LCD shows the current status of the inverter, including the current power, total generation, a bar chart of power operation and inverter ID,etc. Press the Up key and the Down key to see the current DC voltage, DC current, AC voltage, AC current,inverter radiator temperature,software version number and Wifi connection state of the inverter.
*Note : These parameters will be avaiable after the meter is connected successfully. Otherwise, it won’t show.Pic 8.1 LCD operation flow chart
8.14 The initial interface
From the initial interface, you can check PV power, PV voltage, grid voltage,
inverter ID, model and other infomation.
Press UP or Down, you can check inverter DC voltage, DC current, AC voltage, AC current and inverter temperature.
ImpEp: Daily energy purchased from grid;
Total: Total energy purchased from grid. ExpEp: Daily energy sold to
grid;
Total: Total energy sold to grid.
8.2 Submenus in the Main Menu
There are five submenus in the Main Menu.
8.2.1 Device information
You can see the LCD software VerA238 and control board software Ver1400. In
this interface, there are parameters such as rated power communication
addresses.
8.2.2 Fault Record
It can keep Eight fault records in the menu including time, customer can deal
with it depends on the error code. 8.2.3 ON/OFF
setting When the inverter is turned off, it
stops working immediately, and go to standby mode and then will go to self-
test program again. If it passed the self-test, it will start to work again.
8.2.5 Parameter setting
There are five submenus in the setup.Setting includes system param, run param,
protect param, comm: param. All of these information for maintenance
reference.
8.3 System param setting
System Param includes time set, language set, display set and factory
reset.
8.4 Running param set
Warning:
Password required– only for access-authorized engineer. Un-authorized access
may avoid the warranty. The initial password is 1234.
Name | Description | Range |
---|---|---|
ActiveP | Adjust the output active power in % | 0-110% |
Q-Mode | Multiple reactive power control modes | OFF/Q(P)/PF(P) /Q(U)/PF/Q(%) |
Vref | Grid reference voltage for functions including Q(U),PF(P),P(U)etc. |
80-260V
ReactP| Adjust reactive power output in %| -100%-+100%
PF| Power Fator| -1-0.8∼F0.8-1
Fun ISO| Insulation resistance detection| ON/OFF
Fun RCD| Residual current detection| ON/OFF
Self-check| Inverter’s self-check time.The default value 60s| 0-1000s
Island| Anti-islanding protection| ON/OFF
Meter| If you want to use zero output mode,please set Meter to ON and select
OFF to view data only| ON/OFF
Feed IN %| It is used to deploy how much power can be feed in to grid when the
inverter works under zero export mode.(For example,Feed_in=50% of the 8KW
model and load power is 3KW. which means Max 4KW power can be feed intogrid
after inverter providing 3Kw to the load firstly.| 0-100%
Pic 8.26
Name | Description | Range |
---|---|---|
ARC | Arc-fault detection function | ON/OFF/CLR |
OF-Derate | Active power response to overfrequency | ON/OFF/HYS |
U F-Uprate | Active power response to under-frequency | ON/OFF |
PU | power response to grid voltage deviation | ON/OFF |
LVRT | voltage ride through function | ON/OFF |
HVRT | voltage ride through function | ON/OFF |
PowerLim | Hard/soft export limit control | ON/OFF |
DRM | Demand Response Modes | ON/OFF |
Sunspec | Sunspec Function | ON/OFF |
WGraStr | Percentage of Nominal Power per second | o.1%∼1o% |
WGra | percentage of Nominal Power per second | 0.1%∼10% |
ZVRT | Zero Current Mode | ON/OFF |
Pic 8.27
Over-frequency Response
This series inverter provides “over-frequency response” function.
Long pressing the “OFD Mode” to enter the “over-frequency response” setting
menu. Tab. 8-1 Definition of Over-
frequency Response Parameters
Parameter | Range | Description |
---|---|---|
Fstr | 45HZ-65HZ | The Start frequency value for overfrequency response. |
Fstop | 45HZ-65HZ | The Stop frequency value for over-frequency response. |
RecGra | [3,500] 0.010/oPmaxis | Rate of Power recovery(Percentage of active |
power)
For example, StrtPT: 50.5Hz, StopPT:
51.5Hz, RecPT: 50.1Hz, when the grid frequency increases beyond Start: 50.5Hz,
the inverter will linearly reduce the power output with a gradient of 100%
Pmax/Hz until it reaches StopPT: 51.5Hz.Fig. 8-1 Frq-Watt Mode for Over-frequency ConditionsWhen the frequency exceeds
Fstop: 51.5Hz, the inverter output should stop (ie 0 W).
