HEAT GLO 6KX-AU Balanced Flue Gas Fireplace Instruction Manual
- June 14, 2024
- HEAT GLO
Table of Contents
- 6KX-AU Balanced Flue Gas Fireplace
- Product Information
- Specifications:
- Product Usage Instructions:
- Installation and Appliance Setup
- Safety Warnings
- Danger
- Q: Can I use this appliance as a fireplace insert?
- Q: How should I handle the hot glass?
- Q: Can I store flammable materials near this appliance?
- Q: Can I modify this appliance?
6KX-AU Balanced Flue Gas Fireplace
Product Information
Specifications:
- Models: 6KX-AU
- Ref No: GMK10810 AS/NZS 5263.1.8
Product Usage Instructions:
Installation and Appliance Setup
CAUTION! Risk of Fire! DO NOT store instruction manuals inside
fireplace cavity. High temperatures could cause a fire.
INSTALLER: Leave this manual with the appliance, not inside the
appliance. CONSUMER: Retain this manual for future reference. Do
not store inside the appliance.
Safety Warnings
WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety
warnings exactly could result in serious injury, death, or property
damage.
-
DO NOT try to light any appliance.
-
DO NOT touch any electrical switch. DO NOT use any phone in
your building. -
Leave the building immediately.
-
Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions. -
If you cannot reach your gas supplier, call the fire
department.
Danger
NOTE: NOT INTENDED FOR FIREPLACE INSERT.
Decorative barrier front must be ordered separately at the time
of appliance purchase. See Section 3.B.
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
NEVER ALLOW CHILDREN TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall be
installed for the protection of children and other at-risk
individuals.
DO NOT PLACE ARTICLES ON OR AGAINST THIS APPLIANCE. DO NOT USE
OR STORE FLAMMABLE MATERIALS NEAR THIS APPLIANCE. DO NOT SPRAY
AEROSOLS IN THE VICINITY OF THIS APPLIANCE WHILE IT IS IN
OPERATION. DO NOT MODIFY THIS APPLIANCE.
FAQ
Q: Can I use this appliance as a fireplace insert?
A: No, this appliance is not intended for fireplace insert
use.
Q: How should I handle the hot glass?
A: DO NOT TOUCH GLASS UNTIL COOLED. NEVER ALLOW CHILDREN TO
TOUCH GLASS. It is important to exercise caution and ensure the
glass has cooled down before touching it to avoid burns.
Q: Can I store flammable materials near this appliance?
A: No, it is important to not use or store flammable materials
near this appliance to prevent the risk of fire.
Q: Can I modify this appliance?
A: No, it is not recommended to modify this appliance as it may
affect its safety and functionality.
Installation Manual
Installation and Appliance Setup
CAUTION! Risk of Fire! DO NOT store instruction manuals inside fireplace
cavity. High temperatures could cause a fire.
INSTALLER: Leave this manual with the appliance, not inside the appliance.
CONSUMER: Retain this manual for future reference. Do not store inside the
appliance.
NOTICE: DO NOT discard this manual!
Models:
6KX-AU
Ref No GMK10810 AS/NZS 5263.1.8
WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly
could result in serious injury, death, or property damage.
· DO NOT store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
· What to do if you smell gas
– DO NOT try to light any appliance.
– DO NOT touch any electrical switch. DO NOT use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
– If you cannot reach your gas supplier, call the fire department.
· Installation and service must be performed by a qualified installer, service
agency, or the gas supplier.
DANGER
NOTE: NOT INTENDED FOR FIREPLACE INSERT.
Decorative barrier front must be ordered separately at time of appliance
purchase. See Section 3.B.
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
NEVER ALLOW CHILDREN TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is
provided with this appliance and shall be installed for the protection of
children and other at-risk individuals.
DO NOT PLACE ARTICLES ON OR AGAINST THIS APPLIANCE. DO NOT USE OR STORE
FLAMMABLE MATERIALS NEAR THIS APPLIANCE. DO NOT SPRAY AEROSOLS IN THE VICINITY
OF THIS APPLIANCE WHILE IT IS IN OPERATION. DO NOT MODIFY THIS APPLIANCE.
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 1
Safety Alert Key:
· DANGER! Indicates a hazardous situation which, if not avoided will result in
death or serious injury. · WARNING! Indicates a hazardous situation which, if
not avoided could result in death or serious injury. · CAUTION! Indicates a
hazardous situation which, if not avoided, could result in minor or moderate
injury. · NOTICE: Used to address practices not related to personal injury.
Note: The term “recommend” or “recommended” does not indicate a requirement.
It is a best practice suggested by Hearth & Home Technologies®.
Table of Contents
Installation Standard Work Checklist. . . . . . . . . . . . . . . . . . . . 3
1 Product Specific and Important Safety Information A. Appliance Certification
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 B. Glass
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
C. Gas Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . 4
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . .
. . 5 E. Non-Combustible Materials Specification. . . . . . . . . . . . . . 5
F. Combustible Materials Specification . . . . . . . . . . . . . . . . . 5 G.
Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 5
2 Getting Started A. Design and Installation Considerations . . . . . . . . .
. . . . . . 6 B. Good Faith Wall Surface/TV Guidelines . . . . . . . . . . . .
. . 6 C. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . .
. . 9 D. Inspect Appliance and Components. . . . . . . . . . . . . . . . . . 9
3 Framing and Clearances A. Appliance Weights and Dimensions. . . . . . . . .
. . . . . . . . 10 B. Decorative Barrier Front Dimension Diagrams. . . . . . .
. . 11 C. Appliance Location and Clearances to Combustibles . . . 15 D.
Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 22 E.
Floor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 23
4 Termination Location and Vent Information A. Approved Pipe . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 24 B. Vent Termination Minimum
Clearances . . . . . . . . . . . . . . 24 C. Chimney Diagram. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 26 D. Use of Elbows . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 27 E. Vent Diagrams . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 F. Power Vent
Configurations . . . . . . . . . . . . . . . . . . . . . . . . 41
5 Vent Clearances and Framing A. Pipe Clearances to Combustibles . . . . . . .
. . . . . . . . . . . 42 B. Wall Penetration Framing/Firestops . . . . . . . .
. . . . . . . . . 43 C. Ceiling Firestop/Floor Penetration Framing . . . . . .
. . . . . 44 D. Install Attic Insulation Shield. . . . . . . . . . . . . . . .
. . . . . . . 44
6 Appliance Preparation A. Vent Collar Preparation . . . . . . . . . . . . . .
. . . . . . . . . . . . 45 B. Prepare For Heat Management . . . . . . . . . .
. . . . . . . . . . 47 C. Securing and Leveling the Appliance . . . . . . . .
. . . . . . . 48 D. Non-Combustible Material (Factory-Installed). . . . . . .
. 48
7 Venting A. Assemble Vent Sections. . . . . . . . . . . . . . . . . . . . . .
. . . . 49 B. Assemble Slip Sections . . . . . . . . . . . . . . . . . . . . .
. . . . . 50 C. Secure the Vent Sections . . . . . . . . . . . . . . . . . . .
. . . . . . 51 D. Disassemble Vent Sections . . . . . . . . . . . . . . . . .
. . . . . . 51 E. Vertical Termination Requirements. . . . . . . . . . . . . .
. . . . 52 F. Horizontal Termination Requirements . . . . . . . . . . . . . .
. 53
8 Electrical Information A. General Information . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 54 B. Wiring Requirements . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 55 C. Service for Fan . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 56
9 Gas Information A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 57 B. Gas Pressure . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 57 C. Gas Service Access . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 57 D. Gas Connection . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 57 E. High Altitude Installations . .
. . . . . . . . . . . . . . . . . . . . . . . 58 F. Air Shutter Setting . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 58 G. Service/Replace
Appliance Gas Valve . . . . . . . . . . . . . . . 59
10 Finishing A. Facing Material. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 60 B. Installing a Television . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 61 C. Mantel and Wall Projections. . . . . . . . . .
. . . . . . . . . . . . . 61 D. Hearth Extension . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 64 E. Decorative Barrier Front Dimensions for
Finishing. . . . . . 64
11 Appliance Setup A. Remove the Shipping Materials . . . . . . . . . . . . .
. . . . . . 68 B. Clean the Appliance . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 68 C. Install the Black Glass Refractory . . . . . . . . . .
. . . . . . . . 68 D. Install the Burner Overlay. . . . . . . . . . . . . . .
. . . . . . . . . . 72 E. Illuminated Embers. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 73 F. Install Base Refractory and Burner
Media/Embers . . . . . 73 G. Install the Log Assembly. . . . . . . . . . . . .
. . . . . . . . . . . . . 74 H. Fixed Glass Assembly Removal and Replacement .
. . . . 77 I. Install Decorative Barrier Front . . . . . . . . . . . . . . . .
. . . . 77
12 Reference Materials A. Vent Components Diagrams . . . . . . . . . . . . . .
. . . . . . . . 78 B. Accessories . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 83
= Contains updated information.
2
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Installation Standard Work Checklist
ATTENTION INSTALLER:
Follow this Standard Work Checklist
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this
installation manual.
Customer: Lot/Address:
Date Installed: Location of Fireplace: Installer:
Model (circle one): 6KX-AU
Dealer/Distributor Phone # Serial #:
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions could lead to a fire or explosion. Install ONLY components and accessories approved by Hearth & Home Technologies. Unapproved components and accessories could cause fireplace to overheat.
Appliance Install
Verified that the chase is insulated and sealed. (Pg. 22) Verified clearances
to combustibles. (Pg. 15) Fireplace is leveled and secured. (Pg. 48)
YES
IF NO, WHY?
Venting/Chimney Section 7 (Pg 49-53)
Venting configuration complies to vent diagrams. Venting installed, locked and
secured in place with proper clearance.
(May need to order separately.)
Firestops installed.
No insulation or foam materials in contact with venting or between
ceiling/wall shield firestops. Attic insulation shield installed.
Exterior wall/Roof flashing installed and sealed. Terminations installed and
sealed.
Electrical Section 8 (Pg 53-56) Unswitched power (220-240 VAC) provided to the appliance. Switch wires properly installed.
Gas Section 9 (Pg 57-59)
Proper appliance for fuel type. Was a conversion performed?
Leak check performed and inlet pressure verified. Verified proper air shutter
setting for installation type.
Finishing Section 10 (Pg 60-67) Combustible materials not installed in non-
combustible areas. Verified all clearances meet installation manual
requirements. Mantels and wall projections comply with installation manual
requirements.
. Appliance Setup Section 11 (Pg 68-77) All packaging and protective materials
removed (inside & outside of appliance). Refractories, logs, media and embers
installed correctly. Glass assembly installed and secured.
Accessories installed properly.
Decorative barrier front properly installed.
(May need to order separately.) Manual bag and all of its contents are removed
from inside/under
the appliance and given to party responsible for use and operation. Started
appliance and verified no gas leaks exist.
Hearth & Home Technologies recommends the following: · Photographing the installation and copying this checklist for your file. · That this checklist remain visible at all times on the appliance until the installation is complete.
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective action needed
Comments Communicated to party responsible ____ by __on ___
= Contains updated information.
(Builder / Gen. Contractor/) (Installer)
(Date)
2589-982B 5/23
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 3
1 Product Specific and Important Safety Information
A. Appliance Certification
MODELS: 6KX-AU LABORATORY: IAPMO OCEANA TYPE: Gas appliances Decorative effect
gas appliances STANDARD: AS/NZS 5263.1.8
This appliance must be installed in accordance with the AS/NZS 5601.1 rules in
force. PRIMARILY A DECORATIVE AND A NOT HEATING APPLIANCE.
C. Gas Pressure Requirements
Pressure requirements for 6KX-AU fireplaces are shown in table below.
Two taps are provided on the gas control for a test gauge connection to
measure the inlet and outlet pressures.
The fireplace and its individual shut-off valve must be disconnected from the
gas supply piping system during any pressure testing of the system at test
pressures in excess of 3.4 kPa.
If the fireplace must be isolated from the gas supply piping system by closing
an individual shut-off valve, it must be of the handle-less type.
B. Glass Specifications
This appliance is equipped with ceramic glass with an anti-reflective coating.
Replace glass only with ceramic glass. Please contact your dealer for
replacement glass.
NOTE: An inline fuel pressure regulator is recommended to limit NG inlet pressure to 2.49 kPa, and LP/ ULPG inlet pressure to 3.25 kPa, to ensure optimum product performance. The inline fuel pressure regulator may be needed if any of the following symptoms exist: pilot jetting, a highly visible pilot flame, flame variation, etc. The inline pressure regulator should be installed in the gas line upstream of the appliance gas valve either at the appliance or in the utility room. Final main and manifold gas pressure must be tested with inline pressure regulator installed.
Inlet Gas Pressure * Outlet (Manifold) Gas Pressure Nonimal Gas Consumption Burner Injector Pilot Injector
Natural Gas 1.13 – 3.40 kPa
.78 kPa 38 MJ/h #31 DMS (3.050 mm) Ø .023 (.584 mm)
Propane 2.75 – 3.40 kPa
2.44 kPa 38 MJ/h #49 DMS (1.854 mm) Ø .014 (.356 mm)
ULPG 2.75 – 3.40 kPa
2.43 kPa 28 MJ/h #53 DMS (1.511 mm) Ø .010 (.254 mm)
Gas types only through field conversions.
- The allowable Outlet (Manifold) Gas Pressure ranges are: Natural Gas .78 – .95 kPa (.78 kPa nominal) and Propane, ULPG 2.37 – 2.61 kPa (2.44 kPa nominal). Certification testing setpoint values are shown.
4
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not
apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 ft. (610 m) elevation: Reduce input rate 4% for
each 1000 ft. (305 m) above 2000 ft. (610 m).
E. Non-Combustible Materials Specification
Material which will not ignite and burn. Such materials are those consisting
entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or
any combination thereof. Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at
750 ºC (1382 °F) shall be considered non-combustible materials.
F. Combustible Materials Specification
Materials made of or surfaced with wood, compressed paper, plant fibers,
plastics, or other material that can ignite and burn, whether flame proofed or
not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
All electrical safety testing has been done following the EN 60335-2-102
standard. Local codes apply.
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 5
2 Getting Started
A. Design and Installation Considerations
WARNING! Risk of Fire or Explosion! Read all instructions before starting the
installation.
Direct vent gas appliances are designed to operate with all combustion air
siphoned from outside of the building and all exhaust gases expelled to the
outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and
regulations. Consult insurance carrier, local building inspector, fire
officials or authorities having jurisdiction over restrictions, installation
inspection and permits.
Before installing, determine the following:
· Where the appliance is to be installed.
· The vent system configuration to be used.
· Gas supply piping requirements and space for access. See Section 9 Gas
Information.
· Provisions for optional heat management system. If Passive Heat will be
installed, consider location of discharge opening in relation to venting and
other construction materials. Refer to the installation instructions included
with the Passive Heat kit for details and the appropriate sections in this
manual in terms of clearances and framing (Section 3), and finishing and
mantels (Section 10).
· Electrical wiring requirements.
· Framing and finishing details.
· Whether optional accessories–devices such as a fan, wall switch, or remote
control–are desired. See Section 12.B for approved accessories.
Installation and service of this appliance should be performed by qualified
personnel. Hearth & Home Technologies recommends HHT Factory Trained or
certified professionals.
B. Good Faith Wall Surface/TV Guidelines
NOTICE: Surface temperatures listed above are taken with a temperature
measuring probe as prescribed by the test standard used for appliance
certification. Temperatures on walls or mantels taken with an infrared
thermometer may yield increased temperatures of up to 30 °F (17 °C) or more
depending on the thermometer settings and material characteristics being
measured. Use appropriate finishing materials that are able to withstand these
conditions. For additional finishing guidelines, see Section 10. Surface
temperatures will vary due to factors such as ceiling height, room size and
installation configuration.
TO CEILING
FIREPLACE OPENING
140 °F (60 °C)
140°F (60 °C)
145 °F
(63 °C)
30 in.
(762 mm)
150 °F (66 °C)
24 in. (610 mm)
18 in.
165 °F (457 mm) (74 °C) 12 in.
(305 mm)
6 in. (152 mm)
MEASUREMENTS FROM TOP EDGE OF THE OPENING
APPLIANCE FRONT
Figure 2.1 Good Faith Wall Surface Temperatures Above Appliance
Optional Passive Heat Kit Installed
TO CEILING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualified service technician, service agency or your dealer.
