PARMIDA PLED-T818W3KV2-AB-CL LED Hybrid Type A Plus B Light Tube Installation Guide
- June 15, 2024
- PARMIDA
Table of Contents
- PLED-T818W3KV2-AB-CL LED Hybrid Type A Plus B Light Tube
- INSTALLATION INSTRUCTION
- WARNING
- “PLUG & PLAY” INSTALLATION (TYPE A)
- “PLUG & PLAY” WIRING DIAGRAM
- RETROFIT INSTALLATION (TYPE B)
- RETROFIT INSTALLATION (TYPE B) CONTD
- BALLAST COMPATIBILITY LIST. 4FT T8 TYPE A+B TUBE
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PLED-T818W3KV2-AB-CL LED Hybrid Type A Plus B Light Tube
4FT T8 TYPE A+B TUBE
INSTALLATION MANUAL
PLED-T818W3KV2-AB-CL
PLED-T818W3KV2-AB-F
PLED-T818W4KV2-AB-CL
PLED-T818W4KV2-AB-F
PLED-T818W5KV2-AB-CL
PLED-T818W5KV2-AB-F
PLED-T818W6KV2-AB-CL
PLED-T818W6KV2-AB-F
WWW.PARMIDA.COM
INSTALLATION INSTRUCTION
Dual Mode Internal Driver For Compatible Tube
WARNING
-
Risk of fire or electric shock. When installing with an electronic ballast, please check the compatible ballast list first. If you do not
find your ballast on the list, please bypass the fixture. Do not install the LED Tube with a ballast that is not listed on our compatible
ballast list – risk of fire. -
Risk of fire or electric shock. LED Retrofit Kit installation requires knowledge of luminaires electrical systems. If not qualified, do not
attempt installation. Contact a qualified electrician. -
Risk of fire or electric shock. Install this kit only in the luminaires that have the construction features and dimensions shown in the
photographs and/or drawings and where the input rating of the retrofit kit does not exceed the input rating of the luminaire. -
Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
-
To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
-
Installers should not disconnect existing wires from lampholder terminals to make new connections at lampholder terminals.
-
Instead installers should cut existing lampholder leads away from the lampholder and make new electrical connections to lampholder
lead wires by employing applicable connectors. -
For a linear tubular LED lamp conversion, there shall be text or a diagram showing how the supply connections were made to the
lampholders so the correct connections will be made to the lamp when the lamp is installed or replaced. -
This retrofit kit is accepted as a component of a luminaire where the suitability of the combination shall be determined by authorities
having jurisdiction. -
If the tube is installed as Type B, the luminaire, once modified as retrofit fixture will no longer operate fluorescent lamps.
-
These lamps should be installed by a licensed electrician.
-
These lamps are to be used indoors (damp or dry locations only). Not suitable for wet location.
-
Under Type A setting this device can be used with compatible emergency ballasts and compatible dimming ballasts (please refer to
compatible ballast list). -
Under Type B setting this device is not suitable for use with emergency ballasts or dimming ballasts.
“PLUG & PLAY” INSTALLATION (TYPE A)
- Before installation, please check our compatible ballast list and ensure your
ballast is listed. If it is not listed, please install your LED tubes according to the
Type B Installation Method instructions below.
1. Disconnect power to the light fixture at the breaker panel before
installation.
2. Remove the diffuser from the light fixture (if applicable).
3. Remove the existing fluorescent tubes from the light fixture.
4. Install the LED tubes.
5. Install diffuser (if removed in step 2).
6. Switch on power to the light fixture.
“PLUG & PLAY” WIRING DIAGRAM
RETROFIT INSTALLATION (TYPE B)
- Can be installed with either single or double ended connection.
- Double – ended connection can be used with either shunted or non-shunted sockets (tombstones). For single – ended connection,
please use non-shunted sockets.
Please install your LED tubes according to the Type B Installation Method instructions below
1. Disconnect power to the light fixture at the breaker panel before
installation.
2. Remove the diffuser lens from the light fixture (if applicable).
3. Remove any existing fluorescent tubes by rotating them a one quarter turn
and sliding them out.
4. Remove ballast cover (cover may be secured with screws or tabs).
5. Retrofit light fixture according to the diagram applicable to your
fixture.
RETROFIT INSTALLATION (TYPE B) CONTD
A. Retrofit luminaire with inductive ballast
AC INPUT
1.Disconnect the wires between starter and ballast according
to the figure.