When the frequency is lower than Fstop: 51.5 Hz, the inverter will linearly
increase the power output with a gradient of 100% Pmax/Hz until it reaches
Fstr: 50.5 Hz.
In the hysteresis mode, when the frequency is lower than Fstop: 51.5 Hz, the
inverter will not increase the power output until it is lower than RecPT: 50.1
Hz.The inverter provides a reactive
power regulation function.
Tap Reactive Power Regulation Mode to select proper regulation mode and set
the corresponding parameters.
Pic 8.34 OF-Derate
-
“OFF” Mode
The reactive power regulation function is disabled. The PF is fixed at +1.000 -
Q(%)
Adjust reactive power output in %. -
“PF” Mode
The power factor (PF) is fixed and the reactive power is regulated by the parameter PF. The PF ranges from 0.8 leading to 0.8 lagging.
·Leading: the inverter is absorbing reactive power from the Grid.
·Lagging: the inverter is injecting reactive power into the grid. -
“Q(U)” Mode
The reactive power output of the inverter varies in response to the grid voltage. -
“Q(P)” Mode
The reactive power output by the inverter is controlled by the active power of the inverter. -
“PF(P)” Mode
The PF is controlled by the active power of the inverter.
“PU” Mode
The active power output of the inverter varies in response to the grid
voltage.
Pic 8.36 Active Power Regulation Curve in PU Curve
Parameter | Range | Descrption |
---|---|---|
P1 | 0%-110% Pn | Value of P/Pn at point (P1,U1) on the PU mode curve |
Ul | 0% -150% Vref | Grid voltage limit at point (P1,U1) on the PU mode curve |
P2 | 0%-110% Pn | Value of P/Pn at point (P2,U2) on the PU mode curve |
U2 | 0% -150% Vref | Grid voltage limit at point (P2,U2) on the PU mode curve |
P3 | 0%-110% Pn | Value of P/Pn at point (P3,U3) on the PU mode curve |
U3 | 0% -150% Vref | Grid voltage limit at point (P3,U3) on the PU mode curve |
P4 | 0%-110% Pn | Value of P/Pn at point (P4,U4) on the PU mode curve |
U4 | 0% -150% Vref | Grid voltage limit at point (P4,U4) on the PU mode curve |
Ti | 0-10005 | The adjustment time of PU Curve in seconds (time to accomplish a |
change of 95%).
“PU” Mode Parameters Explanation
“Q(U)” Mode
Parameter | Range | Description |
---|---|---|
Pstart | 0%-130% Rate out power | The QU mode starts when the active power is |
greater than this value
Psto p| 0%-130% Rate out power| The QU mode stops when the active power is
less than this value
Q1| -60% -60% Q/Pn| Value of Q/Pn at point (U1,Q1) on the Q(U) mode curve
1/1.| 0-110% VRated| Grid voltage limit at point (U1,Q1) on the Q(U) mode
curve
Q2| -60% -60% Q/Pn| Value of Q/Pn at point (U2,Q2) on the Q(U) mode curve
V2| 0-110% VRated| Grid voltage limit at point (U2,Q2) on the Q(U) mode curve
Q3| -60% -60% Q/Pn| Value of Q/Pn at point (U3,Q3) on the Q(U) mode curve
V3| 0-110% VRated| Grid voltage limit at point (U3,Q3) on the Q(U) mode curve
Q4| -60% -60% Q/Pn| Value of Q/Pn at point (U4,Q4) on the Q(U) mode curve
V4| 0-110% VRated| Grid voltage limit at point (U4,Q4) on the Q(U) mode curve
Q5| -60% -60% Q/Pn| Value of Q/Pn at point (U5,Q5) on the Q(U) mode curve
V5| 0-110% VRated| Grid voltage limit at point (U5,Q5) on the Q(U) mode curve
Q6| -60% -60% Q/Pn| Value of Q/Pn at point (U6,Q6) on the Q(U) mode curve
V6| 0-110% VRated| Grid voltage limit at point (U6,Q6) on the Q(U) mode curve
RMpTime| 0-1000s| Increase or decrease the time required for the reactive
power to reach the specified value of the curve.
“Q(U)” Mode Parameters Explanation
“Q(P)” Mode
The reactive power output by the inverter is controlled by the active power of
the inverter.