FIREPLACE OPENING
90 °F (32 °C)
90°F (32 °C)
95 °F (35 °C)
30 in.
(762 mm)
100 °F (38 °C)
24 in. (610 mm)
18 in. 115 °F (457 mm) (13 °C) 12 in.
(305 mm)
6 in. (152 mm)
MEASUREMENTS FROM TOP EDGE OF THE OPENING
APPLIANCE FRONT
Figure 2.3 Good Faith Wall Surface Temperatures Above Appliance With Passive Heat Kit Installed
6
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
TV Wall Bracket
Good Faith Guidelines for TV Installaons Above Appliance (Passive Heat Not Installed)
TV on the wall
TV recessed into the wall
TV
Item Minimum Dimensions
A 2-1/2 in. (64 mm)
B
2 in. (51 mm) minimum to 3 in. (76 mm) maximum
C 20 in. (508 mm)
Wall Brkt + TV Thickness + 2-1/2 in.
A
D (64 mm)
B
Mantel
D
C
A B
C
Appliance
Appliance Opening
Appliance Opening
Appliance
Appliance Opening
Notes: 1. 2.
3. 4. 5.
These are good faith recommended clearances only and not a guarantee of
compliance with all TV manufacturers’ maximum allowable operang temperatures.
Since every home has unique air flow characteriscs and maximum allowable
operang temperatures can vary from manufacturer to manufacturer and from model
to model, actual TV temperatures should be validated at the me of each
installaon. TVs should not be used in situaons where the actual TV temperature
exceeds the manufacturers’ maximum allowable operang temperatures idenfied in
the TV’s technical specificaons. Contact the TV’s manufacturer directly if you
cannot locate this informaon or have quesons regarding the informaon. Mantel
height and depth must conform to mantel requirements specified in the
appliance installaon
manual.
“C” dimension taken from the top of the hood or appliance opening to the boom
of the TV.
Suggesons on how to further reduce TV temperatures: a. Increase “A” dimension.
b. Increase “C” dimension, however, increasing “B” dimension beyond maximum
recommended typically results in higher temperatures.
Figure 2.4 Good Faith TV Guidelines Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 7
Good Faith Guidelines for TV Installations Above a Fireplace with Passive Heat Option and a Factory-Installed Fan
NOTICE: A mantel is required when the Passive Heat option is installed. The combination of heat from the Passive Heat and the factory-installed fan could reduce the life expectancy of the TV if a mantel is not present.
TV mounted flat
TV mounted at angle
PASSIVE HEAT DISCHARGE OPENING
TV Wall Bracket Required Mantel
PASSIVE HEAT DISCHARGE OPENING
E
WIRE MESH*
E
ITEM MINIMUM DIMENSIONS
A 3 in. (76 mm)
B
5-1/4 in. (133 mm) min. 6-1/4 in. (159 mm) max.
C 12 in. (305 mm)
A
D
Wall Bracket Depth + TV Thickness + 3 in. (76 mm)
E 4 in. (102 mm)
B DC
Required Mantel
B D
A C
A pplia nce
Appliance Opening
A pplia nce
Appliance Opening
- Mesh screen required for front discharge or open top discharge passive heat installations with discharge opening of three inches or greater.
NOTE: The TV installation requirements are the same regardless of whether the Passive Heat kit is installed with a top discharge, side discharge or open top discharge.
“A” Dimension taken from the front of TV to front of the mantel. “B” Dimension taken from the top of mantel to bottom of TV. “C” Dimension taken from the top of the appliance opening to the bottom of the TV. “D” Minimum mantel depth = Wall bracket thickness + TV thickness + 2-1/2 in. (64 mm). “E” Dimension taken from the top of TV to bottom of discharge opening.
Notes: 1. These are good faith recommended clearances only and not a guarantee of compliance with all TV manufacturers’ maximum
allowable operang temperatures. 2. Since every home has unique air flow characteriscs and maximum allowable operang temperatures can vary from manufacturer to
to manufacturer and from model to model, actual TV temperatures should be validated at the me of each installaon. TVs should not be used in situaons where the actual TV temperature exceeds the manufacturers’ maximum allowable operang temperatures idenfied in the TV’s technical specificaons. Contact the TV’s manufacturer directly if you cannot locate this informaon or have quesons regarding the informaon. 3. Mantel height and depth must conform to mantel requirements specified in the appliance installaon manual.
4. Suggesons on how to further reduce TV temperatures: a. Increase “A” dimension. b. Increase “C” dimension, however, increasing “B” dimension beyond maximum recommended typically results in higher temperatures.
Figure 2.5 Good Faith Guidelines – Passive Heat Kit Installed
8
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
C. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Hand Tools
Tape measure
Level
Framing material
Manometer
Framing square
Voltmeter
Electric drill and bits (1/4 in. (6mm)
Plumb line Wrenches 1/4 in. nut driver
Safety glasses/Gloves Reciprocating saw Elongated pressure taps
Hammer
Flathead screwdriver
Tin Snips
Non-corrosive leak check solution
1/2 – 3/4 in. (13 -19 mm) length, #6 or #8 Self-drilling screws
Stove cement / aluminum foil tape
Caulking material (300 ºF (149 ºC) minimum continuous exposure rating)
D. Inspect Appliance and Components
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation.
DO NOT install damaged, incomplete or substitute components. Keep appliance
dry. WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this
appliance if any part has been under water. Call a qualified service
technician to inspect the appliance and to replace any part of the control
system and/or gas control which has been under water. · Carefully remove the
appliance and components from
the packaging. · The vent system components and decorative barrier
fronts may be shipped in separate packages. · If packaged separately, the log
set must be installed. · Report to your dealer any parts damaged in shipment.
Hearth & Home Technologies disclaims any responsibility for, and the warranty
will be voided by, the following actions: · Installation and use of any
damaged appliance or vent
system component. · Modification of the appliance or vent system. ·
Installation other than as instructed by Hearth & Home
Technologies. · Improper positioning of the logs/media (as applicable) or
the glass assembly. · Installation and/or use of any component part not
approved
by Hearth & Home Technologies.
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 9
3 Framing and Clearances
A. Appliance Weights and Dimensions
Dimensions are actual appliance dimensions. Use for reference only. For
framing dimensions and clearances refer to Section 5.
Appliance Weight Table
Model 6KX-AU
Pounds 198
Kilograms 90
HEAT ZONE® –
240V ACCESS ØU
P Q
T
V
W S
R
J
O
G
D
E
F
M
L
K(CL) I
C
N X B A
Y H
Location A B C D E F G H
Inches 41
38-5-16 34-5/8 24-3/4 34-1/4 33-1/2 40-7/8
16
Millimeters 1041 973 879 629 870 851 1038 406
Location I J K L M N O P
Inches 2-1/8 8-1/2 26-7/8 41-3/4 14-1/4 8-1/2
39-13/16 28-3/8
Millimeters 54 216 683
1060 362 216 1011 721
Location Q R S T U V W X Y
Inches 14-3-/16 11-3/16 21-7/16
8-1/2 6 1/2
6-3/8 1-1/4 6-3/8
Millimeters 360 284 545 216 152 13 162 32 162
Figure 3.1 Appliance Dimensions
10
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
B. Decorative Barrier Front Dimension Diagrams
LOFT DECORATIVE BARRIER FRONTS
IMPORTANT! This fireplace requires an installed decorative barrier front to
prevent direct contact with the hot viewing glass. DO NOT operate the
fireplace with the barrier removed. Decorative barrier front must be ordered
at time of fireplace purchase. If decorative barrier front is not present,
contact dealer. WARNING! Risk of Overheating! DO NOT install combustible or
non-combustible flooring or hearth material above top of bottom surround. Gap
between bottom of decorative front and top of bottom surround must be
maintained for proper air flow. Note: See Section 10 for hearth, mantel and
finishing requirements, including complete information for combustible and
non-combustible mantels.
BOTTOM OF MANTEL BOTTOM OF MANTEL
H I
TOP OF APPLIANCE OPENING
A
B
Barrier Mesh: Integral to Decorative Barrier Front
G F
J
C
ED
6 LOFT-6 6 LOFT-6
A
B
C
D
in. 34-1/4
26
39-1/8
1-1/2
mm
870
660
994
38
E
F
G
4
32-7/16 33-15/16
101
824
862
H Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth (No Passive Heat)
I Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth with Passive Heat Installed
in.
19
6
mm
483
152
J
1-1/8 29
Figure 3.2 Decorative Barrier Front Dimensions – LOFT
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 11
FORGE DECORATIVE BARRIER FRONTS
IMPORTANT! This fireplace requires an installed decorative barrier front to
prevent direct contact with the hot viewing glass. DO NOT operate the
fireplace with the barrier removed. Decorative barrier front must be ordered
at time of fireplace purchase. If decorative barrier front is not present,
contact dealer. WARNING! Risk of Overheating! DO NOT install combustible or
non-combustible flooring or hearth material above top of bottom surround. Gap
between bottom of decorative front and top of bottom surround must be
maintained for proper air flow. Note: See Section 10 for hearth, mantel and
finishing requirements, including complete information for combustible and
non-combustible mantels.
BOTTOM OF MANTEL BOTTOM OF MANTEL
H I
TOP OF APPLIANCE OPENING
A B
Barrier Mesh: Integral to Decorative Barrier Front
G F
6 FORGE-6 6 FORGE-6
J E D
C
A
B
C
D
E
F
G
in. 33-9/16 26-5/16 39-5/16
1-5/8
3-5/8
32-7/16
34
mm
853
668
999
41
92
824
864
H Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth (No Passive Heat)
I Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth with Passive Heat Installed
in.
19
6
mm
483
152
J
1-1/8 29
Figure 3.3 Decorative Barrier Front Dimensions – FORGE
12
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
CHAPEL DECORATIVE BARRIER FRONTS
IMPORTANT! This fireplace requires an installed decorative barrier front to
prevent direct contact with the hot viewing glass. DO NOT operate the
fireplace with the barrier removed. Decorative barrier front must be ordered
at time of fireplace purchase. If decorative barrier front is not present,
contact dealer. WARNING! Risk of Overheating! DO NOT install combustible or
non-combustible flooring or hearth material above top of bottom surround. Gap
between bottom of decorative front and top of bottom surround must be
maintained for proper air flow. Note: See Section 10 for hearth, mantel and
finishing requirements, including complete information for combustible and
non-combustible mantels.
BOTTOM OF MANTEL BOTTOM OF MANTEL
H I
TOP OF APPLIANCE OPENING
B
G
A
F
Barrier Mesh: Integral to Decorative Barrier Front
J E
C
D
A
B
C
in. 35-13/16 23-7/8 39-5/16
6 CHAPEL-6
mm
910
606
999
D 1-1/2
38
E 3-1/4
83
F 32-7/16
824
G 33-15/16
862
6 CHAPEL-6
H Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth (No Passive Heat)
I Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth with Passive Heat Installed
in.
19
6
mm
483
152
J
1-1/8 29
Figure 3.4 Decorative Barrier Front Dimensions – CHAPEL
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 13
FOLIO DECORATIVE BARRIER FRONTS
IMPORTANT! This fireplace requires an installed decorative barrier front to
prevent direct contact with the hot viewing glass. DO NOT operate the
fireplace with the barrier removed. Decorative barrier front must be ordered
at time of fireplace purchase. If decorative barrier front is not present,
contact dealer. WARNING! Risk of Overheating! DO NOT install combustible or
non-combustible flooring or hearth material above top of bottom surround. Gap
between bottom of decorative front and top of bottom surround must be
maintained for proper air flow. Note: See Section 10 for hearth, mantel and
finishing requirements, including complete information for combustible and
non-combustible mantels.
BOTTOM OF MANTEL BOTTOM OF MANTEL
H I
TOP OF APPLIANCE OPENING
Barrier Mesh: Integral to Decorative Barrier Front
J
B A
F G
E D
C
6
FOLIO-6
6 FOLIO-6
A
B
C
D
E
F
in.
34-11/16 28-11/16
38
1-1/8
2-3/8
32
mm
881
729
965
29
60
813
H Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth (No Passive Heat)
I Minimum Combustible Mantel Height
at 12 In. (305 mm) Mantel Depth with Passive Heat Installed
in.
19
6
mm
483
152
Figure 3.5 Decorative Barrier Front Dimensions – FOLIO
G 33-3/16
843
J
1-1/8 29
14
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
C. Appliance Location and Clearances to Combustibles
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings
and for service access. Due to high temperatures, the appliance should be
located out of traffic and away from furniture and draperies. When selecting a
location for the appliance it is important to consider the required clearances
to walls and allow sufficient clearance for heat management systems venting.
Refer to Figure 3.6 and Figure 3.7 for Heat-Zone-240V.
Refer to Figures 3.11-3.13 for information regarding framing when the Passive
Heat Kit is installed. Install the Passive Heat Kit per the instructions
provided with the kit.
NOTICE: Illustrations reflect typical installations and are FOR DESIGN
PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual
installation may vary due to individual design preference.
NOTICE: Allow 18 inches minimum clearance on top of appliance for venting of
heat management system. 18 IN. MIN.
Figure 3.6 Clearance for Heat Management System HEAT-ZONE®-240-V
KNOCKOUT LOCATIONS
Figure 3.7 Heat Management Knockout Locations
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 15
A G
I A
B C
TOP VENT
ONE 900 ELBOW
B
ALCOVE INSTALLATION
E
J*
Refer to Section 10 for mantel and wall projection information.
Consider the mantel or cabinet system to be installed and comply with the necessary
B
requirements for elevated hearth. Refer to
instructions included with cabinet system.
REAR VENT, HORIZONTAL TERMINATION,
TWO ELBOWS
REAR VENT, ONE ELBOW
D
BK
REAR VENT, NO ELBOWS
B
KB
D
F
D H
D
J* = When exterior wall is constructed from 2 x 4 material, a termination cap with effective length equal to the DVP-TRAP1 is required. See Figure 3.10.
ABC
D
E
FG HI
J*
K
IN. 51 42 72 56-5/8 See Section 10 22 17-3/4 8 1/2 For terminations 80-1/8
6KX-AU mm 1295 1067 1829 1438
Mantel Projections
559 451
through a 2 x 4 wall,
203 13
see Figure 3.10.
2035
Figure 3.8 Appliance Locations
16
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Top Vent DVP-TRAP1 Exception
For installations that are top vented and horizontally terminated with a 90
degree elbow directly off the appliance and minimum vent run, a termination
cap with effective length equal to the DVP-TRAP1 is REQUIRED. Interior and
exterior wall sheathing 1/2 inch thick and 2 X 4 exterior wall studs are also
assumed for this scenario.
4-1/2 IN. 114 mm
EXTERIOR SHEATHING 1/2 IN. (13 mm) THICK
2 X 4 (51 x 102 mm)
(3-1/2 IN.) (89 mm)
1/2 IN. (13 mm) MIN. CLEARANCE
BACK OF APPLIANCE TO WALL SHEATHING
INTERIOR SHEATHING 1/2 IN. (13 mm) THICK
J* = 5 (127 mm) IN. TO FRONT OF DVP-TRAP1 TERMINATION CAP
DVP90ST
5 IN. (127 mm)
Figure 3.9 DVP-TRAP1 Exception (2 x 4 (51 x 102 mm) Construction)
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 17
MEASURE E FROM TOP OF
A
APPLIANCE OPENING OR
FROM TOP OF HOOD
B
C D
F
G
J
I
EK H
Note: E and K will change if passive heat is installed.
6KX-AU
Inches Millimeters
A
Rough Opening (Vent Pipe)
10
254
- MINIMUM FRAMING DIMENSIONS
B
C**
D
E
F
Rough Opening (Height)
Rough Opening (Depth)
Rough Opening (Width)
Clearance to Room Ceiling
Combustible Floor
40-1/8 22
42
32
0
1019 559 1067
813
0
G***
H
Minimum Hearth Behind
Required
Appliance
0
1/2
0
13
6KX-AU
- MINIMUM FRAMING DIMENSIONS
I
J
K
Sides of Appliance
Front of Appliance
Clearance to Room Ceiling
Inches
1/2
36 83-1/2
Millimeters
13
914 2121
- Adjust framing dimensions for interior chase sheathing (such as sheetrock) C** Add 12 in. (305 mm) for rear venting with one 90 degree elbow. G*** For installations with vinyl flooring, see Section 3.E.