2. Connect two wires to branch circuit L and N according to
the figure.
B. Retrofit luminaire with electronical ballast
A B 1. Disconnect the wires between tombstone and ballast
according to the figure.
2. Connect two wires to branch circuit L and N according to
the figure.
C. Retrofit luminaire with two lamps and one electronical ballast
1. Disconnect the wires between tombstone and ballast
according to the figure.
2. Connect two wires to branch circuit L and N according to
the figure.
D. Retrofit luminaire with three lamps and one electronical ballast
1. Disconnect the wires between tombstone and ballast
according to the figure.
2. Connect two wires to branch circuit L and N according to
the figure
E. Retrofit luminaire with four lamps and one electronical ballast
1. Disconnect the wires between tombstone and ballast
according to the figure.
2. Connect two wires to branch circuit L and N according to
the figure.
BALLAST COMPATIBILITY LIST. 4FT T8 TYPE A+B TUBE
6. Insert LED tubes
a. Read the label on the LED tube to ensure the power end of the LED is
aligned with the powered tube
socket, then insert the LED tube by sliding pins into sockets and rotating a
quarter turn until the LED tube locks in place.
b. LED lamps are now fully installed.
7. Replace the diffuser lens of the light fixture (if applicable).
8. After modification completed. Attach the Replacement Marking and
Cautionary Label to a visible place on the luminaire
and keep it visible after installation.
9. Restore power to the circuit/luminaire and test the light. If necessary,
adjust position of the LED tube(s).
BRAND MODEL NO.
KEYSTONE KTEB-232-UV-IS-N-P
KEYSTONE KTEB-126-1-TP-LC/A
KEYSTONE KTEB-232-UV-IS-N-P
OSRAM SYLVANIA QTP4X32T8/UNV ISN-SC
OSRAM SYLVANIA QHE 2X32T8/UNV PSN-MC
OSRAM SYLVANIA QTP2X32T8/UNV ISN-SC
OSRAM SYLVANIA QTP 3X32T8/UNV ISN-SC
OSRAM SYLVANIA QHE2X32T8/UNV ISN-SC
OSRAM SYLVANIA QHE 4X32T8/UNV ISN-SC
OSRAM SYLVANIA QHE4XLED32T8/UNV ISN-SC
OSRAM SYLVANIA QHE 3XLED32T8/UNV ISN-SC
OSRAM SYLVANIA QHE2X59T8/UNV ISL-SC
OSRAM SYLVANIA QHE 1X32T8/UNV ISN-SC
OSRAM SYLVANIA QHE1X32T8/UNV ISL-SC
PHILIPS ADVANCE IOP-2P59-N
PHILIPS ADVANCE ICN-1P32-N
PHILIPS ADVANCE ICN-2P32-N
PHILIPS ADVANCE ICN-3P32-N
PHILIPS ADVANCE ICN-4P32-N
PHILIPS ADVANCE IOP-2PSP32-N
PHILIPS ADVANCE REZ-2S32-SC
PHILIPS ADVANCE IOPA-2P32-LW-N
BRAND MODEL NO.
PHILIPS ADVANCE IOP-4PSP32-SC
PHILIPS ADVANCE IOPA-2P32-N
PHILIPS ADVANCE IOPA-3P32-N
PHILIPS ADVANCE IOPA-4P32-N
PLUSRITE BAF232IS/MV
PLUSRITE BAF332IS/MV
ROBERTSON ISL432T8HEMV3P20160
SUNLITE 40155-SU.SB/232/MV
UITRASAVE UT 232347
UNIVERSAL B432IUNVHE-A
UNIVERSAL B232IUNVHP-N
UNIVERSAL B232IUNVHP-N
UNIVERSAL B432IUNVHP-A
UNIVERSAL B432PUNVHE-A
UNIVERSAL B232PUNVHE-B
UNIVERSAL B332IUNVHP-A
UNIVERSAL B432IUNVHE-A
UNIVERSAL B332IUNVEL-A
UNIVERSAL QHE 3X32T8/UNV ISH HT-SC
UNIVERSAL B232IUNVHEH-A
UNIVERSAL B332IUNVHE-A
WARNING: Please note that Parmida LLC is not responsible for any problems
occurring from installation with any ballast model
number not found on our compatible ballast list . Any subsequent issues
resulting from installation with a non-listed ballast will not be
covered under our warranty.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>