Parameter | Range | Description |
---|---|---|
P1 | 0%-100% Pn | Power value/Pn at point (P1,Q1) on the Q(P) mode curve |
1 | -60% 60% Q/Pn | Reactive power value at point (P1,Q1) on the Q(P) mode curve |
P2 | 0%-100% Pn | Power value/Pn at point (P2,02) on the Q(P) mode curve |
Q2 | -60% 60% QJPn | Reactive power value at point (P2,02) on the Q(P) mode |
curve
P3| 0%-100% Pn| Power value/Pn at point (P3,03) on the Q(P) mode curve
Q3| -60% 60% Q/Pn| Reactive power value at point (P3,03) on the Q(P) mode
curve
P4| 0%-100% Pn| Power value/Pn at point (P4,04) on the Q(P) mode curve
Q4| -60% 60% Q/Pn| Reactive power value at point (P4,04) on the Q(P) mode
curve
P5| 0%-100% Pn| Power value/Pn at point (P5,05) on the Q(P) mode curve
5| -60% 60% Q/Pn| Reactive power value at point (P5,05) on the Q(P) mode curve
P6| 0%-100% Pn| Power value/Pn at point (P6,06) on the Q(P) mode curve
Q6| -60% 60% Q/Pn| Reactive power value at point (P6,06) on the Q(P) mode
curve
“Q(P)” Mode Parameters Explanation
“PF(P)” Mode
The output power factor is controlled by the active power of the
inverter.
Parameter | Range | Description |
---|---|---|
Vstart | 0-150% Vref | The PFP mode is enable when grid voltage is greater than |
Vstart
Vstop| 0-150% Vref| The PFP mode is disable when grid voltage is less than
Vstop
P1| 0-110% Pn| Power value at point (PF1,P1) on the PF(P) Curve
PF1| 0.8 leading -0.8 lagging| PF value at point (PF1,P1) on the PF(P) Curve
P2| 0-110% Pn| Power value at point (PF2,P2) on the PF(P) Curve
PF2| 0.8 leading -0.8 lagging| PF value at point (P2,PF2) on the PF(P) Curve
P3| 0-110% Pn| Power value at point (P3,PF3) on the PF(P) Curve
PF3| 0.8 leading -0.8 lagging| PF value at point (P3,PF3) on the PF(P) Curve
P4| 0-110% Pn| Power value at point (P4,PF4) on the PF(P) Curve
PF4| 0.8 leading -0.8 lagging| PF value at point (P4,PF4) on the PF(P) Curve
P5| 0-110% Pn| Power value at point (P5,PF5) on the PF(P) Curve
PF5| 0.8 leading -0.8 lagging| PF value at point (P5,PF5) on the PF(P) Curve
P6| 0-110% Pn| Power value at point (P6,PF6) on the PF(P) Curve
PF6| 0.8 leading -0.8 lagging| PF value at point (P6,PF6) on the PF(P) Curve
RMpTime| 0-1000s| The time of the PFF Curve in seconds (time to accomplish a
change of 95%).
“PF(P)” Mode Parameters Explanation
8.5 Protect Param
Warning:
Engineer Only.
We will set the param depends on the safety requirements, so customers don’t
need to reset it. The password is same as 8.4 Running param
Please set the proper grid parameters according to the requirements of your current country’s grid regulations.If you are not clear about it, please consult your installer.
8.6 Comm. param set
Repair and Maintenance
String type inverter doesn’t need regular maintenance. However,debris or dust
will affect heat sink’s thermal performance. It is better to clean it with a
soft brush. If the surface is too dirty and affect the reading of LCD and LED
lamp, you can use wet cloth to clean it up.
High Temperature Hazard:
When the device is running, the local temperature is too high and the touch
can cause burns. Turn off the inverter and wait for it cooling, then you can
clean and maintain.
Safety Hint:
No solvent, abrasive materials or corrosive materials can be used for cleaning
any parts of the inverter.
Error information and processing
Inverter has been designed in accordance with international grid tied standards for safety, and electromagnetic compatibility requirements. Before delivering to the customer the inverter has been subjected to several tests to ensure its optimal operation and reliability.
10.1 Error code
If there is any failure,the LCD screen will display an alarm message. In this
case,the inverter may stop feeding energy into the grid. The alarm description
and their corresponding alarm messages are listed Table 10.1.
Error code | Description | Ongrid – Three Phase |
---|---|---|
F1 | DC input polarity reverse fault | Check the PV input polarity. |
F2 | DC insulation impedance permanent fault | Check the grounding cable of |
inverter.