Figure 3.10 Clearances to Combustibles
18
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Framing Dimensions- Passive Heat Front Discharge (PH-MR) Front Discharge: Air conveyed into the room through one front discharge slot.
C
CHASE DETAIL
A B
1-1/2 IN. (38 mm) (2 X 4 (51 x 102 mm) FRAMING)
0-3 IN. (0-76 mm)
ROOM CEILING
2 IN. (51 mm)MIN.
CHASE CEILING REQUIRED
WITHIN 3 IN. (76 mm) OF TOP
1/2 IN. X 1/2 IN.
OF OPENING
(13 mm X 13 mm)
WIRE MESH**
WIRE MESH**
TV
= PASSIVE HEAT
DISCHARGE OPENING
= CHASE CEILING ZONE
WARNING! Risk of Fire! Wire mesh required on bottom of discharge opening (Dimension A) when finished discharge opening is greater than 3 in. (76 mm). Secure mesh to top of framing.
E
D
6KX-AU
FRONT DISCHARGE MINIMUM FRAMING DIMENSIONS
A
TRIM KIT*
NO TRIM
B
C
INSTALLED
KIT**
Required Height of Discharge Opening
Height of Discharge Opening
Clearance to Top of
Discharge Opening
Width of Discharge Opening
Inches millimeters
3-1/2 89
2
41
36-1/2
51
1041
927
D
Clearance to Top of Discharge
Opening From Bottom of Appliance
78
1981
E
Clearance to Bottom of Discharge
Opening from Bottom of Appliance
76 1930
- Measurement for Trim Kit = 3-1/2 in. (89 mm) + Additional Finishing Material Thickness.
** Measurement without Trim Kit = 2 in. (51 mm) + Additional Finishing Material Thickness. If finished discharge opening height is greater than 3 in. (76 mm), wire mesh is required.
Figure 3.11 Passive Heat Front Discharge Framing Dimensions With and Without a Trim Kit Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 19
Framing Dimensions – Passive Heat Side Discharge (PH-MR)
Side Discharge: Air conveyed into the room through two discharge registers,
one on each side of appliance.
WARNING! Risk of Fire! DO NOT place combustible objects or combustible
materials in non-combustible zone. Appliance and combustible materials will
overheat.
CHASE DETAIL
1-1/2 IN. (38 mm) (2 X 4 (51 X 102 mm) FRAMING) CHASE CEILING ZONE
0-3 IN. (76 MM)
ROOM CEILING
CHASE CEILING REQUIRED WITHIN 3 IN.
OF TOP OF OPENING
B
DISCHARGE OPENING
= PASSIVE HEAT DISCHARGE OPENING
= CHASE CEILING ZONE
E
A
D
C
APPLIANCE MAY BE INSTALLED OFF OF FLOOR
6KX-AU
Inches
SIDE DISCHARGE FRAMING DIMENSIONS
A
B
C
D
Height of Width of Discharge Discharge Opening Opening
Minimum Clearance to Discharge Opening From Bottom of Appliance
Minimum Clearance to Ceiling from
Bottom of Appliance
12-1/4
8-3/4
68-1/4
83-1/2
E
Minimum Clearance to Combustible
Materials
18
millimeters 311
222
1734
2121
457
Figure 3.12 Passive Heat Side Discharge Framing Dimensions
20
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Framing Dimensions – Passive Heat Open Top Discharge (PH-MR) Open Top
Discharge: Both sides and the top are open allowing air to be conveyed into
the room.
WARNING! Risk of Fire! Mesh screen required on bottom of discharge opening
when discharge opening is greater than 3 in. (76 mm). Secure mesh to top of
framing.
C A
B
6KX-AU
OPEN TOP DISCHARGE MINIMUM FRAMING DIMENSIONS
A*
B
Height of Discharge Opening
Clearance to Discharge Opening
Inches
2
41
millimeters
51
1041
C Width of Discharge Opening 36-1/2
927
- Mesh screen required for front discharge or open top discharge passive heat installations with discharge
opening of 3 inches or greater.
Figure 3.13 Passive Heat Minimum Framing Dimensions Open Top Discharge Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 21
D. Constructing the Appliance Chase
NOTICE: Install appliance on hard metal or wood surfaces extending full width
and depth. DO NOT install directly on carpeting, vinyl, or any combustible
material other than wood. WARNING! Risk of Fire! Maintain specified air space
clearances to appliance and vent pipe: · Insulation and other materials must
be secured to prevent
accidental contact. · The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and making contact with
fireplace or chimney. · Failure to maintain airspace may cause overheating and
a fire.
A chase is a vertical box-like structure built to enclose the gas appliance
and/or its vent system. In cooler climates the vent should be enclosed inside
the chase.
NOTICE: Treatment of ceiling firestops and wall shield firestops and
construction of the chase may vary with the type of building. These
instructions are not substitutes for the requirements of local building codes.
Therefore, you MUST check local building codes to determine the requirements
to these steps.
NOTICE: Where required by code, install only sprinkler heads with a sprinkler
activation temperature classified as Extra High. · Sprinklers inside of chase:
Keep sprinkler head away
from vent and chimney. · Heat Management applications: Maintain 36 inches
(914 mm) of clearance to openings from which heat is discharged such as
convection slots, passive heat registers, heat zone registers, etc. Refer to
Section 6.B for Heat Management options allowed for this appliance.
Chases should be constructed and insulated in the same manner as the thermal
envelope of the home based on the code requirements for that climate zone to
prevent air leakage and draft problems. The chase is an extension of the
building thermal envelope.
To further prevent drafts and air leakage, the wall shield and ceiling
firestops should be sealed with caulk with a minimum of 300 ºF (149 ºC)
continuous exposure rating to seal gaps. Gas line holes and other openings
should be sealed with caulk with a minimum of 300 ºF (149 ºC) continuous
exposure rating or stuffed with unfaced insulation. If the appliance is being
installed on a cement surface, a layer of plywood may be placed underneath to
prevent conducting cold up into the room.
Minimum height requirements for an exterior chase on a topvented appliance are
shown in Figure 3.14. Reference Figure 4.5 for additional clearances.
A B*
3 IN. (76 mm) MIN.
C
- NOTE: If overhang is less than 2 inches (51 mm), clearance from top of termination cap to bottom of overhang may be 0 inches.
A – Measured from back of vent cap to end of overhang B – Measured from bottom of overhang to top of termination cap C – Measured from bottom of appliance to combustible surface Vinyl Siding Shield (TRAP-VSS) Information TRAP-VSS required if overhang (A) is greater than 3 inches (76 mm) but less than 5 inches and B dimension is less than 18 inches (457 mm). TRAP-VSS recommended if either of the below is true: – Overhang (A) is less than 5 inches (127 mm) (to combat water
infiltration)
Figure 3.14 Exterior Chase – Minimum Height Requirements
22
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
E. Floor Protection
Vinyl Flooring
Vinyl flooring is sensitive to heat. To avoid damage to the vinyl flooring, a
12 in (305 mm) minimum x 12 in (305 mm) minimum hearth is recommended when
using vinyl flooring up to the wall. See Figure 3.15. If no hearth is used, it
is recommended to provide a minimum of 30 In (762 mm) inches of clearance in
front of the appliance to the vinyl flooring OR the bottom of the appliance
should be raised a minimum of 24 in (610 mm) off of the floor to allow the
vinyl flooring to be installed up to the wall.
NOTICE: Clearances that do not meet the minimum guidelines could result in
damage or buckling to the vinyl flooring and is done at the installer’s risk.
Hearth and Home Technologies does not recommend adhesive based vinyl flooring
products due to thermal expansion during operation. Floating style flooring
can be used, but will reach temperatures up to 110 °F (43 °C) (based on
ambient temperature of 70 °F (21 °C). Consult the manufacturer’s flooring
specifications to ensure compatibility.
FRONT VIEW DETAIL A
FLOORING OR HEARTH MATERIAL NOT ALLOWED ABOVE TOP OF BOTTOM SURROUND
AIR FLOW
Flooring & Hearth Material
FLOORING OR HEARTH MATERIAL ALLOWED UP TO TOP OF BOTTOM SURROUND See Detail A
Front View Figure 3.16 Flooring & Hearth Material Allowed
12 IN.
APPLIANCE VINYL
12 IN. (305 mm)
(305 mm) MIN. WIDTH MIN.
MIN.
Figure 3.15 Vinyl Flooring Recommendations
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 23
4 Termination Location and Vent Information
A. Approved Pipe
WARNING! Risk of Fire, Delayed Ignition or Asphyxiation. This appliance
requires a separate vent. DO NOT vent to a pipe serving any other appliance.
This appliance is only approved for use with Hearth & Home Technologies DVP
venting systems. Refer to Section 12.A for vent component information and
dimensions. Only use listed decorative termination caps/shrouds with Hearth &
Home Technologies approved venting systems.
DO NOT mix pipe, fittings or joining methods from different manufacturers.
The pipe is tested to be run inside an enclosed wall. There is no requirement
for inspection openings at each joint within the wall.
B. Vent Termination Minimum Clearances
WARNING
Fire Risk. Maintain vent clearance to combustibles as specified. · DO NOT pack
air space with insulation or other
materials. Failure to keep insulation or other materials away from vent pipe
could cause overheating and fire.
HORIZONTAL OVERHANG
2 FT. (610 mm)
MIN.
GAS DIRECT VENT TERMINATION CAP
20 INCHES MIN. (508 mm)
LOWEST DISCHARGE
OPENING
VERTICAL WALL
12 X (305 mm)
ROOF PITCH IS X/ 12 (305 mm)
H (MIN.) – MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
Roof Pitch
H (Min.) Ft
Flat to 26.6°……………………………………………………500*
Over 26.6° to 30.3°………………………………………… 500*
Over 30.3° to 33.7°………………………………………….500*
Over 33.7° to 36.9°………………………………………….610*
Over 36.9° to 39.8°………………………………………….760*
Over 39.8° to 42.5° ………………………………………….990
Over 42.5° to 45.0°………………………………………..1220
Over 45.0° to 49.4°………………………………………..1520
Over 49.4° to 53.1°………………………………………..1830
Over 53.1° to 56.3° ……………………………………….2130
Over 56.3° to 59.0°………………………………………..2290
59.0° to 60.3°……………………………………………….2440
- H minimum may vary depending on regional snowfall. Refer to local codes.
Figure 4.1 Minimum Height From Roof to Lowest Discharge Opening
24
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
B. Vent Termination Minimum Clearances (continued)
A 6 in. (minimum) up to 20 in.
(152 mm / 508 mm) 20 in. (152 mm) and over
B 18 in. minimum
(457 mm)
0 in. minimum
Wood or Fuel Oil Termination Cap
B
C
A
*Gas Termination
Cap
OVERHANG WALL
- If two gas terminations are present, they may be level (B = 0 inches) provided A is a minimum of 6 inches (152 mm).
Figure 4.2 Staggered Termination Caps
CAUTION! Risk of Burns! Termination caps are HOT, consider proximity to doors, traffic areas or where people may pass or gather (sidewalk, deck, patio, etc.). Listed cap shields available. Contact your dealer. · Local codes or regulations may require different
clearances.
· Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
· Vinyl protection kits are suggested for use with vinyl siding. · Measure horizontal and vertical termination cap clearances
as noted in Figure 4.3 and 4.4.
F
C and F dimensions are defined in Figure 4.5.
Figure 4.4 Measure Horizontal and Vertical Termination Clearance to Trapezoid
Portion of Cap
H=Measure Horizontal Distances from H V=Measure Vertical Distances from V
Figure 4.3
V
V
C=L6EAINR. ANCE
H H H
V
V H
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 25
C. Chimney Diagram
Ref.
a
b
c d e f g h j k
n
Item
Minimum Clearance (mm) Natural Draft Fan Assisted
Below eaves, balconies or other projections
Appliances up to 50 MJ/h input
300
200
Appliances over to 50 MJ/h input
500
300
From the ground or above a balcony
Appliances 32 MJ/h and below
300
355
Appliances from 32 MJ/h to 53 MJ/h
300
410
Appliances 53 MJ/h and above
300
460
From a return wall or external corner
500
300
From a gas meter (M)
1000
1000
From an electricity meter or fuse box (P)
500
500
From a drain or soil pipe
150
75
Horizontally from any building structure (unless appliance approved for closer installation) or obstruction facing a terminal
500
500
From any other flue terminal, cowl, or combustion air intake
500
300
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a building, with the exception of sub-floor ventilation
Appliances up to 150 MJ/h input
500
300
All fan assisted appliances in the direction of discharge
–
1500
From a mechanical air inlet, including a spa fan
1500
1000
Vertically below an openable window, non-mechanical air inlet or any other opening into a building, with the exception of See table sub-floor ventilation
For space heaters up to 50 MJ/h input
150
150
For other appliances up to 50 MJ/h input
500
500
For appliances over 50 MJ/h input and up to 150 MJ/h
1000
1000
For appliances over 150 MJ/h input
1500
1500
NOTES:
1. All distances are measured vertically or horizontally along the wall to a
point in line with the nearest part of the terminal. 2. Prohibited area below
electricity meter or fuse box extends to ground level. 3. Flue terminal under
covered area:
a) The covered area or recess shall be open on at least two sides. b) Fan
assisted flue appliance shall have at least one side open and the terminal
shall be
within 500 mm of the opening and discharging in the direction of the opening.
4. Clearance from a flue terminal to a LP cylinder shall be a minimum of 1
meter.
MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES
Figure 4.5 Minimum Clearances for Termination
26
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects when calculating
the effects. Use the rise for the vertical aspect and the run for the
horizontal aspect. See Figure 4.6.
Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of
diagonal is equal to 8-1/2 inch (216 mm) horizontal run and 8-1/2 inch (216
mm) vertical run. A length of straight pipe is allowed between two 45º elbows.
See Figure 4.6.
Figure 4.7 shows the vertical and horizontal offsets for DVP or SLP elbows.
RISE
VERTICAL
EFLFEENCGTITVHE RUN
Y
X
Vent Type DVP
Inches 6-5/8
X Millimeters
168
Inches 16-1/2
Y Millimeters
419
X
HORIZONTAL
DVP Pipe
DVP4 DVP6 DVP12 DVP24 DVP36 DVP48 DVP6A DVP12A
Effective Length
Inches Millimeters
4
102
6
152
12
305
24
610
36
914
48
1219
3 to 6 76 to 152
3 to 12 76 to 305
Rise/Run
Inches
Millimeters
2-3/4
70
4-1/4
108
8-1/2
216
17
432
25-1/2
648
34
864
2-1/8-4-1/4 54-108
2-1/8-8-1/2 54-216
Figure 4.6
X
Vent Type DVP
Inches 16-1/4
X Millimeters 413
Figure 4.7 Vertical and Horizontal Offset for DVP and SLP Elbows
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 27
E. Vent Diagrams
General Rules:
· When penetrating a combustible wall, a wall shield firestop must be
installed.
· When penetrating a combustible ceiling, a ceiling firestop must be
installed.
· Horizontal runs of vent do not require vertical rise; horizontal runs may be
level.
· It is recommended that the horizontal termination cap have a 1/4 inch (6 mm)
downward slant to allow any moisture in cap to be released. See Figure 4.8.
If venting configuration differs from the vent diagrams on the following pages
(Figure 4.12-4.27), these rules also apply:
· SUBTRACT 3 ft (914 mm) from the total H measurement for each 90º elbow
installed horizontally.
· SUBTRACT 1-1/2 ft (457 mm) from the total H measurement for each 45º elbow
installed horizontally.
· A maximum of three 90º elbows (or six 45º elbows) may be used in any vent
configuration. Some elbows may be installed horizontally. See Figure 4.13.
· Elbows may be placed back to back anywhere in the system.
· Any 90º elbow may be replaced with two back to back
45º elbows.
· 2 x 45° elbow jog directly off the top of the fireplace is allowed but has
no V or H value and DOES NOT count towards total elbow count.
WARNING
Fire Risk. Explosion Risk. Do NOT pack insulation or other combustibles
between ceiling firestops. · ALWAYS maintain specified clearances around
venting and firestop systems. · Install wall shield and ceiling firestops as
speci-
fied. Failure to keep insulation or other material away from vent pipe may
cause fire.
WARNING
Fire Risk. · When using DVP-HRC-SS and DVP-HRC-ZC-
SS termination caps on top vented fireplaces, a 6 inch (152 mm) minimum
vertical vent section is required before installing first elbow.
1/4 in. max. (6 mm)
Figure 4.8
28
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Measuring Standards: Vertical and horizontal measurements listed in the vent
diagrams and clearances for termination were made using the following
standards: · Pipe measurements are shown using the effective length
of pipe. See Section 12.A for information on effective length of pipe
components. · Horizontal terminations are measured to the outside mounting
surface (flange of termination cap). See Figure 4.9. · Vertical terminations
are measured to top of last section of pipe. See Figure 4.10. · Horizontal
pipe installed level with no rise.
MEASURE TO SHADED SURFACE (OUTSIDE MOUNTING SURFACE) Figure 4.9 Measure to
Outside Mounting Surface
Figure 4.10 Measure to Top of Last Section of Pipe
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 29
Flue Components and Terminations
NOTE: DO NOT USE AN UNLINED MASONRY CHIMNEY AS THE FLUE FOR THIS APPLIANCE.
VERTICAL TERMINATION
HORIZONTAL TERMINATION
STORM COLLAR
ROOF FLASHING
HORIZONTAL PIPE SUPPORT
WALL FIRESTOP
90 DEGREE ELBOW
Flue system termination kits
DVP-SERIES
CEILING FIRESTOP
PIPE LENGTH WALL BRACKET
DVP-TVHW DVP-TRAP2
Figure 4.11 Flue Components and Terminations
30
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Top Vent – Horizontal Termination
One Elbow
Note: For corner installations: A 6 inch (152 mm) section of straight pipe may
need to be attached to the appliance before a 90º elbow, to allow the vent
pipe to clear the top standoffs.
6KX-AU (NG/LP)
V1 Minimum
.5 ft.
152
H1 Maximum
2 ft.
610 mm
1 ft.
305 mm
3 ft.
914 mm
2 ft.
610 mm
6 ft.
1.8 m
3 ft.
914 mm
11 ft.
3.4 m
4 ft.
1.2 m
16 ft.
4.9 m
5 ft.
1.5 m
20 ft.
6.1 m
V1 + H1 = 40 ft. (12.2 m) Maximum H1 = 20 ft. (6.1 m) Maximum
WARNING! Risk of Fire! Elbow heat shield required
when must
bVe 1
= 2 ft. or less. maintained. See
Clearances to Section 5.A.
combustibles
6KX-AU (ULPG)
V1 Minimum 1 ft. 305 mm
H1 Maximum
1 ft.
305 mm
2 ft. 610 mm
4 ft.
1.2 m
3 ft. 914 mm
6 ft.
1.8 m
4 ft.
1.2 m
8 ft.
2.4 m
5 ft.
1.5 m
10 ft.
3.0 m
V1 + H1 = 40 ft. (12.2 m) Maximum H1 = 10 ft. (3.0 m) Maximum
V1
H1
Figure 4.12 Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 31
Top Vent – Horizontal Termination – (continued)
Two Elbows
Note: For corner installations: A 6 in. (152 mm) section of straight pipe may need to be attached to the appliance before a 90º elbow, to allow the vent pipe to clear the top standoffs.
WARNING! Risk of Fire! Elbow heat shield required
when must
bVe1m=a2intfat.inoerdl.esSse.e
Clearances to Section 5.A.
combustibles
6KX-AU (NG/LP)
V1 Minimum .5 ft. 152 mm
1 ft. 305 mm
2 ft. 610 mm
3 ft. 914 mm
4 ft.
1.2 m
6 ft.
1.8 m
H1 + H2 Maximum 1 ft. 305 mm
2 ft. 610 mm
4 ft.
1.2 m
8 ft.
2.4 m
12 ft.
3.7 m
20 ft.
6.1 m
V1 + H1 + H2 = 40 ft. (12.2 m) Maximum H1 + H2 = 20 ft. (6.1 m) Maximum
6KX-AU (ULPG)
V1 Minimum 1 ft. 305 mm
H1 + H2 Maximum
1 ft.
305 mm
2 ft. 610 mm
3 ft.
914 mm
3 ft. 914 mm
5 ft.
1.5m
4 ft.
1.2 m
7 ft.
2.1 m
6 ft.
1.8 m
11 ft.
3.4 m
V1 + H1+ H2 = 40 ft. (12.2 m) Maximum H1+ H2 = 11 ft. (3.4 m) Maximum
H2
V1
H1
INSTALLED HORIZONTALLY
Figure 4.13 32
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Top Vent – Horizontal Termination – (continued)
Three Elbows
Note: For corner installations: A 6 in. (152 mm) section of straight pipe may need to be attached to the appliance before a 90º elbow, to allow the vent pipe to clear the top standoffs.
WARNING! Risk of Fire! Elbow
heat ft. or
lsehsise.ldCrleeqaurairnecdeswthoecnoVm1b=us2-
tibles must be maintained. See
Section 5.A.
6KX-AU (NG/LP)
V1 Min. .5 ft. 152 mm 1 ft. 305 mm 2 ft. 610 mm 3 ft. 914 mm 4 ft. 1.2 m
H1 Max. 2 ft 610 mm 4 ft. 1.2 m 8 ft. 2.4 m 12 ft. 3.7 m 16 ft 4.9 m
V2 Min.
6 in.
152 mm
1 ft. 305 mm
2 ft. 610 mm
3 ft. 914 mm
4 ft.
1.2 m
H2 Max.
2 ft.
610 mm
4 ft.
1.2 m
8 ft.
2.4 m
12 ft. 3.7 m
16 ft. 4.9 m
*H1 + H2 = 20 ft. (6.1 m) Maximum
V1 + V2 + H1 + H2 = 40 ft. (12.2 m) Maximum
6KX-AU (ULPG)
V1 Min. 1 ft. 305 mm 2 ft. 610 mm 3 ft. 914 mm 4 ft. 1.2 m
H1 Max. 2 ft. 610 mm 4 ft. 1.2 m 6 ft. 1.8 m 8 ft. 2.4 m
V2 Min. 1 ft. 305 mm
2 ft. 610 mm
3 ft. 914 mm
4 ft.
1.2 m
H2 Max.
2 ft.
610 mm
4 ft.
1.2 m
6 ft.
1.8 m
8 ft.
2.4 m
*H1 + H2 = 16 ft. (4.9 m) Maximum
V1 + V2 + H1 + H2 = 40 ft. (12.2 m) Maximum
H2
V2
H1
V1
Figure 4.14 Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 33
Top Vent – Vertical Termination No Elbow
V1 = 40 ft. Max. (12.4 m) V1 = 3 ft. Min. (914 mm)
Note: If installing a vertical vent/ termination off the top of the appliance,
the flue restrictor should be used.
V1
Figure 4.15 34
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Top Vent – Vertical Termination (continued)
Flue Restrictor Instructions
1. Remove the top piece of refractory, if already installed. See Figure 4.16.
2. Remove the flue visor and discard. See Figure 4.16. 3. Orientate and align
the two pieces of the flue restrictor
as shown in Figure 4.17. 4. Refer to Table 4.1 and Figure 4.17 to match the
amount
of vertical you have in the system and determine the appropriate position to
set the flue restrictor. 5. Center the two flue restrictor pieces on the vent
at the setting selected in step 4 and secure in place by using two self-
tapping screws. See Figure 4.16. 6. Reinstall the refractory.
REMOVE TOP REFRACTORY
Vertical
4 ft. (1.2 m)
8 ft. (2.4 m)
15 ft. (4.6 m)
20 ft. (6.0 m)
25 ft. (7.6 m)
30 ft. (9.1 m)
35 ft. (10.7 m)
40 ft. (12.2 M)
Table 4.1
TOP VENT
NG
LP/ULPG
1-1
No Restrictor
2-2
1-2
REAR VENT
NG
LP/ULPG
No
No
Restrictor Restrictor
1-1
No Restrictor
3-2
3-2
2-2
1-2
3-2
3-2
3-2
3-2
3-2
3-2
3-2
3-2
3-3
3-3
3-3
3-3
3-4
3-4
3-4
3-3
3-4
3-4
3-4
3-4
REMOVE FLUE VISOR AND DISCARD
FLUE RESTRICTOR INSTALLED TOP VENTED APPLIANCE
FLUE RESTRICTOR INSTALLED REAR VENTED APPLIANCE
Figure 4.16
ALWAYS USED WITH THE HOLES TO THE RIGHT
1 2 3 45
1 2 3 45
TO BREAK APART BEND HERE
1 2 3 45
1 2 3 45
ALWAYS USED WITH THE HOLES TO THE RIGHT
FLUE RESTRICTOR SET TO 4-4
Figure 4.17 Setting the Flue Restrictor
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 35
Top Vent – Vertical Termination – (continued) Two Elbows
V2
V1 Elbow only
H1 Maximum V2 V1 + V2 Min.
2 ft. 610 mm
.5 ft. 152 mm 6 ft. 1.8 m
2 ft. 610 mm 11 ft. 3.4 m
3 ft. 914 mm 16 ft. 4.9 m
4 ft. 1.2 m 20 ft. 6.1 m
V1 + V2 + H1 = 50 ft. (15.2 m) Maximum *No specific restrictions on this value
EXCEPT
V1 + V2 + H1 cannot exceed 50 ft (15.2 m)
V1 H1
Figure 4.18
Three Elbows
V1 Elbow only
H1 + H2
V2 V1 + V2 Minimum
1 ft. 305 mm *
H1 + H2 Maximum
1 ft.
305 mm
.5 ft. 152 mm 2 ft. 610 mm *
2 ft.
610 mm
1 ft. 305 mm 2 ft. 610 mm *
2 ft.
610 mm
2 ft. 610 mm 4 ft.
1.2 m
4 ft.
V2
3 ft. 914 mm 9 ft.
2.7 m
9 ft.
1.2 m 2.7 m
4 ft.
1.2 m 18 ft. 5.5 m *
18 ft.
5.5 m
H1 + H2 = 18 ft. (5.5 m) Maximum
V1 + V2 + H1 + H2 = 40 ft. (12.2 m) Maximum
- No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2 cannot exceed 40 ft. (12.2 m).
H1
H2
V1
INSTALLED HORIZONTALLY
Figure 4.19 36
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Rear Vent – Horizontal Termination No Elbow
H1 Maximum (NG/LP)
6KX-AU
16 in. (406 mm)
H1 Maximum (ULPG)
6KX-AU
12 in. (305 mm)
H1
Figure 4.20
One 45º Elbow
Do not use a 45º elbow in corner installations.
H1
Use two 90º elbows instead.
Figure 4.21 Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 37
Rear Vent – Horizontal Termination – (continued)
Two Elbows
H1 Maximum .5 ft. 152 mm
V1 Minimum
Back to Back 90º Elbows
H2
1 ft.
305 mm
H1 + H2 Maximum
1.5 ft
457 mm
1 ft. 305 mm 6 in. 152 mm 1.5 ft.
457 mm
2.5 ft.
762 mm
2 ft. 610 mm 1 ft. 305 mm
2 ft.
610 mm
4 ft.
1.2 m
3 ft. 914 mm 2 ft. 610 mm
3 ft.
914 mm
6 ft.
1.8 m
3 ft. 914 mm 3 ft. 914 mm
7 ft.
2.1 m
10 ft.
3.0 m
3 ft. 914 mm 4 ft.
1.2 m
12 ft.
3.7 m
15 ft.
4.6 m
3 ft. 914 mm 5 ft
1.5 m
17 ft.
5.2 m
20 ft.*
6.1 m*
V1 + H1 + H2 = 40 ft. (12.2 m) Maximum H1 = 3 ft. (914 mm) Maximum *H1 + H2 = 20 ft (6.1 m) Maximum
H2
Figure 4.22
Three Elbows
INSTALLED HORIZONTALLY
H3
V1
H1
H1 Maximum 0 ft. 0 mm
V1 Minimum
Back to Back 90º Elbows
H2+ H3 1 ft. 305 mm
H1+ H2+ H3 Max. 1 ft. 305 mm
1 ft. 305 mm 6 in. 152 mm 1.5 ft. 457 mm 2.5 ft. 762 mm
2 ft. 610 mm 1 ft. 305 mm 2 ft. 610 mm 4 ft.
1.2 m
3 ft. 914 mm 2 ft. 610 mm 3 ft. 914 mm 6 ft.
1.8 m
3 ft. 914 mm 3 ft. 914 mm 7 ft.
2.1 m
10 ft.
3.0 m
3 ft. 914 mm 4 ft.
1.2 m
12 ft.
3.7 m
15 ft.
4.6 m
3 ft. 914 mm 5 ft.
1.5 m
17 ft.
5.2 m
20 ft. 6.1 m
V1+ H1+ H2+ H3= 40 ft. (12.2 m) Maximum H1= 3 ft. (914 mm) Maximum H1+ H2+ H3= 20 ft. (6.1 m) Maximum
H2
V1
Figure 4.23 38
H1
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Rear Vent – Vertical Termination One Elbow
V1 H1
Figure 4.24
Two Elbows
V1
V1 Minimum
H1 Maximum
.5 ft. 152 mm 2 ft. 610 mm
1 ft. 305 mm 3 ft. 914 mm
2 ft. 610 mm 5 ft. 1.5 m
3 ft. 914 mm 7 ft. 2.1 m
4 ft.
1.2 m 8 ft. 2.4 m
5 ft.
1.5 m 8 ft. 2.4 m
V1 + H1 = 40 ft. (12.2 m) Maximum H1 = 8 ft. (2.4 m) Maximum
V1 Minimum
H1 + H2 Maximum
Back to Back 90º Elbows
3 ft.
914 mm
2 ft.
610 mm
6 ft.
1.8 m
4 ft.
1.2 m
9 ft.
2.7 m
6 ft.
1.8 m
12 ft.
3.7 m
8 ft.
2.4 m
15 ft.
4.6 m
V1 + H1 +H2 = 40 ft. (12.2 m) Maximum H1 + H2 = 15 ft. (4.6 m) Maximum
INSTALLED
HORIZONTALLY
H1
H2
Figure 4.25 Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 39
Rear Vent – Vertical Termination – (continued)
Three Elbows
H1 Maximum 2 ft. 610 mm
V1 Minimum 6 in. 152 mm
H2
2 ft.
610 mm
H1 + H2 Maximum 4 ft. 1.2 m
3 ft. 914 mm 1 ft. 305 mm 4 ft. 1.2 m 7 ft.
2.1 m
5 ft. 1.5 m 2 ft. 610 mm 6 ft. 1.8 m 11 ft. 3.4 m
V2
7 ft. 2.1 m 3 ft. 914 mm 8 ft. 2.4 m 15 ft. 4.6 m
8 ft 2.4 m 4 ft. 1.2 m 10 ft. 3.1 m 18 ft. 5.5 m
H1= 8 ft (2.4 m) Max. V1 + V2 + H1 + H2= 40 ft (12.2 m) Max. H1 + H2 = 20 ft (6.1 m) Max.
H2 V1
Figure 4.26
Three Elbows
H1
H1 H2 H3 ***
V1 Minimum H1 + H2 + H3 Maximum
8 ft. 2.4 m 6 ft.
1.8 m
-
-
- 9 ft. 2.7 m 7 ft.
-
2.1 m
-
-
- 10 ft. 3.1 m 8 ft.
-
2.4 m
-
-
- 10 ft. 3.1 m 8 ft.
-
2.4 m
V1 + H1 + H2 + H3 = 40 ft. (12.2 m) Maximum
V1
*No specific restrictions on this value EXCEPT
V1 + H1 + H2 + H3 cannot exceed 40 ft. (12.2 m) Maximum
H1 + H2 + H3 = 8 ft. (2.4 m) Maximum
H3
Figure 4.27 40
H1
H2
INSTALLED HORIZONTALLY
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
F. Power Vent Configurations
The PVLP-SLP-AU power vent is appoved for use with this appliance.
Table 4.1 below shows the allowable vent length and elbow combinations when
using PVLP-SLP-AU. Refer to the PVLP-SLP-AU instruction manual for limitations
and appliance specific requirements.
Horizontal Termination
Total Venting Length (Feet) Includes both horizontal and vertical section of pipe
of Elbows
10 ft. 20 ft. 30 ft.
40 ft.
50 ft.
60 ft.
70 ft.
80 ft.
90 ft.