F3| DC leakage current fault| Hardly appear the code. Never ever happened so
far.
F4| Ground fault GFDI| Check the solar panel output connection.
F5| Read the memory error| Failure in reading memory (EEPROM). Restart the
inverter if the fault still exists, contact your installer or Deye service.
F6| Write the memory error| Failure in writing memory (EEPROM). Restart the
inverter if the fault still exists, contact your installer or Deye service.
F7| GFDI blown fuse| Hardly appear the code. Never ever happened so far.
F8| GFDI grounding touch failure| Hardly appear the code. Never ever happened
so far.
F9| IGBT damaged by excessive drop voltage| Hardly appear the code. Never ever
happened so far.
F10| Auxiliary l
power supply switch p ppy
failure| 1.It tells the DC 12V is not existed.
2.Restart the inverter, if the fault still exists, please contact your
installer or Deye service.
F11| AC main contactor errors| Hardly appear the code. Never ever happened so
far.
F12| AC auxiliary contactor errors| Hardly appear the code. Never ever
happened so far.
F13| reserved| 1.Loss of one phase or AC voltage detection part failure or
relays not closed.
2.Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F14| DC firmware over current| Hardly appear the code. Never ever happened so
far.
F15| AC firmware over current| 1.The internal AC sensor or detection circuit
on control board or connection wire may loose.
2.Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F16| GFCI(RCD) Ac leakage current fault| 1.This fault means the average
leakage current is over 300mA. Check whether DC power supply or solar panels
is ok, then check ‘Test data’-> ‘diL’value is about 40; Then check the leakage
current sensor or circuit (the following picture). Checking test data needs
using big LCD.
2.Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F17| Three phase current, over-current fault| Hardly appear the code. Never
ever happened so far.
F18| AC over current fault of hardware| 1.Check AC sensor or detection circuit
on control board or connection wire.
2.Restart the inverter or factory reset, if the error still exists, please
contact your installer or Deye service.
F19| All hardware failure synthesis| Hardly appear the code. Never ever
happened so far.
F20| DC over current fault of the hardware| 1.Check whether solar panel output
current is within the allowed range.
2.Check DC current sensor and its detection circuit.
3.Check if the inverter FW version is suitable for the hardware.
4.Restart the inverter, if the error still exists, please contact your
installer or Deye service.
F21| DC leakage flow fault| Hardly appear the code. Never ever happened so
far.
F22| Crash stop (if there is a stop button)| Contact your installer for help.
F23| AC leakage current is transient over current| 1.This fault means the
leakage current is above 30mA suddenly. Check whether DC power supply or solar
panels is ok, then check ‘Test data’-> ‘diL’value is about 40; Then check the
leakage current sensor or circuit. Check test data needs using big LCD.
2.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F24| DC insulation impedance failure| 1.Check Vpe resistance on main board or
detection on control board. Check PV panels is OK. Many times this issue is
the PV problem.
2.Check whether the PV panel (aluminum frame) is grounded well and inverter is
grounded well. Open the cover of inverter and then check the inside ground
cable is fixed well on the shell.
3.Check if the AC/DC cable, terminal block are shorted to ground or the
insulation is damaged.
4.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F25| DC feedback fault| Hardly appear the code. Never ever happened so far.
F26| The DC busbar is unbalanced| 1.Check whether the ‘BUSN’ cable or driver
board power supply cable is loose.
2.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F27| DC end insulation error| Hardly appear the code. Never ever happened so
far.
F28| Inverter 1 DC high fault| Hardly appear the code. Never ever happened so
far.
F29| AC load switch failure| Hardly appear the code. Never ever happened so
far.
F30| AC main contactor failure| 1.Check relays and AC voltage of relays.
2.Check relays driver circuit. Check if the software is not suitable for this
inverter. (Old inverter not have relays detection function)
3.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F31| Relay open circuit fault| 1.At least one Relay can’t be closed. Check
relays and its driver signal. (Old inverter not have relays detection
function)
2.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F32| Inverter 2 dc high fault| Hardly appear the code. Never ever happened so
far.
F33| AC over current| Hardly appear the code. Never ever happened so far.
F34| AC current over load| Hardly appear the code. Never ever happened so far.
F35| No AC grid| 1.Check AC grid voltage. Check AC voltage detection circuit.
Check if the AC connector in good condition. Check whether the AC grid is
normal in voltage.