(3.05 m) (6.10 m) (9.14 m) (12.19 m) (15.24 m) (18.29 m) (21.34 m) (24.38 m) (27.43 m)
1
2
3 4
ALLOWABLE
5
6 7 8
VENT RUNS
NOT
9
10 11
ALLOWED
12
Table 4.28 Allowable Vent Runs – Horizontal Termination
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 41
5 Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack
insulation or other combustibles:
· Between ceiling firestops · Between wall shield firestops · Around vent
system Failure to keep insulation or other material away from vent pipe could
cause overheating and fire.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). · DVP heat
shield – designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184
mm) thick. · If wall thickness is less than 4 in. (102 mm) the existing heat
shields must be field
trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will
be required.
DVP Pipe
Heat Shield
3 in. (76 mm) top clearance *
Heat Shield
To Install Elbow Heat Shield:
1. Remove the elbow heat shield from the shipping position by removing
screws.
2. Fasten the shield in place using the four pilot holes. The shield should
be oriented such that the dimension (longest dimension) is running in the same
direction the elbow is pointing. The shield should be centered directly above
the elbow, and positioned so that it creates a 1/2 in. (13 mm) airspace
between the shield and the combustible surface. See Figure 5.2.
CORRECT
INCORRECT
COMBUSTIBLE SURFACE DIRECTION UP
HEAT SHIELD
Wall Shield Firestop
1 in. (25 mm) clearance bottom & sides
WALL
90º ELBOW
SCREW
Warning! Risk of Fire: Elbow heat shield required with 3 in. (76 mm) top
clearance or V1 of 2 ft. (610 mm) or less.
Figure 5.1 Horizontal Venting Clearances To Combustible Materials – Generic
Fireplace Shown
3 in. (76 mm)
Elbow Heat Shield
WARNING! Risk of Fire! Elbow heat shield MUST be installed if required.
Overheating will occur.
Top vented appliances: Installation of the elbow heat shield is required when
the clearance to combustible material above the first 90 degree vent elbow is
three inches or less. See Figure 5.1.
Note: A minimum of three inches (76 mm) clearance from the top of the pipe to
any combustible material must always be maintained.
To Install Elbow Heat Shield:
1. Remove the elbow heat shield from the shipping position by removing
screws.
2. Fasten the shield in place using the four pilot holes. The shield should
be oriented such that the dimension (longest dimension) is running in the same
direction the elbow is pointing. The shield should be centered directly above
the elbow, and positioned so that it creates a 1/2 in. (13mm) airspace between
the shield and the combustible surface. See Figure 5.2.
Figure 5.2 Elbow Heat Shield Installation
42
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Elbow and Offset Clearances to Combustibles
1 in (25 mm) MIN. ALL SIDES
1 in (25 mm) MIN. ALL SIDES
1 in (25 mm) MIN. ALL SIDES
3 in (76 mm) VERTICAL CLEARANCE HORIZONTAL PIPE SECTIONS
1 IN. (25 mm) MIN. HORIZONTAL CLEARANCE VERTICAL PIPE SECTIONS
= NO COMBUSTIBLES ALLOWED IN SHADED AREA
Figure 5.3 Clearances from Vent to Combustible Framing Materials
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-combustible materials such
as concrete, a hole with diameter one inch greater than the pipe is
acceptable.
Whenever a non-combustible wall is penetrated, the wall shield firestop is
only required on one side and no heat shield is necessary.
B. Wall Penetration Framing/Firestops
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must frame a hole for the wall
shield firestop(s). The wall shield firestop maintains minimum clearances and
prevents cold air infiltration.
· The opening must be framed on all four sides using the same size framing
materials as those used in the wall construction.
· DVP pipe – A wall shield firestop is required on one side only on interior
walls. If your local inspector requires a wall shield firestop on both sides,
then both wall shield firestops must have a heat shield (refer to Section
12.A.) attached to them.
· See Section 7.F. for information for regarding the installation of a
horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-combustible materials such
as concrete, a hole with diameter one inch greater than the pipe is
acceptable.
Whenever a non-combustible wall is penetrated, the wall shield firestop is
only required on one side and no heat shield is necessary.
DO NOT PACK VENT FRAMING HOLE WITH INSULATION OR OTHER MATERIAL.
10 in.
(254 mm)
10 in.
(254 mm)
A*
B*
12 in.
(305 mm)
C D
12 in.
(305 mm)
A* in. 42-3/4 6KX-AU mm 1086
B* 27-7/8
708
C 41-3/4 1060
D 26-7/8
683
- Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) in. (25 mm) above the center of the horizontal vent pipe.
Note: Center of the horizontal vent pipe to the vertical measuring surface of a trap cap is 5 inches (127 mm).
Figure 5.4 Wall Penetration Heat & Glo · 6KX-AU Installation Manual · 2589-980
Rev. B · 5/23
43
C. Ceiling Firestop/Floor Penetration Framing
A ceiling firestop MUST be used between floors and attics.
· DVP pipe only – Frame an opening 10 in. by 10 in. (254 mm by 254 mm)
whenever the vent penetrates a ceiling/floor (see Figure 5.5).
· Frame the area with the same sized lumber as used in ceiling/floor joist.
· The ceiling firestop may be installed above or below the ceiling joists when
installed with an attic insulation shield. It must be under joists between
floors that are not insulated. See Figure 5.6.
· Secure in place with nails or screws.
WARNING! Risk of Fire! DO NOT pack insulation around the vent. Insulation must
be kept back from the pipe to prevent overheating.
ATTIC ABOVE A
A
D. Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent.
Hearth & Home Technologies requires the use of an attic shield.
The International Fuel Gas Code requires an attic shield constructed of 26
gauge minimum steel that extends at least 2 in. (51 mm) above insulation.
· Attic insulation shields must meet specified clearances to combustible
materials and be secured in place.
· An attic insulation shield kit is available from Hearth & Home Technologies.
Contact your dealer to order. Install attic insulation shield according to
instructions included with kit.
PIPE DVP
A 10 in. (254 mm)
Figure 5.5 Installing Ceiling Firestop – Generic Fireplace Shown
INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP INSTALLED BELOW CEILING
Figure 5.6 Installing the Attic Shield
CEILING FIRESTOP INSTALLED ABOVE CEILING
44
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
6 Appliance Preparation
A. Vent Collar Preparation
CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and
safety glasses during installation. Sheet metal edges are sharp. NOTICE: Once
appliance is set up for top or rear venting, it CANNOT be changed at a later
time.
Top Vent
REMOVE SCREWS
Figure 6.1 Remove Elbow Heat Shield by Removing Two Screws
SEAL CAP
Figure 6.4 Remove Seal Cap NOTICE: Once the seal cap has been removed it CANNOT be reattached.
INSULATION BASKET
INNER VENT INSULATION
OUTER VENT INSULATION
TIN SNIPS
Figure 6.2 Cut Seal Cap Strap Using a Tin Snips and Bend the Pieces to 90
Degrees
Figure 6.5 Remove Insulation Basket, Inner Vent Insulation and Outer Vent
Insulation
VENT GASKET
GASKET MATERIAL
Figure 6.3 Remove the White Gasket Material Covering the Seal Cap
Figure 6.6 (Generic Fireplace Shown) To attach the first section of vent pipe,
make sure to use the vent gasket in the manual bag to seal between the first
vent component and the outer fireplace wrap. Seal with four screws or caulk
with a minimum of 300 ºF (149 ºC) continuous exposure rating may be used to
hold the part in place.
Secure the first section of venting to the fireplace by screwing through the
two straps left over from cutting the seal cap strap (Figure 6.6).
It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer
pipe sections together. If predrilling holes, DO NOT penetrate inner pipe.
Figure 6.3 (Generic Appliance Shown) Remove the seal cap.
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 45
Rear Vent
NOTICE: Once appliance is set up for top or rear venting, it CANNOT be changed
at a later time.
INNER VENT INSULATION
SEAL CAP
TIN SNIPS
Figure 6.7 Cut Seal Cap Strap Using a Tin Snips and Bend the Pieces to 90
Degrees
INSULATION BASKET
Figure 6.10 Remove Insulation Basket and Inner Vent Insulation
GASKET MATERIAL
VENT GASKET
Figure 6.8 Remove the White Gasket Material Covering the Seal Cap
REMOVE SEAL CAP
Figure 6.11 (Generic Fireplace Shown) To attach the first section of vent
pipe, make sure to use the vent gasket in the manual bag to seal between the
first vent component and the outer fireplace wrap. Seal with four screws or
caulk with a minimum of 300 ºF (149 ºC) continuous exposure rating may be used
to hold the part in place.
Secure the first section of venting to the fireplace by screwing through the
two straps left over from cutting the seal cap strap (Figure 6.11).
It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer
pipe sections together. If predrilling holes, DO NOT penetrate inner pipe.
SEAL CAP STRAPS Figure 6.9 Remove Seal Cap NOTICE: Once the seal cap has been removed it CANNOT be reattached.
46
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
B. Prepare For Heat Management
WARNING! Risk of Fire! DO NOT block passive heat registers! Overheating of
appliance and combustible materials will occur. WARNING! Risk of Fire! DO NOT
remove a knockout unless a heat management system will be installed in its
place. Appliance and combustible materials will overheat.
Introduction
An optional heat management system allows the heat from the appliance to be
redirected as desired.
An optional heat management system must be installed by a qualified service
technician at the time of the appliance installation. Follow the instructions
shipped with the kit for installation and operation.
Heat Management System options are:
· HEAT-ZONE®-240V: The heat is diverted into an adjacent room. The HZMR-ADP
Heat-Zone Adapter kit may be required and is ordered separately. See Table
6.1.
· Passive Heat (PH-MR): The heat is vented into the room in which the
appliance is installed through a discharge opening(s).
NOTICE: Additional clearances are required for heat management systems
installations. Provisions must be made in advance to ensure fit within the
framing.
· Determine the heat management system(s) that will be installed.
· Locate the two heat management knockouts on the top of the appliance. Remove
the knockout from the fireplace and discard it. See Figure 6.12. Either one or
two heat management systems may be installed. Remove the knockout(s) from the
appliance with a tin snips.
· Center the duct collar around the exposed hole and attach it to the
appliance with 3 screws.
Note: Do this BEFORE final positioning of the appliance.
· Determine the location for the air register/fan housing assembly.
Reference the appropriate instructions included with the kit for the remaining
installation steps.
These models may utilize two Heat Management Systems, but not all are
compatible.
Passive Heat may be used with HEAT-ZONE®-240V. The dedicated knockouts, as
shown in Figure 6.12, must be used only as indicated.
Note: When a fan is operated with the Passive Heat system, there will be a
decrease in the amount of air flowing from the appliance opening. Air will be
flowing from both the appliance opening and the passive heat opening.
HZMR-ADP
HEAT-ZONE-240V HEAT-ZONE-240V + PASSIVE HEAT
Table 6.1 HZMR-ADP Kit
Required Not Required
HEAT-ZONE®-240V KNOCKOUT LOCATIONS
PASSIVE HEAT REAR COVER KNOCKOUTS
PASSIVE HEAT ADAPTER KNOCKOUTS
PASSIVE HEAT FRONT COVER KNOCKOUT
Figure 6.12 Heat Management Knockout Locations
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 47
C. Securing and Leveling the Appliance
WARNING
Risk of Fire!
Prevent contact with: · Sagging or loose insulation · Insulation backing or
plastic · Framing and other combustible materials
DO NOT remove standoffs or notch the framing around the appliance standoffs.
Failure to maintain air space clearance could cause overheating and fire.
Block openings into the chase to prevent entry of blown-in insulation. Make
sure insulation and other materials are secured.
The diagram shows how to properly square and position, and secure the
appliance. See Figures 6.13 and 6.14. Nailing tabs are provided to secure the
appliance to the framing members. · Bend out nailing tabs on each side. ·
Place the appliance into position. · Keep nailing tabs flush with the framing.
· Level the appliance from side to side and front to back. · “Square” the unit
by securing diagonal dimensions to
within 1/4 in. (6 mm) of each other. See Figure 6.14. · Shim the appliance as
necessary. It is acceptable to use
wood shims underneath the appliance. · Secure the appliance to the framing by
using nails or
screws through the nailing tabs. Use a minimum of one fastener per nailing
tab. · Optional: Secure the appliance to the floor by inserting two screws
through the pilot holes at the bottom of the appliance.
A
B
Note: Diagonal dimensions (A) and (B) must be within 1/4 in. (6 mm) of each
other.
Figure 6.14 Positioning the Appliance Squarely
D. Non-Combustible Material (FactoryInstalled)
WARNING! Risk of Fire! DO NOT remove factory-installed non-combustible
material. A non-combustible board is factory-installed above the fireplace
opening. Do not remove. The factory supplied non-combustible board spans the
distance from the top of the fireplace to the center of the framing header.
This board must be used. See Figure 6.15.
6-5/16 IN. (160 mm) FACTORY-INSTALLED NON-COMBUSTIBLE BOARD DO NOT REMOVE
NAILING TABS (BOTH SIDES)
Figure 6.13 Proper Positioning and Securing of an Appliance
Figure 6.15 Non-Combustible Board – Studio Decorative Barrier Front Shown
48
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
7 Venting
A. Assemble Vent Sections
(DVP Pipe Only)
WARNING! Risk of Fire or Explosion! Vent sections MUST be installed correctly.
Improperly installed vent sections could leak or cause appliance to overheat.
Attach Vent to the Firebox Assembly
Note: The end of the pipe sections with the lanced tabs will face toward the
appliance. Attach the first pipe section to the starting collar: · Lanced pipe
end of the starting collar. · Inner pipe over inner collar. · Push the pipe
section until all lanced tabs snap in place. · Lightly tug on pipe to confirm
it has locked.
Required: Commercial, Multi-family (Multi-level exceeding two stories), or
High-Rise Applications
Recommended: Vent Configurations with five or more pipe joints/pipe
connections
WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip
sections. Use care when removing termination cap from slip pipe. If slip
section seals are broken during removal of the termination cap, vent could
leak.
All outer pipe joints must be sealed using one of the methods below, including
the slip section that connects directly to the horizontal termination cap.
· Apply a bead of silicone sealant (300 ºF (149 ºC) minimum continuous
exposure rating) inside the female outer pipe joint prior to joining sections.
See Figure 7.1 OR
· Apply a bead of silicone sealant (300 ºF (149 ºC) minimum continuous
exposure rating) to the outside of connecting joint after joining sections OR
Apply aluminum foil tape (300 ºF (149 ºC) minimum continuous exposure rating)
to the outside of connecting joint after joining sections. On horizontal pipe
runs, it is recommended that the tape seam is positioned on the bottom side of
the vent pipe.
· Only outer pipes need to be sealed. All unit collar, pipe, slip section,
elbow and cap outer flues shall be sealed in this manner, unless otherwise
stated.
Assemble Pipe Sections
Per Figure 7.2:
· Start the inner pipe on the lanced end of section A into the flared end of
section B.
· Start the outer pipe of section A over the outer pipe of section B.
· Once both vents sections are started, push firmly until all lanced tabs lock
into place.
· Lightly tug on the pipe to confirm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer
pipe sections together. If predrilling holes, DO NOT penetrate inner pipe.
For 90º and 45º elbows that are changing the vent direction from horizontal to
vertical, one screw minimum should be put in the outer flue at the horizontal
elbow joint to prevent the elbow from rotating. Use screws no longer than 1/2
in. (13 mm). If predrilling screw holes, DO NOT penetrate inner pipe.
Figure 7.1 High Temperature Silicone Sealant
A
Lances
B
Figure 7.2
Figure 7.3
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 49
Note: Make sure that the seams are not aligned to prevent unintentional disconnection.
B. Assemble Slip Sections
· Slide the inner flue of the slip section into the inner flue of the pipe
section and the outer flue of the slip section over the outer flue of the pipe
section. See Figure 7.5.
· Slide together to the desired length.
CORRECT
INCORRECT
Figure 7.4 Seams
NOTICE: When installing a vent system with an HRC termination cap, all pipe
system joints shall be sealed using a high temperature silicone sealant (300
ºF (149 ºC) minimum continuous exposure rating). · Apply a bead of silicone
sealant (300 ºF (149 ºC) minimum
continuous exposure rating) inside the female outer pipe joint prior to
joining sections. · Only outer pipes are sealed, sealing the inner flue is not
required. · All unit collar, pipe, slip section, elbow and cap outer flues
shall be sealed.
Pilot hole
Figure 7.5 Slip Section Pilot Holes
· Maintain a 1-1/2 in. (38 mm) overlap between the slip section and the pipe
section.
· Secure the pipe and slip section with two screws no longer than 1/2 in. (13
mm), using the pilot holes in the slip section. See Figure 7.6.
Figure 7.6 Screws into Slip Section
· Continue adding pipe as necessary following instructions in “Assembling Pipe
Sections.”
NOTICE: If slip section is too long, the inner and outer flues of the slip
section can be cut to the desired length.
50
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
C. Secure the Vent Sections
WARNING! Risk of Fire, Explosion or Asphyxiation! Improper support could allow
vent to sag and separate. Use vent run supports and connect vent sections per
installation instructions. DO NOT allow vent to sag below connection point to
appliance.
· Vertical runs originating off the top of the appliance, with no offsets,
must be supported every 8 feet (2.44 m) after the maximum allowed 25 feet
(7.62 m) of unsupported rise.
· Vertical runs originating off the rear of the appliance, or after any elbow,
must be supported every 8 feet (2.44 m).
· Horizontal runs must be supported every 5 feet (1.52 m).
· Vent supports or plumbers strap (spaced 120º apart) may be used to support
vent sections. See Figures 7.7 and 7.8.
Note: Figures 7.7 and 7.8 are to be used for reference only. Method of strap
installation could vary by configuration of vent system.
· Wall shield firestops may be used to provide horizontal support to vent
sections.
D. Disassemble Vent Sections
· Rotate either section (see Figure 7.9) so the seams on both pipe sections
are aligned as shown in Figure 7.10.
· Pull carefully to separate the pieces of pipe.
Figure 7.90 Rotate Seams for Disassembly
120º
Figure 7.7 Securing Vertical Pipe Sections
120º
Figure 7.10 Align and Disassemble Vent Sections
Figure 7.8 Securing Horizontal Pipe Sections Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 51
E. Vertical Termination Requirements Install and Seal Metal Roof Flashing
· See minimum vent heights for various pitched roofs (Section 4, Figure 4.1)
to determine the length of pipe to extend through the roof.
· Slide the roof flashing over the pipe sections extending through the roof as
shown in Figure 7.11.
· Use an elastomeric or silicone sealant with a minimum of 150 ºF temperature
rating to seal the metal roof flashing.
Note: When installing a silicone or EPDM pipe flashing boot on a metal roof,
it is recommended to put a bead of 100% silicone sealant where the boot
contacts the vent pipe to prevent the entry of water. Follow the
manufacturer’s recommendations when installing the boot. Climate regions with
frequent temperatures below – 50 °F (-45.6 °C) should use a silicone flashing
boot.
NOTICE: Failure to properly seal the roof flashing and pipe seams could permit
entry of water. · Seal the gap between the roof flashing and the outside
diameter of the pipe. · Seal the perimeter of the flashing where it contacts
the
roof surface. See Figure 7.11. · Seal the exposed pipe section seams that are
located
above the roof.
SEAL
Figure 7.12 Insert Bolt into Brackets
· Slide the assembled storm collar down the pipe section until it rests on the
roof flashing. See Figure 7.12.
· Tighten nut and make sure the collar is tight against the pipe section.
· Seal around the top of the storm collar. See Figure 7.13.
Install Vertical Termination Cap
· Attach the vertical termination cap by sliding the inner collar of the cap
into the inner flue of the pipe section while placing the outer collar of the
cap over the outer flue of the pipe section.
· Secure the cap by driving three self-tapping screws (supplied) through the
pilot holes in the outer collar of the cap into the outer flue of the pipe.
See Figure 7.13.
TERMINATION CAP
Figure 7.11
Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and
safety glasses during installation. Sheet metal edges are sharp. · Slide the
storm collar onto the exposed pipe section
and align brackets. · Insert a bolt (provided) through the brackets and
install
nut. Do not completely tighten.
(1 OF 3) SCREWS
SEAL
Figure 7.13
52
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
STORM COLLAR
F. Horizontal Termination Requirements
Heat Shield Requirements for Horizontal Termination
WARNING! Risk of Fire! To prevent overheating and fire, heat shields must
extend through the entire wall thickness.
· DO NOT remove the heat shields attached to the wall shield firestop and the
horizontal termination cap (shown in Figure 7.14).
· Heat shields must overlap 1-1/2 in. (38 mm) minimum.
There are two sections of the heat shield. One section is factory-attached to
the wall shield firestop. The other section is factory-attached to the cap.
See Figure 7.14.
If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat
shield overlap when installed, an extended heat shield must be used.
· If the wall thickness is less than 4 in./102 mm (DVP), the heat shields on
the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm)
overlap MUST be maintained.
· Use an extended heat shield if the finished wall thickness is greater than
7-1/4 in. (184 mm).
· The extended heat shield may need to be cut to length maintaining sufficient
length for a 1-1/2 in. (38 mm) overlap between heat shields.
· Attach the extended heat shield to either of the existing heat shields using
the screws supplied with the extended heat shield. Refer to vent components
diagrams in the back of this manual.
· Rest the small leg on the extended heat shield on top of the pipe section to
properly space it from the pipe section.
Important Notice: Heat shields may not be field constructed.
Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping flue section of the termination cap
MUST be used when connecting vent.
· 1-1/2 (38 mm) minimum overlap of flue telescoping section is required.
Failure to maintain overlap could cause overheating and fire.
· Vent termination must not be recessed in the wall. Siding may be brought to
the edge of the cap base.
· Flash and seal as appropriate for siding material at outside edges of cap.
CAUTION! Risk of Burns! Local codes may require installation of a cap shield
to prevent anything or anyone from touching the hot cap.
NOTICE: For certain exposures which require superior resistance to wind-driven
rain penetration, a flashing kit and HRC caps are available. When penetrating
a brick wall, a brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied heat shield attached,
no additional wall shield firestop is required on the exterior side of a
combustible wall.
DVP-TRAP1 Exception See Section 3.C for DVP-TRAP1 exception for top vent,
horizontally terminated installation.
WALL SHIELD FIRESTOP
HEAT SHIELD OR EXTENDED
HEAT SHIELD
HEAT SHIELD 1-1/2 IN. (38 MM) MIN.
OVERLAP
SLIP SECTION CAN BE EXTENDED
INNER VENT OUTER VENT
INTERIOR
SHEATHING EXTERIOR
Figure 7.14 Venting Through the Wall
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 53
8 Electrical Information
A. General Information
WARNING! Risk of Shock or Explosion! DO NOT wire 220/240 VAC to the valve or
to the appliance wall switch. Incorrect wiring will damage controls. · Wire
the appliance junction cord to unswitched 220/240
VAC. This is required for proper operation of the appliance. · A 220/240 VAC
circuit for this product must be protected with ground-fault circuit-
interrupter protection, in compliance with the applicable electrical codes,
when it is installed in locations such as in bathrooms or near sinks. · Low
voltage and 220/240 VAC voltage cannot be shared within the same wall box.
Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation. Verify
proper operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with type 105 ºC rated wire. Wire
must have high temperature insulation.
Accessories Requirements
· This appliance may be used with a wall switch, wall mounted thermostat
and/or a remote control.
Wiring for optional Hearth & Home Technologies approved accessories should be
done now to avoid reconstruction. Follow instructions that come with those
accessories.
54
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
B. Wiring Requirements
IntelliFireTM Plus Ignition System Wiring
· Wire the appliance junction cord to 220/240 VAC for proper operation of the
appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire IPI controlled appliance
junction cord to a switched circuit. Incorrect wiring will override IPI safety
lockout. · Refer to Figure 8.1, IPI Wiring Diagram.
· This appliance is equipped with an IntelliFireTM Plus control valve which
operates on a 6 volt/1.5 AMP system.
· Plug the 6 volt transformer plug into the appliance junction cord to supply
power to the unit OR install 4 AA cell batteries (not included) into the
battery pack before use.
NOTICE: Batteries should only be used as a power source in the event of an
emergency power outage. Batteries should not be used as a primary long-term
power source. Battery polarity must be correct when installing batteries. When
using batteries as a power source, the 6-volt transformer must be unplugged
from the receptacle.
Do not store batteries in the battery pack when the appliance is powered by
the 6 volt transformer connected to permanent electrical service.
Accessories Requirements
· This appliance ships standard with a remote control. Wiring for optional
Hearth & Home Technologies approved accessories should be done now to avoid
reconstruction. Follow instructions that come with those accessories. The
junction cord, control module, LED power supply and wall switch receiver can
be accessed by removing the vanity panel and component heat shield. The
decorative front must be removed to access these components. See Figure 8.1.
CAUTION! Risk of Overheating! Component heat shield MUST be installed before
operating appliance. Electrical components will be damaged.
CAUTION! Risk of Overheating! DO NOT remove component insulation from top of
component heat shield. Electrical components will be damaged.
Note: When using PVLP-SLP-AU power vent, see PVLP-SLP-AU instructions for
additional wiring requirements.
PILOT ASSEMBLY
2106-169 (N) 2106-170 (LP)
FLAME SENSE
IGNITER
RC300 REMOTE CONTROL REM300-HNG-AU
240V FAN GFK-240V
CONTROL MODULE 2166-306
TRANSFORMER SRV2326-131
GAS VALVE
2166-302 (N) 2166-303 (LP)
WIRE HARNESS 2166-304
GREEN WIRE ORANGE WIRE
RED WIRE BLACK WIRE
BATTERY PACK 2166-323
JUNCTION CORD 2222-037
AUX MODULE 2166-340
GROUND
LED CONTROL 2326-114
EMBER LIGHTING 2583-061
2589-160
Figure 8.1 IntelliFire® Plus Wiring Diagram with Remote Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 55
C. Service for Fan
If appliance is already installed, service should be performed by a qualified
service technician.
· Remove decorative barrier front, glass, logs, base pan assembly, burner
assembly and valve plate assembly.
· Service can be performed through the valve plate cavity. See Figure 8.2.
· Reinstall valve plate assembly, burner assembly, basepan assembly, logs,
appliance glass and decorative barrier front.
FAN INSTALLED
Figure 8.2 Fan Installed in Valve Plate Cavity
56
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
9 Gas Information
A. Fuel Conversion
· Make sure the appliance is compatible with available gas types.
· Conversions must be made by a qualified service technician using Hearth &
Home Technologies specified and approved parts.
B. Gas Pressure
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
· Disconnect gas supply piping BEFORE pressure testing gas line at test
pressures above 3.40 KPa (1/2 psig).
· Close the manual shutoff valve BEFORE pressure testing gas line at test
pressures equal to or less than 3.40 KPa (1/2 psig).
WARNING! Risk of Explosion! An in-line regulator MUST be installed if the gas
pressure exceeds 3.4 kPa. Failure to install a regulator could damage valve.
Pressure requirements for 6KX-AU fireplaces are shown in the table below.
Two taps are provided on the right hand side of the gas control for a test
gauge connection to measure the inlet and outlet pressures.
The fireplace and its individual shut-off valve must be disconnected from the
gas supply piping system during any pressure testing of the system at test
pressures in excess of 6 kPa.
If the fireplace must be isolated from the gas supply piping system by closing
an individual shut-off valve, it must be of the handle-less type.
· Optimum appliance performance requires proper input pressures.
· Pressure requirements are:
Gas Pressure Minimum inlet pressure Maximum inlet pressure Manifold pressure
Natural Gas 1.13 KPa 3.40 KPa .87 KPa
Propane 2.75 KPa 3.40 KPa 2.49 KPa
ULPG 2.75 KPa 3.40 KPa 2.49 KPa
C. Gas Service Access
Note: This appliance does include a manual gas shutoff valve that is located
in the valve compartment. This manual gas shutoff valve is accessible for
service by removing the decorative front. The valve is most accessible if it
is located forward in the control cavity of the appliance. Depending upon
local code, an additional manual gas shutoff, in a readily accessible area may
be required and located upstream from the appliance.
D. Gas Connection
Note: Have the gas supply line installed in accordance with local building
codes by a qualified installer approved and/or licensed as required by the
locality.
Note: Before the first firing of the appliance, the gas supply line should be
purged of any trapped air.
Note: Consult local building regulations to properly size the gas supply line
leading to the (Rp 1/2 in.) hook-up at the unit.
Incoming gas line should be piped into the valve compartment and connected to
the ISO 7-Rp 1/2 (BSP Rp 1/2) threaded gas inlet connection on the manual
shutoff valve.
IMPORTANT NOTICE: (Items 1, 2 and 3 applies to ALL Heat & Glo gas appliances)
- 1/2 in. GAS LINE: Run through cavity 70 mm
above finished hearth level, NOT RIGID, NOT CLIPPED, with minimum 500 mm into cavity and 120 mm back from plaster face. 2. PVC (COMPOSITE) GASLINE must terminate minimum 500 mm short of gas heater. Copper pipe MUST be the final connection to the gas heater. 3. ISOLATING SWITCH: Location within 1 metre of fireplace, subject to mantelpiece etc. Check to ensure it remains clear of any mantelpiece installation.
Leak test all gas line points and the gas control valve prior to and after starting the gas appliance.
WARNING! Risk of Fire or Explosion! High pressure will damage valve. Low
pressure could cause explosion. · Elongated pressure taps are recommended for
gas
pressure testing on these models.
· Verify inlet pressures. Verify minimum pressures when other household gas
appliances are operating.
· Install regulator upstream of valve if line pressure is greater than 3.40
KPa.
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 57
· Refer to Section 3 for location of gas line access in appliance.
· The bottom surround for this appliance may be removed to gain access to the
control cavity for ease of access during the gas connection process. See
Figure 9.1.
· Gas line may be run through knockout(s) provided. · The gap between supply
piping and gas access hole
may be sealed with caulk or aluminum foil tape with a minimum of 300 ºF
continuous exposure rating or stuffed with non-combustible, unfaced insulation
to prevent cold air infiltration. · Ensure that gas line does not come in
contact with outer wrap of the appliance. Follow local codes. · Pipe incoming
gas line into valve compartment. · Connect incoming gas line to the 1/2 in.
(13 mm) NPT connection on manual shutoff valve. WARNING! Risk of Fire or
Explosion! Support control when attaching pipe to prevent bending gas line.
WARNING! Risk of Fire or Explosion! Gas build-up during line purge could
ignite. · A small amount of air will be in the gas supply lines. · Ensure
adequate ventilation. · Ensure there are no ignition sources such as sparks or
open flames. Light the appliance. It will take a short time for air to purge
from lines. When purging is complete the appliance will light and operate
normally. WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings
and connections with a non-corrosive commercially available leak-check
solution. DO NOT use open flame. Fittings and connections could have loosened
during shipping and handling.
GAS CONNECTION AND SERVICE ACCESS
E. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not
apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 ft. (610 m) elevation:
Reduce input rate 4% for each 1000 ft. (305 m) above 2000 ft. (610 m).
F. Air Shutter Setting
WARNING! Risk of Explosion or Delayed Ignition! Improperly adjusted air
shutter could cause soot buildup. CAUTION! Risk of Burns! Components are HOT!
Wear protective gloves when adjusting shutter. NOTICE: If sooting occurs,
provide more air by opening the air shutter. Air shutter settings should be
adjusted by a qualified service technician at the time of installation. The
air shutter is set at the factory for a typical minimum vent run which
consists of enough horizontal to vent pipe terminate through a 2×6 (51×152 mm)
wall:
Top Vented with one 90 degree elbow and DVP-TRAP2 termination cap for Natural
Gas or Rear Vented with the DVP-TRAP2 termination cap. It may need to be
adjusted for other venting scenarios up to full open.
Adjust air shutter for different vent runs. See Figure 9.2.
· Loosen the wing nut.
· Move the air handle to the right to open the air shutter.
· Move the air handle to the left to close the air shutter.
· Tighten the wing nut.
Shutter Setting Verification / Flame Appearance · After 15 minutes, the flames
will be a yellow/blue mix.
The front flames may be blue at this time. · After 30 minutes, the flames
should be yellow with
some blue flames near the burner ports. · After 1 hour, the flame will be at
its maximum maturity.
NOTICE: Flames should not appear orange or stretch to the top refractory/ top
of firebox. If flames are dark orange with dark, smoky tips, provide more
primary air to the burner by opening the air shutter accordingly.
Figure 9.1 Bottom Surround Removal
58
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
AIR SHUTTER WING NUT
G. Service/Replace Appliance Gas Valve
· See Figure 9.3. · Remove decorative barrier front, glass, logs, base
pan assembly, burner assembly and valve plate assembly. See Figure 9.3. ·
Perform service or replace gas valve. · Reinstall valve plate assembly, burner
assembly, basepan assembly, logs and appliance glass and front.