2.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F36| AC grid phase error| Hardly appear the code. Never ever happened so far.
F37| AC three-phase voltage unbalance failure| Hardly appear the code. Never
ever happened so far.
F38| AC three-phase current unbalance failure| Hardly appear the code. Never
ever happened so far.
F39| AC over current(one cycle)| 1.Check AC current sensor and its circuit.
2.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F40| DC over current| Hardly appear the code. Never ever happened so far.
F41| AC Line W,U over voltage| Check the AC voltage protection setting. And
Check if the AC cable is too thin.Check the voltage difference between LCD and
meter.
F42| AC Line W,U low voltage| Check the AC voltage protection setting. Check
the voltage difference between LCD and meter. Also need to check whether AC
cables are all firmly and correctly connected.
F43| AC Line V,W over voltage| Check the AC voltage protection setting.And
Check if the AC cable is too thin.Check the voltage difference between LCD and
meter.
F44| AC Line V,W low voltage| Check the AC voltage protection setting. Check
the voltage difference between LCD and meter. Also need to check whether AC
cables are all firmly and correctly connected.
F45| AC Line U,V over voltage| Check the AC voltage protection setting.And
Check if the AC cable is too thin.Check the voltage difference between LCD and
meter.
F46| AC Line U,V low voltage| Check the AC voltage protection setting.
F47| AC Over frequency| Check the frequency protection setting.
F48| AC lower frequency| Check the frequency protection setting.
F49| U phase grid current DC component over current| Hardly appear the code.
Never ever happened so far.
F50| V phase grid current DC component over current| Hardly appear the code.
Never ever happened so far.
F51| W phase grid current DC component over current| Hardly appear the code.
Never ever happened so far.
F52| AC inductor A, phase current DC current high| Hardly appear the code.
Never ever happened so far.
F53| AC inductor B, phase current DC current high| Hardly appear the code.
Never ever happened so far.
F54| AC inductor C, phase current DC current high| Hardly appear the code.
Never ever happened so far.
F55| DC bulbar voltage is too high| 1.Check PV voltage and Ubus voltage and
its detection circuit. If the PV input voltage exceeds the limit, please
reduce the number of solar panels in series.
2.For Ubus voltage, please check the LCD display.
F56| DC bulbar voltage is too low| 1.It tells the PV input voltage is low and
it always happens in the early morning.
2.Check PV voltage and Ubus voltage. When inverter is running, then showing
F56, maybe Loss of driver or need update firmware.
3.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
F57| AC reverse irrigation| AC reverse irrigation.
F58| AC grid U over current| Hardly appear the code. Never ever happened so
far.
F59| AC grid V over current| Hardly appear the code. Never ever happened so
far.
F60| AC grid W over current| Hardly appear the code. Never ever happened so
far.
F61| Reactor A phase over current| Hardly appear the code. Never ever happened
so far.
F62| Reactor B phase over current| Hardly appear the code. Never ever happened
so far.
F63| ARC fault| 1.Check PV module cable connection and clear the fault;
2.Seek help from us, if can not go back to normal state.
F64| IGBT heat sink high temperature| 1.Check temperature sensor. Check if
firmware is suitable for the hardware. Check if the inverter is its right
model.
2.Restart the inverter, if the fault still exists, contact your installer or
Deye service.
Table 10.1 Error codes and their solutions
Safety Hint:
If your string inverter has any of the fault information shown in Table
10.1,and when you reset the machine and still don’t solve the problem,please
contact our distributor and provide the below details:
- Serial number of the inverter;
- The distributor/dealer of the inverter(if available);
- Installation date;
- The discription of problem(include LCD’error code and LED starus indicator lights);
- Your contact details.