VALVE PLATE ASSEMBLY
Figure 9.2 Air Shutter
Air Shutter Settings
MODEL 6KX-AU
GAS TYPE
Natural Propane
ULPG
SHUTTER SETTING
Min Vent Run *Max Vent Run
5/8 in. (16 mm) Full Open
3/4 in. (19 mm) Full Open
Full Open
Full Open
- As tested 3 ft. (914 mm) out of rear vent, 90 degree verticle elbow, 2 ft. (610 mm) horizontal, 90 degree horizontal elbow, 1 ft. (309 mm) horizontal and a DVP-TRAP2 termination cap.
FULL VALVE ACCESS
TO REMOVE BOTTOM SURROUND: FLATTEN TABS PUSH BACK AND OUT
TABS
Figure 9.3 Gas Valve Access
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 59
10 Finishing
A. Facing Material
WARNING
Risk of Fire! DO NOT apply combustible materials beyond the minimum
clearances. Comply with all minimum clearances to combustibles as specified in
this manual. Materials overlapping into non-combustible zones could ignite and
will interfere with air flow through decorative barrier fronts. · Metal front
of appliance may be covered with non-
combustible materials only.
· Facing and/or finishing materials must not interfere with air flow through
decorative barrier fronts, removal of decorative barrier fronts or access for
service.
· Facing and/or finishing materials must never overhang into the glass
opening.
· Observe all clearances when applying combustible materials.
· Seal gaps between the finished wall and appliance top and sides using a 300
ºF (149 ºC) minimum sealant. Refer to Figure 10.1 and Figure 10.2.
· Finishing materials must be installed with no gaps in order to prevent the
escape of heat between the finishing material and the wall. See Figure 10.2.
NOTICE: Surface temperatures around the appliance will become warm while the
appliance is in operation. Ensure finishing materials used for all surfaces
(floor, walls, mantels, etc.) will withstand temperatures up to 190° F (88°
F).
WARNING! Risk of Overheating! DO NOT allow gap between finishing materials and
front of appliance.
DRYWALL OR WALL SHEATHING MATERIAL
NON-COMBUSTIBLE FINISHING MATERIAL
FACTORY-INSTALLED NON-COMBUSTIBLE BOARD
0 IN.
FACING MATERIAL UP TO 1/2 in (13 mm) THICK MAY BE COMBUSTIBLE – TOP AND SIDES
B
FACTORY-INSTALLED NON-COMBUSTIBLE BOARD DO NOT REMOVE
A
___ IN.
0 IN.
HIGH TEMPERATURE (300 ºF/ 149 ºC MIN.) TOP AND SIDE SEAL JOINT
REMOVEABLE SURROUND (SHADED AREA) MAY BE COVERED WITH COMBUSTIBLE OR NON-
COMBUSTIBLE MATERIAL
6KX-AU
inches millimeters
A 40-7/8 1038
0 IN.
B 41 1041
Figure 10.2 Non-combustible Facing Diagram
WARNING! Risk of Overheating! DO NOT install combustible or non-combustible flooring or hearth material above top of bottom surround. Gap between bottom of decorative front and top of bottom surround must be maintained for proper air flow.
FLOORING OR HEARTH MATERIAL NOT ALLOWED ABOVE TOP OF BOTTOM SURROUND
DECORATIVE BARRIER FRONT
NO GAP ALLOWED
REQUIRED AIR FLOW GAP
Flooring & Hearth Material (1-1/8 IN. MAX.)
(29 mm)
Figure 10.3 Required Air Flow Gap
Figure 10.1 Finishing Material Installed
60
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
B. Installing a Television
If installing a television (TV) above the appliance, see Section 2.B.
C. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clearances as specified. Mantel
MUST be fastened to wall with no gaps. · Framing closer than the minimums
listed must be
constructed entirely of non-combustible materials (i.e., steel studs, concrete
board, etc.). · No gaps allowed between the wall and the bottom of the mantel.
· Combustible mantel legs and wall projections may be applied over the non-
combustible board supplied with the appliance. Follow guidelines as shown in
the figures below for mantels, mantel legs and wall projections.
Note: Measurement is taken from top/side of the opening, NOT the top/side of
the appliance.
Combustible Mantels
Note: All measurements in millimeters.
TO CEILING 457
305
279
254
813
229
203
635
178 152 127 102 76
483 457 432
406 381
356 330
305
64
279
254
127
Measurement from fireplace opening to bottom of appliance: = 33-1/2 in. (851
mm) (6KX-AU)
Note: Measurement is taken from top of the opening, NOT the top of the
appliance.
Figure 10.3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles
or Painted Surfaces
Combustible Mantels – Passive Heat Installed
Note: All measurements in millimeters.
TO CEILING
459
432
1270
406
381
305
356 330
279 254
305
229
64
203
178 152 127
Measurement from fireplace opening to bottom of appliance: = 33-1/2 IN. (851
mm)
Note: Measurement is taken from top of the opening, NOT the top of the
fireplace.
Figure 10.4 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles
– Passive Heat Kit Installed
Non-Combustible Mantels
TO CEILING
457
305 279
254 229 208 178
813
635 483
457 432
406 381
356
152
Measurement from fireplace opening to bottom of appliance: = 33-1/2 in (851
mm) (6KX-AU)
Note: Measurement is taken from top of the opening, NOT the top of the
appliance.
Figure 10.5 Minimum Vertical and Maximum Horizontal Dimensions of Non-
Combustibles
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 61
Non-Combustible Mantels – Passive Heat Installed
Note: All measurements in millimeters.
TO CEILING
457 432 406 381
356 330 305
1270
305 279 254
229
203
152
178
152
Measurement from fireplace opening to bottom of appliance: = 33-1/2 IN (851
mm). (6KX-AU)
Note: Measurement is taken from top of the opening,
Figure 10.6 Minimum Vertical and Maximum Horizontal Dimensions of Non-
Combustibles – Passive Heat Kit Installed
Combustible Mantel Legs or Wall Projections
TOP VIEW
INTERIOR WALL
FIREPLACE OPENING
A
B
MANTEL LEG OR WALL PROJECTIONS
If A minimum is __, then B maximum is___.
A Inches 2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
Millimeters 62
87 113 138 164 189
Inches
1
2
3
4
5
B
Millimeters 25
51
76 102 127
Figure 10.7 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)
Non-Combustible Mantel Legs or Wall Projections
TOP VIEW
INTERIOR WALL
FIREPLACE OPENING
6 IN. (152 mm)
B
A
MANTEL LEG OR WALL PROJECTIONS
If A minimum is __, then B maximum is___.
Inches
A Millimeters Inches
B Millimeters
0-7-7/16 0-189 6 152
7-7/16 189
Figure 10.8 Non-Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)
62
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Finishing Material Installed with Passive Heat Optional Heat Management System
= COMBUSTIBLE MATERIAL ALLOWED OPEN TOP DISCHARGE
2 IN. MIN.*
(51 mm)
DO NOT INSTALL FINISHING MATERIAL ON THIS SURFACE.
2 IN. (51 mm) MIN. OPENING MUST NOT BE BLOCKED
CEILING
FRONT DISCHARGE
2 IN. MIN.*
(51 mm)
DO NOT INSTALL FINISHING MATERIAL ON THIS SURFACE.
2 IN. (51 mm) MIN. OPENING MUST NOT BE BLOCKED
CEILING
- = Mesh screen required for front discharge or open top discharge passive heat installations with
discharge opening of 3 in. (76 mm) or greater.
SIDE DISCHARGE (DISCHARGE SLOTS ON BOTH SIDES OF APPLIANCE)
CEILING
8-3/4 IN. (222 mm)
REGISTER COVER SLOTS FACE FRONT OF APPLIANCE
12-1/4 IN. (311 mm)
Figure 10.9 Finishing Material installed with Passive Heat Optional Heat Management System Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 63
D. Hearth Extension
A hearth extension is not required with these models. Refer to Section 3 for
clearances and information regarding vinyl flooring restrictions.
E. Decorative Barrier Front Dimensions for Finishing
Only decorative barrier fronts certified for use with this appliance model may
be used. Contact your dealer for a list of decorative barrier fronts that may
be used.
Decorative Barrier Front Fit Types
· Inside Fit as shown in Figure 10.10. Decorative barrier front fits inside
appliance opening.
· Overlap fit as shown in Figure 10.11. Decorative barrier front is installed
on top of finishing material.
THE GUARD IS FITTED TO THIS APPLIANCE TO REDUCE THE RISK OF FIRE OR INJURY
FROM BURNS AND NO PART OF IT SHOULD PERMANENTLY BE REMOVED. FOR PROTECTION OF
YOUNG CHILDREN OR THE INFIRM, A SECONDARY GUARD IS REQUIRED.
NON-COMBUSTIBLE FINISHING MATERIAL 6 IN. (152 mm) MAX.
THICKNESS
NON-COMBUSTIBLE FINISHING MATERIAL 6 IN. (152 mm) MAX.
THICKNESS
DECORATIVE BARRIER FRONT
Y
X
(Includes 1/8 in. (3 mm) opening each side of door)
Non-Combustible Finishing material between 1 in. (25 mm)and 6 in. (152 mm)
thick.
Figure 10.10 Inside Fit Decorative Barrier Front
FRONT FACE OF FIREPLACE
DECORATIVE BARRIER FRONT
1 in. (25 mm) MAX NON-COMBUSTIBLE FINISHING MATERIAL
(TOP EDGE)
Finishing materials 1 in. maximum thick. Stop finishing material flush with opening.
Figure 10.11 Overlap Fit Decorative Barrier Front
64
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
1. A Overlap Fit Method with Overlap Fit Front FINISHING STRIPS NOT REQUIRED Non-combustible Finishing Material Thickness: 1 Inch (25 mm) Thick or Less
DECORATIVE BARRIER FRONT
LOFT
FORGE CHAPEL
FIT OPTION
Overlap Overlap Overlap
1. B Inside Fit Method with Inside Fit Front
FINISHING STRIPS NOT REQUIRED Non-Combustible Finishing Material Thickness:
0-6 Inches (0-152 mm) Maximum
DECORATIVE BARRIER FRONT
FOLIO
FIT OPTION Inside
NON-COMBUSTIBLE FINISHING MATERIAL
NON-COMBUSTIBLE FINISHING MATERIAL
DECORATIVE BARRIER FRONT
1 in. (25 mm) MAX. NON-COMBUSTIBLE FINISHING MATERIAL
(TOP EDGE)
Non-Combustible Finishing materials 1 in. (25 mm) maximum thickness. Stop finishing material flush with appliance opening.
Figure 10.12 Non-Combustible Finishing Material 1 In. (25 mm) Thick or Less – Overlap Fit Fronts
DECORATIVE FRONT
NON-COMBUSTIBLE
NON-COMBUSTIBLE
FINISHING MATERIAL
FINISHING MATERIAL
Non-Combustible Finishing materials 6 in. (152 mm) maximum thickness. Stop
finishing material flush with appliance opening.
Figure 10.13 Inside Fit Method
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 65
2.A Inside Fit Method with Overlap Fit Front FINISHING STRIPS REQUIRED Non-
Combustible Finishing Material Thickness: 1-6 Inches (25 mm-152 mm) Maximum
Finishing strips will add the proper clearances for the installation of the
front.
DECORATIVE BARRIER FRONT
LOFT FORGE CHAPEL
FIT OPTION
Inside Inside Inside
Install and Remove Finishing Strips 1. Align finishing strip with the two pre-
drilled holes on
the appliance top and sides as shown in Figure 10.15. 2. Install screws to
attach finishing strips. 3. To remove the finishing strips, remove screws.
Finishing strips will add the proper clearances for the installation of the
front. NOTICE: Remove finishing strips before firing appliance. Remove glass
assembly to access finishing strip screws.
FINISHING STRIPS
NON-COMBUSTIBLE FINISHING MATERIAL
FINISHING STRIPS
FINISHING STRIP ALIGNS WITH HOLES
FINISHING STRIP ALIGNMENT DETAIL
NON-COMBUSTIBLE FINISHING MATERIAL
NON-COMBUSTIBLE FINISHING MATERIAL
DECORATIVE FRONT
Figure 10.14 Non-Combustible Finishing Material Thickness Greater Than One
Inch – Finishing Strips Required
Figure 10.15 Install Finishing Strips
66
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Good Faith TV Guidelines
Good Faith Guidelines for TV Installations Above a Fireplace with Passive Heat
Option
WARNING! Risk of Fire! Wire mesh required on bottom of discharge opening when
discharge opening is greater than 3 inches (76 mm). Secure wire mesh to top of
framing.
1-1/2 IN. (38 mm) (2 X 4 FRAMING) (90 x 35 mm for AU)
ROOM CEILING
2 IN. (51 mm)MIN.
4 IN. MIN. (102 mm)
1/2 IN. X 1/2 IN. (13 mm x 13 mm)
WIRE MESH*
41 IN. MIN. (1041 mm) (MINIMUM CLEARANCE TO
DISCHARGE OPENING)
TV
2 X 4 FRAMING (90 x 35 mm for AU)
2 X 4 OR 2 X 6 (90 x 35 mm for AU)
FRAMING
CHASE CEILING REQUIRED WITHIN 3 IN. (76 mm) OF TOP OF OPENING
WIRE MESH*
= PASSIVE HEAT DISCHARGE OPENING
76 IN. MIN. (1930 mm) (Appliance may be installed off of floor)
FIREPLACE OPENING
83-1/2 IN. (2121 mm) MIN. (Appliance may be installed off of floor)
12 IN. MIN. (305 mm)
Measurement from top edge of opening to bottom of
appliance = 33-1/2 IN. (851 mm)
- Wire mesh required for front discharge or open top discharge passive heat installations with discharge
opening of three inches (76 mm) or greater. NOTE: The TV installation requirements are the same regardless of whether the Passive Heat kit is installed with a
top discharge, side discharge or open top discharge.
Figure 10.16 Good Faith Guidelines for TV Installations Above a Fireplace with Passive Heat Option
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 67
11 Appliance Setup
A. Remove the Shipping Materials
WARNING! Risk of Fire! Close the ball valve before installing the splatter
guard to prevent accidental lighting. Remove the splatter guard before
lighting the appliance. Remove shipping materials from inside or underneath
the firebox. · The splatter guard is a piece of corrugated material
used to protect the appliance during the installation process before finishing
work on the whole hearth is complete. Splatter guards may be factory installed
or accompany the decorative barrier front of the appliance, depending on the
fireplace model. Splatter guards must be removed before appliance is fired.
B. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated inside the firebox or
underneath in the control cavity.
C. Install the Black Glass Refractory
SIDE REFRACTORY BRACKET
(Assembly breaks into two pieces)
KIT COMPONENTS (1) Glass Refractory Assembly (Back, Left, Right) (1) Side
Refractory Bracket Assembly (See Figure 1) (1) Back Insulation Board (2) Side
Insulation Board (1) Back Refractory Support (See Figure 2) (1) Base
Refractory (1) Top Refractory Panel
REQUIRED TOOLS · Screw gun equipped with 1/4 in (6 mm) socket · 1/4 in. (6 mm)
wrench
Installation Instructions
1. Remove decorative front, appliance glass assembly and logs, if installed.
2. Locate back refractory support, included in manual bag assembly shipped
with the kit. Remove LED covers from refractory support by bending as shown in
Figure 2. Discard LED covers.
3. Bend two tabs on back refractory support as shown in Figure 2. Bend at
perforation and remove.
BEND ALL TABS 90 DEGREES 36 INCH MODELS: 7
36 INCH MODELS: BEND AT PERFORATION AND REMOVE
Figure 1 Side Refractory Bracket
Figure 2 Back Refractory Support
68
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
5. Place back refractory support on back air passage return bend, align holes and install with one screw as shown in Figure 3 and Figure 4.
7. Install the back glass panel in front of the insulation board and bend/secure the tabs on the back refractory support.
Figure 3 Install Back Refractory Support
BACK REFRACTORY PANEL
REFRACTORY SUPPORT
REFRACTORY SUPPORT
INSTALL SCREW
Figure 6 Back Glass Panel Installed
8. Hold rear glass panel in place and slide one side insulation board into
position as shown in Figure 7.