Specification
Model | SUN-8K-G03-LV |
---|
Input Side
Max.DC Power(kW)| 10.4kW
Max.DC Input Voltage(V)| 800V
Start-up DC Input Voltage(V)| 250V
MPPT Operating Range(V)| 200V-700V
Max.DC Input Current(A)| 13A+26A
Max. Short Circuit Current (A)| 19.5A+39A
Number of MPPT/Strings per MPPT| 2/1+2
MAX inverter backfeed current (A)| OA
Output Side
Rated Output Power(kW)| 8kW
Max.Active Power(kW)| 8.8kW
Rated AC Grid Voltage(V)| 3L/N/PE 127/220V
AC Grid Voltage Range(V)| 0.85Un-1.1Un (this may vary with grid standards)
Rated Grid Frequency(Hz)| 50/60 (Optional)
Operating Phase| Three phase
Rated AC Grid Output Current(A)| 21A
Max.AC Output Current(A)| 23.1A
Maximum output fault current (a.c. A, peak )| 40.1A
Maximum output over current protection (a.c. A,peak)| 44.5A
Output Power Factor| 0.8 leading to 0.8 lagging
Grid Current THD| <3%
DC Injection Current| <0.5%
Grid Frequency Range| 45-55 or 55-65 (Optional)
Efficiency
Max.Efficiency| 99.%
Euro Efficiency| 98.%
MPPT Efficiency| >99%
Surge Protection| DC Type II / AC Type II
General Data
Cabinet Size(WHD) [mm]| 332 x472 x203 (Excluding connectors and brackets)
Weight(kg)| 15
Topology| Transformerless
Internal consumption| <1W (Night)
Operating temperature| -25 to +65°C,>45°C derating
Ingress protection| IP65
Noise Emission(Typical)| ≤ 40 dB (A)
Type Of Cooling| Smart cooling
Permissible Altitude (m)| 4000m
Warranty [year]| Standard 5 years, extended warranty
Grid Connection Standard| I EC61727,I EC62116
Operation surrounding humidity| 0-100%
Safety EMC / Standard| I EC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
Display| LCD 1602
Interface| RS485/RS232/Wifi/LAN
Protective Class| Class I
Over Voltage Category| II (AC), II (DC)
Inverter Topology| Non-is olated
Pollution degree| PD2(Inside), PD3(Outside)
EU Declaration of Conformity
within the scope of the EU directives
- Electromagnetic compatibility 2014/30/EU (EMC)
- Low Voltage Directive 2014/35/EU (LVD)
- Restriction of the use of certain hazardous substances 2014/65/EU(RoHS)
NINGBO DEYE INVERTER TECHNOLOGY CO.,LTD. confirms herewith that the products described in this document are in compliance with the fundamental requirements and other relevant provisions of the above mentioned directives. The entire EU Declaration of Conformity and certificate can be found at https://www.deyeinverter.com/download/#string-inverter.
Product: Grid-connected PV Inverter
Models: SUN-3K-G03-1;SUN-3K-G03;SUN-3.2K-G03;SUN-4K-G03;SUN-5K-G03;SUN-6K-G03
;SUN-7K-G03;
SUN-8K-G03;SUN-9K-G03;SUN-10K-G03;SUN-12K-G03;SUN-15K-G03;SUN-6K-G03-LV;SUN-
8K-G03-LV;
Name and address of the manufacturer: Ningbo Deye Inverter Technology Co.,
Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China
This declaration of conformity is issued under the sole responsibility of the
manufacturer. Also this product is under manufacturer’s warranty.
This declaration of conformity is not valid any longer: if the product is
modified, supplemented or changed in any other way, as well as in case the
product is used or installed improperly.
The object of the declaration described above is in conformity with the
relevant Union harmonization legislation:
The Low Voltage Directive (LVD) 2014/35/EU;the Electromagnetic Compatibility
(EMC) Directive 2014/30/EU;the restriction of the use of certain hazardous
substances (RoHS) Directive 2011/65/EU.
References to the relevant harmonized standards used or references to the
other technical specifications in relation to which conformity is declared:
LVD:|
---|---
EN 62109-1:2010|
EN 62109-2:2011|
EMC:|
EN 61000-6-1:2007|
EN 61000-6-3:2007+A1:2011+AC:2012|
EN 61000-3-2:2014|
EN 61000-3-3:2013|
EN 61000-3-11:2000|
EN 61000-3-12:2011|
Nom et Titre / Name and Title:
Bard Dai Senior Standard and Certification Engineer Au nom de / On behalf
of:” Ningbo Deye Inverter Technology Co., Ltd.
Date / Date (yyyy-mm-dd):2023-10-14
A / Place:Ningbo, China
EU DoC – v1
Ningbo Deye Inverter Technology Co., Ltd.
No. 26 South YongJiang Road, Daqi, Beilun, NingBo, China
NINGBO DEYE INVERTER TECHNOLOGY CO., LTD.
Add. : No.26 South YongJiang Road, Daqi, Beilun, NingBo, China.
Tel. : +86 (0) 574 8622 8957
Fax. : +86 (0) 574 8622 8852
E-mail. : service@deye.com.cn
Web. : www.deyeinverter.com
231014006
www.deyeinverter.com