Figure 4 Back Refractory Support Installed
6. Install back insulation board by positioning it at the rear of the firebox
and behind the refractory support tabs as shown in Figure 5.
BACK REFRACTORY SUPPORT
Figure 7 Rear Glass Panel and Side Insulation Board Installed
Figure 5 Back Insulation Board Installed Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 69
9. Install side glass panel in front of insulation board as shown in Figure
8.
10. Bend the side refractory bracket tab down as shown in Figure 9, labeled
Bend 1. Place the side refractory bracket into position. Put the top in first
and orient it as shown in Figure 8.
11. Install side refractory bracket between the insulation board and the side
of the firebox. Position the side refractory bracket, insulation board and
side glass panel upright against the inside wall of the firebox as shown in
Figure 8. Secure side refractory bracket with one self-tapping screw as shown
in Figure 9. Bend side refractory bracket tab over glass panel as shown in
Figure 10, labeled Bend 2. Refractory bracket is shown installed, with the tab
bent correctly, in Figure 11.
All Refractory Kits:
NOTICE: Refractory bracket is positioned so that the edge of the white
insulation board is completely covered.
NOTICE: Ensure the side glass and insulation board are positioned flush
against the firebox to allow the base refractory to fit properly.
12. Install side insulation board on opposite side and repeat steps 8-11 for
other side.
SIDE GLASS (BLACK)
SIDE REFRACTORY BRACKET
INSULATION BOARD (WHITE)
SCREW
Note: This figure is intended solely to illustrate the location of bracket.
The insulation board and glass panel are installed prior to the installation
of the side refractory bracket.
Figure 9 Side Refractory Bracket in Position
BEND 1
BEND 2
Figure 10 Bend Side Refractory Bracket Tabs
REFRACTORY SUPPORT INSTALLED
Figure 8 Install Side Refractory Bracket with Side Insulation Board and Side Glass Panel
70
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
TAB DOWN
SCREW
Figure 11 Install Side Glass Refractory Bracket
13. Install top refractory panel. Rest it on top of the side glass panels and
gently push to the back of firebox until it rests on back refractory panel.
See Figure 12.
BASE REFRACTORIES
TOP REFRACTORY
Figure 13 Type 2 Base Refractory Installed (Two Piece Model)
15. Reinstall logs using log placement instructions in appliance installation
manual.
16. Reinstall appliance glass assembly using instructions in appliance
installation manual.
17. Install decorative front according to instructions included with
decorative front.
Figure 12 Top Refractory Installed
14. Set new base refractory pieces in place as shown Figure 13.
2581-937
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 71
D. Install the Burner Overlay
1. Locate the burner overlay shipped inside the firebox. 2. Remove the burner
overlay from the packaging.
Check to ensure all ports are free from any obstructions. See Figure 11.1. 3.
To install the burner overlay, mate the locating holes with the guide sleeves.
Install fiber burner top so that it makes full contact with the underlying
burner assembly. See Figure 11.2. 4. Ensure that the ports in the steel burner
are visible through the holes in the fiber burner top.
BURNER OVERLAY
BURNER OVERLAY
LOCATING HOLES
BURNER ASSEMBLY
GUIDE SLEEVES FOR BURNER OVERLAY
DETAIL
BLOCKED PORT
PARTIALLY BLOCKED PORT
OPEN PORT
Figure 11.1 Check Burner Ports
BURNER OVERLAY
Figure 11.2 Burner Overlay Installed
72
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
E. Illuminated Embers Illuminated Embers Placement
1. Pour illuminated embers between the left and right base refractories as
shown in Figure 11.3.
ILLUMINATED EMBERS
Figure 11.3 Illuminated Embers Installed
F. Install Base Refractory and Burner Media/Embers
Install Base Refractory
Install base refractory into firebox. Base refractory will fit around burner.
The front edge of the refractory is positioned flush with the firebox return
bend.
Install Burner Media/Embers WARNING! Risk of Explosion! Follow ember placement
instructions in manual. DO NOT completely block burner ports with ember
material. Replace ember material annually. Improperly placed embers interfere
with proper burner operation. Ember material is shipped with this gas
appliance. To place the ember material:
· Embers CANNOT completely block burner ports. Care should be taken not to
block the lighting trail of ports.
· Embers may only be placed in areas as shown in Figure 11.4.
· Save the remaining ember materials for use during appliance servicing. The
embers provided should be enough for 3 to 5 applications.
Apply embers here for smooth lighting characteristics.
Figure 11.4 Burner Media / Ember Placement
= NO EMBERS
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 73
G. Install the Log Assembly
CAUTION: Logs are fragile, handle with care.
NOTICE: To simplify the installation process, positively identify each
individual log before beginning installation. See Figure 1. Key log location
features are shown in Figure 2.
Log Assembly: LOGS-6KX
LOG 1 POSITIONING LEDGE
LOG STOP
LOG PIN
1
2 3 456
Figure 1. Log Identification – LOGS-6KX
Figure 2 Log Location Features
Log #1: Position Log #1 along the log positioning ledge referenced in Figure
2. Slide Log #1 back until it contacts the log stop.
Log #2: Position the right end of Log #2 against the log pin as shown in
Figure 4. Refer to Figure 2 for log pin location. Position the bottom side of
the log on the log shelf and place it just behind the log shelf return bend.
The back side of the log will touch the back refractory, if installed. Set the
left end of the log on the flat area of Log #1 shown in Figure 3.
FLAT AREA FOR LOG 5
FLAT AREA FOR LOG 2 LOG STOP
ALIGN LOG #3 WITH EDGE OF BURNED OUT AREA FLAT AREA FOR LOG 3
1
2
LOG SHELF RETURN BEND LOG PIN
1
Figure 3 Place Log #1
Figure 4 Place Log #2
74
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
Log #3:
Set the top of Log #3 on the flat spot of Log #2. The bottom corner of the top
of Log #3 will overhang Log #2 as shown in Figure 6. The bottom right edge of
Log #3 will touch the back refractory, if installed, as noted in Figure 5.
Appliances without refractory will have a one inch gap between the bottom
right edge of Log #3 and the side wall of the firebox.
3 2
1/2 IN.
BOTTOM RIGHT EDGE OF LOG #3 CONTACTS REFRACTORY NO REFRACTORY = 1 IN. GAP
3 2
Figure 5 Place Log #3 (LOGS-6K / LOGS6KX / LOGS-6-BIR)
Figure 6 Log #3 Placement in Relation to Log #2
Log #4: Position Log #4 on the flat area of the fiber burner overlay noted in Figure 8. Slide Log #4 so the notch, shown in Figure 9, mates with the “bump” detail. The back edge of Log #4 rests against the log placement edge on the fiber overlay. The flat area for Log #4 must be kept parallel to the burner overlay. See Figure 7.
FLAT AREA FOR LOG 6 PARALLEL TO BURNER FLAT AREA FOR LOG 5
4
MATE NOTCH ON LOG 6 WITH BUMP DETAIL ON FIBER BURNER OVERLAY
Figure 7 Install Log #4
FLAT AREA FOR LOG 4 LOG PLACEMENT EDGE
Figure 8 Log Placement Details
BUMP DETAIL
NOTCH
4
Figure 9 Bottom View of Log #4 Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 75
Log #5:
LOGS-6KX : Place the large end of Log #5 on the flat area of Log #1,
highlighted in Figure 3. The other end rests on the flat area of Log #4 as
referenced in Figure 7. The edge of the large end of Log #5 should be flush
with the back edge of Log #1 as shown in Figure 10.
Log #6: Position Log #6 on the flat area of Log #4, which is highlighted in
Figure 7. The top left corner of Log #6 will overhang the side of Log #4 by
1/2 inch. The bottom corner of Log #6 will be flush with the front of the
firebox opening as noted in Figure 12.
EDGE OF LOG 1 FLUSH WITH EDGE OF LOG 5
3
5
1 4
5 4
1/2 INCH
4 4
6
FIREBOX OPENING
Figure 11 Install Log #6
Figure 10 Install Log #5
2 5
1
4
3 6
Service Parts List
Log # 1 2 3 4 5 6
PART NUMBER SRV2582-700 SRV2582-701 SRV2582-702 SRV2582-703 SRV2582-704 SRV2582-705
Figure 12 Log Set Installed
76
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
H. Fixed Glass Assembly Removal and Replacement
WARNING! Risk of Asphyxiation! Handle fixed glass assembly with care. Inspect
the gasket to ensure it is undamaged and inspect the glass for cracks, chips
or scratches. · DO NOT strike, slam or scratch glass. · DO NOT operate
fireplace with glass removed, cracked,
broken or scratched. · Replace as a complete assembly.
Removing Fixed Glass Assembly
· Pull the four glass assembly latches away from the tabs on the glass frame.
Remove glass assembly from the appliance. See Figure 11.5.
Replacing Fixed Glass Assembly
· Replace the glass assembly on the appliance. Hold glass in place with one
hand. Use the other hand to pull out and latch the four glass assembly latches
onto the glass frame tabs.
· Inspect and operate all glass latches to ensure they move freely and no
obstructions are present.
· Reinstall decorative barrier front.
I. Install Decorative Barrier Front
WARNING! Risk of Fire! Install ONLY decorative barrier fronts approved by
Hearth & Home Technologies. Unapproved decorative barrier fronts could cause
fireplace to overheat.
IMPORTANT! This fireplace requires an installed decorative barrier front to
prevent direct contact with the hot viewing glass. DO NOT operate the
fireplace with the barrier removed. Contact your dealer or Hearth & Home
Technologies if the barrier is not present or help is needed to properly
install one.
For more information refer to the instructions supplied with your decorative
barrier front.
GLASS FRAME TABS
LATCHES (BOTH BOTTOM
AND TOP)
Figure 11.5 Fixed Glass Assembly
GLASS ASSEMBLY
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 77
12 Reference Materials
A. Vent Components Diagrams
Effective Height/Length
DVP Pipe (see chart)
Pipe
DVP4 DVP6 DVP12 DVP24 DVP36 DVP48 DVP6A DVP12A
Effective Length
Inches Millimeters
4
102
6
152
12
305
24
610
36
914
48
1219
3 to 6 76 to 152
3 to 12 76 to 305
10-1/2 in.
(267 mm)
45 °
4-7/8 in. (124 mm)
10-7/8 in. (276 mm)
DVP45 (45º Elbow)
20-3/4 in. (527 mm)
Tab=1 in. (25.4 mm)
Finished Height: 19-3/4 in./502 mm UNIV-AS2 (Attic Insulation Shield)
10 in. (254 mm)
10 in. (254 mm)
1 in. (25 mm)
10 in. (254 mm)
UP
5 in. (127 mm)
1- 1/2 in. (38 mm)
DVP-FS (Ceiling Firestop)
12 in. (305 mm)
11-3/8 in. (289 mm)
7-3/8 in. (187 mm)
9-1/4 in. (235 mm)
13-1/4 in. (337 mm)
1-1/4 in. (32 mm)
1/2 in. TYP (13 mm)
DVP90ST (90° Elbow)
DVP-HVS (Vent Support)
14 IN. (356 MM)
20 IN. (508 MM)
14 in. (356 mm)
12 in. (305 mm)
1 in. (25 mm)
8 in. (203 mm)
14 IN. (356 MM)
12 IN.
DVP-RDS
(305 MM)
ROOF DECK INSULATION SHIELD
6 in. (152 mm)
DVP-WS (Wall Shield Firestop)
Figure 12.1 DVP Vent Components
78
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
A. Vent Components Diagrams (continued)
overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.
12 in. (305 mm)
8 in. (203 mm)
15-1/8 in. (384 mm)
*5 in. (127 mm)
Heat Shield
- Center of the horizontal vent pipe to the vertical measuring surface.
DVP-TRAP Horizontal Termination Cap
Max Effective Length
Term Cap Trap1 Trap2
Minimum Effective Length
3-1/8 in. 79 mm 5-3/8 in. 137 mm
Maximum Effective Length
4-5/8 in. 117 mm 9-3/8 in. 238 mm
DVP-TRAP2
Figure 12.2 DVP Vent Components Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 79
A. Vent Components Diagrams (continued)
13-1/4 in. (337 mm)
24-5/8 in. (625 mm)
31 in. (787 mm)
24-5/8 in. (625 mm)
27-1/2 in. (699 mm)
RF6 Roof Flashing
RF12 Roof Flashing
13-1/4 in. (337 mm)
7 IN. (178 mm)
7 IN. (178 mm)
11-7/8 in. (302 mm)
5 in. (127 mm)
A
A
A
4-15/16 IN. (125 mm)
13-7/8 in. (352 mm)
12 IN. (305 mm)
7/8 IN. (22 mm)
TRAP-VSS Vinyl Siding Shield
1/2 IN. (13 mm)
DVP-BEK2 DVP-HPC Cap Brick Extension
DVP-TRAPFL Flashing
26 in. 660 mm
DVP-HSM-B Extended Heat Shield
Figure 12.3 DVP Vent Components
80
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
A. Vent Components Diagrams (continued)
12 in. 305 mm
7-1/4 in. (184 mm) 5-1/4 in. (133 mm)
12-1/2 in. (318 mm)
DVP-TVHW Vertical Termination Cap (Highwind)
Figure 12.4 DVP Vent Components
DECORATIVE TERMINATIONS/SHROUDS
Only use listed decorative termination caps/shrouds with Hearth & Home
Technologies approved venting systems. This applies to both DVP and SLP
venting systems.
Decorative Terminations Caps/Shrouds
DTO134
LDS33
DTO146
LDS46
DTS134
LDS-BV
DTS146
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 81
Top View
6-1/4 IN. 159 mm
14 IN. 356 mm
Front View 15-1/2 IN. 394 mm
11-1/2 IN. 292 mm
1-1/2 IN. 38 mm
Side View
2-1/4 IN. 57 mm
8 IN. 203 mm
4-3/4 IN. 121 mm
9-1/2 IN. 241 mm
4-3/8 IN. 112 mm
10 IN. 254 mm
5-1/4 IN. 135 mm
2-1/4 IN. 57 mm
PVLP-SLP-AU Power Vent Low Profile
PVLP-HS Heat Shield
PVLP-BEK Brick Kit
Note: Wire harnesses required to power the PVLP-SLP-AU connect to the
appliance and are ordered separately from PVLP-SLP-AU. Contact your dealer to
order.
Note: A PVLP-HS heat shield is available and sold separately. Use if the PVLP-
SLP is installed in a high traffic area.
Figure 12.5 PVLP-SLP-AU Vent Components
82
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23
B. Accessories
WARNING! Risk of Fire and Electric Shock! Use ONLY Hearth & Home Technologies-
approved optional accessories with this appliance. Using non-listed
accessories could result in a safety hazard and will void the warranty.
Contact your dealer for more information and details, such as color options
and specific quantities required, on individual accessories. A qualified
service technician must install the approved accessories. Operate installed
accessories according to the included instructions.
Note: Some optional accessories must be installed at the time of appliance
installation. See Section 2.A.
WARNING! Risk of Fire and Electric Shock! Use ONLY Hearth & Home Technologies-
approved optional accessories with this appliance. Using non-listed
accessories could result in a safety hazard and will void the warranty.
Contact your dealer for more information and details, such as color options
and specific quantities required, on individual accessories. A qualified
service technician must install the approved accessories. Operate installed
accessories according to the included instructions.
Note: Some optional accessories must be installed at the time of appliance
installation. See Section 2.A.
Options:
Refractory Kit
BRICK-6KX-(TG/CU/SJ) GL-36KX, GL-42KX
Brick Refractory Black Glass Liner
Heat Management Systems Kits
HEAT-ZONE-240V HZMR-ADP PH-MR PH-SIDETRIM PH-FRTTRIM-36
Heat-Zone-Gas Heat Zone Adapter Passive Heat-Front, Side or Top Discharge Passive Heat registers for side discharge (requires PH-MR) Passive Heat registers for front discharge (requires PH-MR)
Log Sets
LOGS-6-BIR
Birch Log Set
Heat & Glo, a brand of Hearth & Home Technologies 7571 215th Street West,
Lakeville, MN 55044 www.heatnglo.com
Please contact your Heat & Glo dealer with any questions or concerns. For the
location of your nearest Heat & Glo dealer, please visit www.heatnglo.com.
Printed in U.S.A. – Copyright 2023
Heat & Glo · 6KX-AU Installation Manual · 2589-980 Rev. B · 5/23 83
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>